TROUBLESHOOTING

Continued

WARNING: If you smell gas

Shut off gas supply.

Do not try to light any appliance.

Do not touch any electrical switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

IMPORTANT: Operating heater where impurities in air exist may create odors. Cleaning supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These fumes may mix with combustion air and create odors. These odors will disappear over time.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

Heater produces a clicking/ticking noise

1.

Metal expanding while heating or con-

1.

This is common with most heaters. If

just after burner is lit or shut off

 

tracting while cooling

 

noise is excessive, contact qualified ser-

 

 

 

 

vice person

 

 

 

 

 

Heater produces unwanted odors

1.

Heater burning vapors from paint, hair

1.

Open window and ventilate room. Stop

 

 

spray, glues, cleaners, chemicals, new

 

using odor causing products while heater

 

 

carpet, etc. (See IMPORTANT state-

 

is running

 

 

ment above)

 

 

 

2.

Gas leak. See Warning statement at

2.

Locate and correct all leaks (see Check-

 

 

top of page

 

ing Gas Connections, page 15)

 

 

 

 

 

Heater shuts off in use (ODS operates)

1.

Not enough fresh air is available

1.

Open window and/or door for ventilation

 

2.

Low line pressure

2.

Contact local natural gas company

 

3.

ODS/pilot is partially clogged

3.

Clean ODS/pilot (see Cleaning and

 

 

 

 

Maintenance, page 21)

 

 

 

 

 

Gas odor even when control knob is in OFF

1.

Gas leak. See Warning statement at

1.

Locate and correct all leaks (see Check-

position

 

top of page

 

ing Gas Connections, page 15)

 

2.

Control valve defective

2.

Replace control valve

 

 

 

 

 

Gas odor during combustion

1.

Foreign matter between control valve

1.

Take apart gas tubing and remove for-

 

 

and burner

 

eign matter

 

2.

Gas leak. See Warning statement at

2.

Locate and correct all leaks (see Check-

 

 

top of page

 

ing Gas Connections, page 15)

www.desatech.com

For more information, visit www.desatech.com

24

107034

Image 24
Contents VENT-FREE PROPANE/LP GAS What to do if YOU Smell GASSafety Information Compact Classic Hearth FireplaceProduct Features Remote Control AccessoriesLocal Codes UnpackingAssembly Installing LogAssembling Fireplace Assembling HoodAIR for Combustion and Ventilation Providing Adequate VentilationUnusually Tight Construction Confined and Unconfined SpaceAIR for Combustion Ventilation Determining FRESH-AIR Flow for Fireplace LocationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Installation Installation ItemsCheck GAS Type Locating FireplaceBUILT-IN Fireplace Installation Rough Opening for Installing in WallOptional Mantel Installation Mantel Clearances for Built-In InstallationAssembling Brass Trim Brass trim shipped with mantel Installing Blower Accessory GA3400T Installing Blower AssemblyRemoving Upper Louver Assembly For Built-In Installation Extension CordConnecting to GAS Supply Attaching Wood Base to Solid FloorFor attaching base to solid floors concrete or masonry Connecting Fireplace to GAS Supply Installation Items NeededPressure Testing Fireplace Gas Connections Pressure Testing Gas Supply Piping SystemChecking GAS Connections Optional Wireless HAND- Held Remote Control Accessories Installing ReceiverInstalling 9-Volt Battery in Hand- Held Remote Control Unit Wire harness provided in the fireplace hardware packOptional Wall Switch GWMS2 For Your Safety Read Before Lighting Operating FireplaceLighting Instructions Manual Lighting Procedure To Turn OFF GAS To ApplianceOptional Remote Operation GWMS2 Wall Mounted Switch Optional Inspecting BurnersGWMT1 Wall Mounted Thermostat Optional Operating BlowerCleaning and Maintenance Cleaning Burner Injector Holder and Pilot AIR Inlet HoleInspecting Burner Burner Flame PatternTroubleshooting Observed Problem Possible CauseLation requirements Pane/LP gas companyGas odor even when control knob is in OFF Vice personCarpet, etc. See Important state Is running Ment above PositionSpecifications Replacement PartsService Hints Technical ServiceIllustrated Parts Breakdown VMH26PRA4Parts List VMH26PRAAccessories Wall Mounted Switch KIT GWMS2 Cleaning KIT CCKWall Mounted Thermostat KIT GWMT1 Warranty Information International