Trane WCY030G1, WCY042G1, WCY048G1 manual Rooftop -- Units, Typical Rooftop Applications with Frame

Page 9

INSTALLATION

ROOFTOP -- UNITS

For roof top applications using a field fabricated frame and ducts, use the following procedure:

1.The frame must be located and secured by bolting or welding to the roof. Flashing is required.

2.The hole in the roof must be prepared in advance of installing the unit.

3.Secure the ducts to the roof.

4.Place the unit on the frame or roof curb. Refer to Figures 9 or 10.

5.Secure the unit to the frame or roof curb.

6.Insulate any ductwork outside of the structure with at least two (2) inches of insulation and then weatherproof. There must be a weatherproof seal where the duct enters the structure.

7.Complete the installation according to the instructions in the following sections of this manual.

9

TYPICAL ROOFTOP APPLICATIONS WITH FRAME

 

(WCY024-060G MODELS)

 

RETURN AIR

SUPPLY AIR

 

WEATHER-PROOF

 

 

DUCT

 

 

ROOF FLASHING

 

 

 

ANGLE IRON

 

 

FRAME

0

TYPICAL ROOFTOP APPLICATION WITH FRAME

(WCY024-060G MODELS)

 

 

WEATHER-PROOF

ROOF FLASHING

 

DUCT

 

 

 

 

SUPPLY AIR

 

ROOF FLASHING

 

 

RETURN AIR

ANGLE IRON

 

 

FRAME

Page 9

Image 9 Contents
Installation Operation Maintenance Inspection General InformationConverting Horizontal to Downflow Typical Rooftop Installation with BAYCURB030ADimensional Data WCY024-060G Outline Front Locations and Recommendations Clearances InstallationUnit Support Location and ClearancesOutdoor Coil END of Unit Rooftop -- Units Typical Rooftop Applications with FrameTypical Rooftop Application with Frame Ground Level -- Horizontal Units DuctworkTypical Ground Level Application Attaching Downflow Ductwork to Roof CurbDuct Attachment Methods Condensate Drain PipingElectrical Wiring Filter InstallationWCY-G Field Wiring Diagram Start UP ICM FAN Control Sequence of OperationFault Detection Demand Defrost SystemDefrost Control Demand Defrost Control Checkout Symptoms Checks YES/NO ActionsMaintenance Maintenance section Limited Warranty High Efficiency Heat Pump WCZ, WCY and WCXTrane Company