DEMAND DEFROST CONTROL CHECKOUT
SYMPTOMS | CHECKS | YES/NO | ACTIONS | |
|
|
|
| |
1. LED off. | 1. 24V | N | Repair low voltage wiring. | |
|
|
| ||
| Y | Complete Check #2. | ||
|
| |||
|
|
|
| |
| 2.Short FRC_DFT pin to TEST_COMMON pin. | N | Replace defrost control. | |
|
|
| ||
| Is defrost cycle initiated? | Y | LED is bad but control will still function. | |
|
| |||
|
|
|
| |
2. LED flashing very rapidly (greater |
| Y | Remove short. | |
than 4 times/sec) or appears to be on |
| |||
TEST_COMMON pin shorted to TST pin? |
|
| ||
|
| |||
continuously. | N | Replace defrost control. | ||
| ||||
|
| |||
|
|
|
| |
3. Control does not initiate a normal | OD Temp. below 49°F. |
| Check refrigerant circuits for balanced | |
defrost. | OD Coil temp. below 35°F.? | N | distribution of refrigerant if OD coil is | |
| "Delta" T increasing? |
| frosting and delta T is not increasing | |
|
|
|
| |
| 1. LED flashing? | N | Refer to SYMPTOM #1. | |
|
|
| ||
| Y | Complete Check #2. | ||
|
| |||
|
|
|
| |
| 2. Check for 24V | N | Repair low voltage wiring. | |
|
|
| ||
| Y | Complete Check #3. | ||
|
| |||
|
|
|
| |
| 3. Check sensors for correct mounting |
| Remount or replace sensor if necessary. | |
| (connection) and resistance. |
| ||
|
|
| ||
| 4. Short FRC_DFT pin to TEST_COMMON pin. | N | Replace defrost control. | |
|
|
| ||
| Is defrost cycle initiated? | Y | ||
|
| |||
|
|
|
| |
4. Control does not initiate a forced |
| N | Repair low voltage wiring. | |
defrost. | 24V | |||
|
| |||
Y | Replace defrost control. | |||
|
| |||
|
|
|
| |
5. Defrost initiates manually but terminates in less than 10 seconds. |
| Replace defrost control. | ||
|
|
| ||
|
|
|
| |
6. Defrost initiates manually but | 1. Coil sensor circuit open or reading at a very | Y | Replace coil sensor. | |
terminates on time. | high resistance? | |||
|
| |||
|
|
|
| |
| 2. Does OD fan cycle off in defrost? | N | Replace defrost control. | |
|
|
|
| |
| 3. Windy weather preventing normal |
|
| |
| termination? |
|
| |
7. Defrost initiates on approximately | Be sure OD coil is clean. | N | Complete Check #2. | |
15/25 minute intervals. | ||||
|
|
| ||
| 1. Coil sensor open or reading a very | Y | Replace coil sensor. | |
| high resistance? | |||
|
|
| ||
| 2. Ambient sensor reading less than normal? | N | Complete Check #3. | |
|
|
| ||
| Y | Replace ambient sensor. | ||
|
| |||
|
|
|
| |
| 3. OD fan off in defrost? | N | Replace defrost control. | |
|
|
|
| |
8. Defrost initiates on approximately | 1.TEST_COMMON pin shorted to TST pin? | Y | Remove short. | |
30/45 minute intervals. | ||||
|
|
| ||
| N | Replace defective sensor (Clear coil and | ||
|
| |||
| 2. Do both sensors check OK? | reset Emergency heat light). | ||
|
| |||
|
| Y | Complete SYMPTOM #3. | |
|
|
|
| |
| 3. Verify correct system charge. |
| Adjust as needed. | |
|
|
|
| |
| 4. Verify a "forced defrost" terminates less than | N | Replace defrost control. | |
| 15 minutes. | |||
|
|
| ||
|
|
|
| |
| 5. OD fan motor off in defrost. |
| See SYMPTOM #9. | |
|
|
|
| |
| 6. Verify proper SOV operation. |
| Replace if necessary. | |
|
|
|
| |
9. OD fan runs during defrost. |
|
| Replace defrost control. | |
|
|
|
| |
10. No SOV delay on defrost |
| Y | The | |
termination. | Has J1 been cut? | is cut. | ||
| ||||
|
| N | Replace defrost control. | |
|
|
|
| |
11. |
| Y | Check low voltage wiring for miswire. | |
| 1. B to T greater than 10 volts? | N | Check for short in low voltage wiring. | |
|
| |||
|
|
|
| |
12. On SCROLL bearing units, | 1. 24V | N | Repair low voltage wiring. | |
compressor does not operate. | ||||
|
|
| ||
2. Check protective devices in YO circuit . 24V | N | |||
| ||||
| ||||
|
|
| ||
13. On SCROLL bearing units, no 30 | Check voltage between control terminals 2 and |
|
| |
second off delay at defrost initiation. | 7,force a defrost cycle. Is 24V present for 30 | N | Replace defrost control. | |
| seconds and 0V thereafter? |
|
|