Trane WCY042G1, WCY048G1, WCY036G1, WCY030G1, WCY060G1 manual Filter Installation, Electrical Wiring

Page 12

FILTER INSTALLATION

TABLE 1

AIR FILTERS

Filters are to be used with the WCY024-060Gheating/cooling units. The basic unit does not have filters in it. However, a filter frame accessory is offered that will allow filters to be installed within the unit.

Otherwise a filter rack must be installed by the installer in the duct work.

Affix the filter label supplied with the unit adjacent to the filter area.

UNIT

NOMINAL

FILTER*

FILTER

CFM

(Sq Ft) SIZE

RESISTANCE

 

WCY024G

800

2.67

0.05

 

 

 

 

WCY030G

1000

3.33

0.05

WCY036G

1200

4.00

0.05

WCY042G

1400

4.67

0.05

WCY048G

1600

5.33

0.05

 

 

 

 

WCY060G

2000

6.67

0.05

*Filters must be installed in the return air system. The above square footages are based on 300 F.P.M. face velocity. If permanent filters are used, size per mfg. recommendation with clear resistance of 0.05"WC.

ELECTRICAL WIRING

ELECTRICAL CONNECTIONS

Electrical wiring and grounding must be installed in accordance with local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA 70, Latest Revision.

ELECTRICAL POWER

It is important that proper electrical power be available for the unit. Voltage variation should remain within the limits stamped on the unit nameplate.

DISCONNECT SWITCH

Provide an approved weather-proof disconnect either on the side of the unit or within close proximity and within sight of the unit.

OVER CURRENT PROTECTION

The branch circuit feeding the unit must be protected as shown on the unit rating plate.

POWER WIRING

The power supply lines must be run in weathertight conduit to the disconnect and into the bottom of the unit control box. Provide strain relief for all conduit with suitable connectors.

Provide flexible conduit supports whenever vibration transmission may cause a noise problem within the building structure.

Be sure all connections are made tight. See Figure 14.

NOTES: For branch circuit wiring (main power supply to unit disconnect), wire size for the length of run should be determined using the circuit ampacity found on the unit nameplate and the N.E.C.

For more than 3 conductors in a raceway or cable, see the N.E.C. for derating the ampacity of each conductor.

GROUNDING: THE UNIT MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR THE NATIONAL ELECTRIC CODE.

NOTE: Ground the unit internally as provided. See wiring diagram for location.

CONTROL WIRING (CLASS II)

Low voltage control wiring should not be run in conduit with power wiring unless Class 1 wire of proper voltage rating is used. Route the thermostat cable or equivalent single leads of No. 18 AWG colored wire from the thermostat subbase terminals through the rubber gromment on the unit. See Figure 5 for the control entry location. Make connections as shown on the unit wiring diagram and in Figure 14.

Do not short thermostat wires since this will damage the control transformer.

Recommended wire sizes and lengths for installing the unit thermo- stat are provided in Table 2. The total resistance of these low voltage wires must not exceed one (1) ohm. Any resistance in excess of 1 ohm may cause the control to malfunction because of the excessive voltage drop

TABLE 2

THERMOSTAT WIRE SIZE AND MAXIMUM LENGTH

WIRE SIZE

MAXIMUM LENTGH (Ft)

18

75

16

125

14

200

THERMOSTAT HEAT ANTICIPATOR

The thermostat heat anticipators should be set to equal the amper- age draw of the W1 thermostat circuit.

IMPORTANT: Upon completion of wiring check all electrical connections, including factory wiring within the unit. Make sure all connections are tight. Replace and secure all electrical box covers and access doors before leaving the unit or turning on the power to the unit.

Page 12

Image 12
Contents Installation Operation Maintenance General Information InspectionTypical Rooftop Installation with BAYCURB030A Converting Horizontal to DownflowDimensional Data WCY024-060G Outline Front Locations and Recommendations Installation ClearancesUnit Support Location and ClearancesOutdoor Coil END of Unit Rooftop -- Units Typical Rooftop Applications with FrameTypical Rooftop Application with Frame Ductwork Ground Level -- Horizontal UnitsTypical Ground Level Application Attaching Downflow Ductwork to Roof CurbCondensate Drain Piping Duct Attachment MethodsFilter Installation Electrical WiringWCY-G Field Wiring Diagram Start UP Sequence of Operation ICM FAN ControlFault Detection Demand Defrost SystemDefrost Control Symptoms Checks YES/NO Actions Demand Defrost Control CheckoutMaintenance Limited Warranty High Efficiency Heat Pump WCZ, WCY and WCX Maintenance sectionTrane Company

WCY036G1, WCY042G1, WCY060G1, WCY048G1, WCY030G1 specifications

The Trane WCY series is a line of water-cooled chillers that exemplify innovation and efficiency in commercial HVAC systems. Models such as WCY024G1, WCY030G1, WCY042G1, WCY048G1, and WCY060G1 are designed to meet diverse cooling needs while maintaining energy efficiency and reliability.

One of the standout features of the WCY series is its use of advanced chiller technology, which incorporates a reliable, scroll compressor. These compressors are known for their durability and efficiency, allowing the chillers to provide cooling capacity ranging from 24 to 60 tons, making them suitable for various building sizes and applications. The efficient design of these compressors contributes to lower energy consumption, leading to potential savings on operational costs.

Another significant characteristic of the Trane WCY series is its use of microchannel heat exchangers. These heat exchangers feature a compact design that minimizes refrigerant charge and enhances heat transfer performance. The microchannel technology not only improves overall efficiency, but it also contributes to a smaller physical footprint for the units, allowing for flexible installation options in tight spaces.

The chillers are equipped with advanced controls that optimize performance, enabling users to easily monitor and adjust system operations through a user-friendly interface. The integration of Trane's Tracerâ„¢ control technology enhances operational efficiency by providing real-time data and analytics, which can inform maintenance needs and system adjustments.

In addition to these features, the WCY series includes robust construction that ensures reliability in diverse environments. The units are designed to withstand various weather conditions and are built with corrosion-resistant materials to enhance durability.

Furthermore, the Trane WCY chillers are designed with sustainability in mind. They utilize refrigerants with low global warming potential (GWP), aligning with contemporary environmental standards and enhancing the overall sustainability of building operations.

In summary, the Trane WCY024G1, WCY030G1, WCY048G1, WCY060G1, and WCY042G1 chillers represent cutting-edge technology in water-cooled cooling solutions. With their efficient compressors, innovative heat exchange design, advanced controls, and commitment to sustainability, these chillers are an excellent choice for commercial buildings seeking reliable and efficient cooling solutions. Whether for new installations or retrofits, the Trane WCY series offers versatility and performance that meets the demands of modern HVAC applications.