Venting Installation
instructions
Continued
Horizontal Termination Configurations
Figures 14 through 18 show different configurations and alterna- tives for venting with horizontal termination. Each figure includes a chart with critical minimum and maximum dimensions which MUST be met. IMPORTANT: If using a venting configuration of only horizontal venting with no vertical run, a 1/4" rise for every 12" of run toward the termination is required.
 WARNING: Never run vent downward as this may cause excessive temperatures which could cause a fire. Operation of improperly installed and maintained venting system could result in serious injury, property damage or loss of life.
GROUND FLOOR INSTALLATION
Recommended Applications:
•Installation using cabinet surrounds
•Through the wall using round or square termination (up to 12" horizontal pipe)
•NOT FOR CORNER INSTALLATION
Adjustable  | 45° Elbow  | 
Pipe 12" Max.  | 
  | 
Horizontal High
Wind Square
Termination
Wall Firestop ![]()
Square Termination
  | Vertical (V) | Horizontal (H)  | 
36" Series  | 32 3/4" min.  | 17" max.  | 
42" Series  | 36 3/4" min.  | 17" max.  | 
45° Elbow  | 
  | Exterior Portion of  | |||
  | 
  | 
  | 
  | 
  | |
Wall  | 
  | Wall Firestop (Round  | |||
  | Termination Only)  | ||||
Firestop  | 
  | ||||
  | 
  | ||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
CORNER INSTALLATION
Recommended Applications:
•Corner ground floor installation
•Ground floor installation where pipe vents horizontally through wall (over 12" horizontal pipe)
•Basement installation where one foot clearance from ground to termination is possible
  | Not to Exceed  | 90° Elbow  | 
  | (H) Limits  | |
Wall  | 
  | |
  | 
  | |
Firestop  | 
  | As Required for (V)  | 
  | 
  | |
  | 
  | See Chart for Pipe  | 
  | 
  | Section Required  | 
Square  | 
  | 
  | 
Termination  | 45°  | 
  | 
  | 
  | |
  | Elbow  | 
  | 
Vertical (V) | Required | 
  | 
  | Horizontal (H) | ||||||||
36"  | 42"  | Vertical Pipe  | (36"/42")  | |||||||||
*43 1/2" min.  | 46 1/4" min.  | None  | 
  | 
  | 
  | 30" max.  | ||||||
54 1/2" min.  | 57 1/4" min.  | 1 ft.  | 
  | 
  | 
  | 48" max.  | ||||||
66 1/2" min.  | 69 1/4" min.  | 2 ft.  | 
  | 
  | 
  | 60" max.  | ||||||
78 1/2" min.  | 81 1/4" min.  | 3 ft.  | 
  | 
  | 
  | 84" max.  | ||||||
90 1/2" min.  | 93 1/4" min.  | 4 ft.  | 
  | 
  | 
  | 20' max.  | ||||||
*Note: Ground Floor Corner Venting  | 
  | 
  | 
  | 
  | 
  | |||||||
  | Not to Exceed  | 
  | 
  | 
  | 
  | 
  | ||||||
  | (H) Limits  | 
  | 
  | 
  | 
  | Square  | ||||||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | 90° Elbow  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Termination  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Wall  | 
  | 
Firestop  | 12" Minimum  | 
45° Elbow
Round  | Figure 15 - Horizontal Termination Configuration for Corner | 
Termination  | Installation Using One 90° Elbow  | 
Cap  | 
  | 
Round Termination
(Kit 01491 Shown)
Figure 14 - Horizontal Termination Configuration for Square
and Round Terminations
10  | www.desatech.com  |