Desa (V)VC42PE Series Installing GAS Piping to Fireplace Location, Blower Wiring Diagram

Page 18

18

FIREPLACE INSTALLATION Installing Optional Blower Accessory (Cont.) Installing Gas Piping to Fireplace Location

FIREPLACE INSTALLATION

Continued

5.Mount the speed control box against the mounting plate provided in the lower fireplace cavity by placing the plastic control shaft forward through the round hole (see Figure 26, page 17).

6.While supporting speed control, secure control shaft with lock nut by pushing and turning lock nut with pliers clockwise until it is tight against mounting plate. Place control knob provided on shaft (see Figure 26, page 17).

7.Check to make sure that the power cord is completely clear of the blower wheel and that there are no other foreign objects in blower wheel.Also double check all wire leads and make sure wire routing is not pinched or in a precarious position. Correct accordingly.

8.Turn on power to duplex outlet if previously turned off per the warning in column 2, page 16.

9.Plug in blower power cord to duplex outlet.

10.The blower will only run when the speed control knob is in the ON position and the thermal switch senses temperature after the fireplace begins to heat up. The blower speed can be adjusted by rotating the control knob. To turn off, turn knob fully counterclock- wise until it clicks off. If the blower is ON and has been running with the fireplace operating, the blower will continue to run for a short time after the fireplace has been turned off. As the thermal switch cools down, the blower shuts down automatically.

11.Peel off the backing paper and stick the supplied wiring diagram decal on the firebox bottom approximately 12" in front of the blower (see Figure 27, page 17).

Blower Wiring Diagram

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

INSTALLING GAS PIPING TO FIREPLACE LOCATION

WARNING: A qualified service person must con- nect fireplace to gas supply. Follow all local codes.

CAUTION: For propane/LP units, never connect fireplace directly to the propane/LP supply. This heater requires an external regulator (not supplied). Install the external regulator between the fireplace and propane/LP supply.

Installation Items Needed

Before installing fireplace, make sure you have the items listed below.

external regulator (supplied by installer)

piping (check local codes)

sealant (resistant to propane/LP gas)

equipment shutoff valve *

test gauge connection *

sediment trap

tee joint

pipe wrench

approved flexible gas line with gas connector (if allowed by local codes)

*ACSAdesign-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA design-certified equipment shutoff valve from your retailer.

For propane/LPconnection only, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, fireplace regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 31, page 19. Pointing the vent down protects it from freezing rain or sleet.

 

 

Variable

Fan Switch

 

Fan Switch

 

 

 

(N.O.)

 

Off

1

Black

 

2

 

 

 

 

On

 

110/115

 

 

Blue

V.A.C.

Black

 

 

 

 

Blower

 

 

 

 

White

 

Motor

 

Green

 

 

Figure 29 - Blower Wiring Diagram for Thermostat-Controlled Models

External

Propane/LP

Regulator

Supply Tank

Vent

Pointing

Down

Figure 30 - External Regulator with Vent Pointing Down (Propane/LP Only)

www.desatech.com

116237-01C

Image 18
Contents For Your Safety For Your Safety What to do if YOU Smell GASTable of Contents Safety InformationSafety Information Product Identification Local CodesProduct Features PRE-INSTALLATION PreparationLocation and Space Requirements Clearances Framing and FinishingLocation of Termination CAP Termination CAP AIR Supply Inlet GAS MeterVenting Installation Instructions Installation PrecautionsInstallation Planning Horizontal Termination InstallationInstalling Horizontal Vent Cap Noncombustible Exterior Venting Installation Instructions Horizontal Termination ConfigurationsCorner Installation Venting with Two 90 Elbows Installation for Vertical Termination Flat Ceiling InstallationVertical Termination Configurations Vertical V Horizontal H Min Max 12 max 18 max 20 maxHigh Altitude Installation Installing Optional Blower Accessory Venting InstallationFireplace Installation Check GAS Type Desa 5/8 Pipe & Vent KitsFireplace Installation Model BKT InstallationInstalling GAS Piping to Fireplace Location Blower Wiring DiagramInstallation Items Needed Connecting Fireplace to GAS Supply Pressure Testing Gas Supply Piping SystemChecking GAS Connections Pressure Testing Fireplace Gas Connections REMOVING/REPLACING Glass DoorRemoving Louver Panels Installing Lava Rock and Glowing Embers Cleaning Glass DoorRemoving Glass Door Installing Brick Liner Models BL42DASA and BL42DHASA Wall Switch InstallationOptional Remote Control Installation Model WRC Wiring Diagram Operating FireplaceLighting Instructions Optional Remote Operating Optional Blower AccessoryTo Turn OFF GAS To Appliance OperationPilot and Burners Cleaning MaintenanceGlass Door LogsTroubleshooting Observed Problem Possible Cause RemedyGas leak. See Warning statement at Technical Service Replacement PartsService Hints Parts Under WarrantySpecifications Illustrated Parts Breakdown Models VC42NE, VC42PE, VVC42NE and VVC42PEParts List KEY Part Number Description QTY2827 19 18 116237-01C KEY Part Number Description Accessories Owners Registration Form Postage Required 116237-01C Warranty Information Keep this Warranty