Desa VsGF28PTF, VsGF28nTF installation manual Determining FRESH-AIR Flow for Heater Location

Page 7

AIR FOR COMBUSTION

AND VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or

Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with door- less passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height =__________cu. ft. (volume of space)

Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

___________ (volume of space) x 20 = (Maxi- mum Btu/Hr the space can support)

Example: 3168 cu. ft. (volume of space) x 20 = 63,360 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

____________ Btu/Hr

Gas water heater*

____________ Btu/Hr

Gas furnace

____________ Btu/Hr

Vented gas heater

____________ Btu/Hr

Gas fireplace logs

____________ Btu/Hr

Other gas appliances*

+__________ Btu/Hr

Total

=__________ Btu/Hr

*Do not include direct-vent gas appliances. Di- rect-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

 

40,000

 

Gas water heater

 

Btu/Hr

Vent-free fireplace

+_

39,000

Btu/Hr

Total

=_

79,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________ Btu/Hr (maximum the space can support)

__________ Btu/Hr (actual amount of Btu/Hr used) Example: 63,360 Btu/Hr (maximum the space

can support)

79,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maxi- mum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 9.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors, page 9.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maxi- mum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING:Iftheareainwhich the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

119303-01Awww.desatech.com

Image 7
Contents Thermostatically-controlled Models VSGF28NTF and VSGF28PTF What to do if YOU Smell GASSafety Information Table of ContentsSafety Information Local Codes Product Identification Product FeaturesUnpacking Confined and Unconfined Space Air For Combustion VentilationProviding Adequate Ventilation Unusually Tight ConstructionDetermining if You Have a Confined or Unconfined Space Determining FRESH-AIR Flow for Heater LocationVentilation Air From Outdoors InstallationVentilation AIR Ventilation Air From Inside BuildingCheck GAS Type Installing HoodConventional Fireplace Installation Installation ClearancesFront Width Built-In Firebox InstallationChecking Gas Connections, Actual Framing HeightMantel Clearances for Built-In Installation Installing Gas Piping to Fireplace Location,Installation Items Needed Installing Gas Piping to Fireplace LocationPropane/LP Connecting Fireplace to Gas SupplyAccessories, Natural GasTest Pressures Equal To or Less Than Psig 3.5 kPa Checking GAS ConnectionsPressure Testing Fireplace Gas Connections Installing LogsOperating Fireplace For Your Safety Read Before LightingThermostat Models Shutting Off Fireplace Lighting InstructionsTo Turn OFF GAS To Appliance Thermostat Control OperationPilot Flame Pattern Manual Lighting ProcedureInspecting Burners Blower OperationBurner Injector Holder Pilot Air Inlet Hole Cleaning MaintenanceModel VSGF28NTA Wiring DiagramSpecifications LogsObserved Problem Possible Cause Remedy TroubleshootingIng and Maintenance, Maintenance, Stalling Logs, See Checking Gas Connec Accessories Replacement PartsTechnical Service Service HintsDuplex Outlet KIT GA3555 Cleaning KIT GCKModels VSGF26NTF, VSGF26PTF Illustrated Parts BreakdownParts List Models VSGF28PTF and VSGF28NRF Parts List Keep this Warranty Warranty InformationLimited Warranty VENT-FREE GAS Fireplace System