DEMAND DEFROST SYSTEM

DEFROST CONTROL

The demand defrost control measures heat pump outdoor ambient temperature with a sensor located outside the outdoor coil. A second sensor located on the outdoor coil is used to measure the coil temperature. The difference between the ambient and the colder coil temperature is the difference or delta-T measurement. This delta-T measurement is representative of the operating state and relative capacity of the heat pump system. By measuring the change in delta-T, we can determine the need for defrost. The coil sensor also serves to sense outdoor coil temperature for termina- tion of the defrost cycle.

FAULT DETECTION

A fault condition is indicated by the flashing light on the defrost control inside the heat pump control box.

In normal operation, the defrost control light will flash once each second. If the light is flashing more than once per second or not-at- all, refer to the service manual for that unit.

PIN IDENTIFICATION (See Figure)

1.TEST_COMMON (Shorting any of the other pins to this pin causes the function of the other pin to be executed. Leaving this pin open results in the normal mode of operation.)

2.TST = Test (Shorting TEST_COMMON to this pin speeds up all defrost board timings.)

3.FRC_DFT = Forced Defrost (Short TEST_COMMON to this pin for two (2) seconds to initiate a forced defrost. Remove the short after defrost initiates.)

PIN IDENTIFICATION

FRC_DFT

TEST_COMMON

TST

DEFROST CONTROL CHECKOUT

Normal operation requires:

a.LED on board flashing 1 time/second.

b.24V AC between R & B

c.24V AC between Y & B with unit operating

d.Defrost initiation when FRC_DFT pin is shorted to TEST_COMMON pin.

If a defrost control problem is suspected, proceed to DEMAND DEFROST CONTROL CHECKOUT in this Service Facts.

WARNING: Do NOT connect 24 VAC to T1 (ODS-A) terminal. ODS-A thermistor WILL BE BLOWN.

PROCEDURE FOR TESTING SENSORS

Measure the temperature the subject sensor is exposed to. If the sensor is mounted on a tube, place the lead on an Annie A-8 (or equiv.) temperature tester on the same tube near the sensor and insulate the bulb.

Unplug the sensor and measure the resistance with a good quality ohmmeter (Simpson 260 or equiv.). Read the value as quickly as possible to prevent the meter current from changing the resistance reading.

Using the chart on the right, locate (as close as possible) the actual sensor temperature. The measured resistance should be relatively close to the resistance value shown in the chart.

Example:

 

Sensor temp.

= 19°F.

Measured Resistance

= 46K ohms

This sensor is good since the measured value is relatively close to the chart value.

FLASH RATE INDICATIONS:

TEMP °F

RESISTANCE

86

7.85K

81

8.85K

75

10.24K

70

11.59K

65

13.14K

59

15.32K

55

16.93K

50

19.41K

45

22.20K

41

24.76K

36

28.45K

32

31.84K

25

37.50K

19

46.44K

14

53.94K

10

57.64K

5

67.06K

0

78.05K

1

— Flash/Second

= Normal operation.

2

— Flashes/Second

= Fault A (Low T) i.e.: Inoperative compressor, loss of charge, open ambient sensor, shorted coil sensor.

3

— Flashes/Second

= Fault B (20 defrosts terminated on time)

 

 

Fault C (High T) i.e.: SOV stuck in heating, shorted ambient sensor, open coil sensor, closed TXV,

 

 

OD motor failure, OD fan on in defrost, undercharged unit.

4

— Flashes/Second

= Fault A & C or A & B

For additional information consult Pub. No. 34-1001 Heat Pump Defrost Controls.

Page 16

Image 16
Contents Installation Operation Maintenance General Information InspectionTypical Rooftop Installation with BAYCURB030A Converting Horizontal to DownflowDimensional Data WCY024-060G Outline Front Locations and Recommendations Installation ClearancesUnit Support Location and ClearancesOutdoor Coil END of Unit Typical Rooftop Applications with Frame Rooftop -- UnitsTypical Rooftop Application with Frame Ductwork Ground Level -- Horizontal UnitsTypical Ground Level Application Attaching Downflow Ductwork to Roof CurbCondensate Drain Piping Duct Attachment MethodsFilter Installation Electrical WiringWCY-G Field Wiring Diagram Start UP Sequence of Operation ICM FAN ControlDemand Defrost System Fault DetectionDefrost Control Symptoms Checks YES/NO Actions Demand Defrost Control CheckoutMaintenance Limited Warranty High Efficiency Heat Pump WCZ, WCY and WCX Maintenance sectionTrane Company

WCY036G1, WCY042G1, WCY060G1, WCY048G1, WCY030G1 specifications

The Trane WCY series is a line of water-cooled chillers that exemplify innovation and efficiency in commercial HVAC systems. Models such as WCY024G1, WCY030G1, WCY042G1, WCY048G1, and WCY060G1 are designed to meet diverse cooling needs while maintaining energy efficiency and reliability.

One of the standout features of the WCY series is its use of advanced chiller technology, which incorporates a reliable, scroll compressor. These compressors are known for their durability and efficiency, allowing the chillers to provide cooling capacity ranging from 24 to 60 tons, making them suitable for various building sizes and applications. The efficient design of these compressors contributes to lower energy consumption, leading to potential savings on operational costs.

Another significant characteristic of the Trane WCY series is its use of microchannel heat exchangers. These heat exchangers feature a compact design that minimizes refrigerant charge and enhances heat transfer performance. The microchannel technology not only improves overall efficiency, but it also contributes to a smaller physical footprint for the units, allowing for flexible installation options in tight spaces.

The chillers are equipped with advanced controls that optimize performance, enabling users to easily monitor and adjust system operations through a user-friendly interface. The integration of Trane's Tracerâ„¢ control technology enhances operational efficiency by providing real-time data and analytics, which can inform maintenance needs and system adjustments.

In addition to these features, the WCY series includes robust construction that ensures reliability in diverse environments. The units are designed to withstand various weather conditions and are built with corrosion-resistant materials to enhance durability.

Furthermore, the Trane WCY chillers are designed with sustainability in mind. They utilize refrigerants with low global warming potential (GWP), aligning with contemporary environmental standards and enhancing the overall sustainability of building operations.

In summary, the Trane WCY024G1, WCY030G1, WCY048G1, WCY060G1, and WCY042G1 chillers represent cutting-edge technology in water-cooled cooling solutions. With their efficient compressors, innovative heat exchange design, advanced controls, and commitment to sustainability, these chillers are an excellent choice for commercial buildings seeking reliable and efficient cooling solutions. Whether for new installations or retrofits, the Trane WCY series offers versatility and performance that meets the demands of modern HVAC applications.