REQUIRED CLEARANCE FOR UNIT INSTALLATION

AND ROOF PENETRATION HOLE SIZE REQUIRED

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

A

 

 

 

 

 

 

 

 

 

 

 

 

SERVICE

 

 

 

 

SERVICE

 

 

 

CLEARANCE

 

 

 

 

CLEARANCE

 

 

 

LINES

 

 

 

 

LINES

 

 

 

 

 

 

 

SUPPLY AIR

 

 

 

 

 

 

 

 

 

C

RETURN AIR

B

 

 

 

 

 

 

 

 

 

 

SIDE RAIL

 

 

 

 

 

 

 

 

WOOD NAILER

 

 

 

 

 

SERVICE CLEARANCE & PENETRATION DIMENSIONS

 

 

 

MODEL NO.

A

B

C

D

E

F

HOLE IN ROOF

 

 

WCY024-030G

30"

30"

*12"

24"

36"

25"

 

 

 

WCY036-042G

30"

30"

*12"

30"

44"

25"

 

 

 

WCY048-060G

42"

30"

*12"

36"

50"

25"

E

 

F

 

 

 

 

 

 

 

 

 

* 18" WITH FRESH AIR ACCESSORY

 

 

 

 

 

 

* 30" WITH ECONOMIZER

 

 

 

 

 

 

 

 

LOCATIONS AND RECOMMENDATIONS

These units are designed for outdoor installation. For proper instal- lation, the following recommendations must be considered.

NOTE: Unit shipped for horizontal installation. Convert to downflow per instruction.

The discharge air from the condenser fans must be unrestricted for a minimum of 3 feet above the unit.

Roof Mounting Curb (field assembled BAYCURB030A and BAYCURB033A, BAYCURB034A) or a field fabricated curb must be in place before unit is hoisted to the roof.

Roof Mounting Curb (frame) must be installed on a flat, level section of the roof (max. of 1/4" per foot pitch), providing a level mounting surface for the unit. In addition, provide sufficient height above the roof to prevent water from entering unit.

In locations where deep snows are encountered,RAlSE THE UNlT A MINIMUM OF 12" OFF THE ROOF, DECK OR SLAB—the chance of the coil being blocked with snow will be reduced. The water that occurs during the defrost has a better chance of flowing from the vicinity of the unit.

Roof Mounting Curb used with WCY—F models is approximately 14" high. This is normally sufficient height to prevent snow blockage and additional clearance is not necessary.

AVOID LOCATING THE UNIT WHERE SNOW TENDS TO DRIFT. This will reduce the times when it is necessary for the customer to remove the snow from around the unit. MAKE CERTAIN THE CUSTOMER KNOWS THAT SNOW ACCUMULATIONS SHOULD BE REMOVED FROM THE SIDES OF THE UNIT FOR BEST EFFICIENCY.

A snow drift barrier may be installed around the unit to prevent a build up of snow on the sides of the unit. The barrier should be of sufficient distance from the unit to prevent restriction of airflow to and from unit.

LOCATE THE UNIT SO THAT THE WATER VAPOR THAT DIS- CHARGES UPWARD DURING DEFROST DOES NOT CONDENSE ON WINDOWS AND FOG THEM OR CAUSE ICICLES TO FORM ON OVERHANGS.

1.Be sure the mounting curb spans structural members (trusses) of the roof, thereby providing sufficient support for weight of the unit, curb and duct(s) plus any accessories (factory or field installed). See Figures 1, 2, 3, 4, 5, 6, 7, 8, 9,10,11 and 12.

NOTE: If any internal accessories are to be added to the unit it should be done at the shop if at all practical.

2.Unit should be positioned so Roof-Run-Off water does not pour directly on unit.

Page 6

Image 6 Contents
Installation Operation Maintenance General Information InspectionTypical Rooftop Installation with BAYCURB030A Converting Horizontal to DownflowDimensional Data WCY024-060G Outline Front Locations and Recommendations Unit Support InstallationClearances Location and ClearancesOutdoor Coil END of Unit Rooftop -- Units Typical Rooftop Applications with FrameTypical Rooftop Application with Frame Typical Ground Level Application DuctworkGround Level -- Horizontal Units Attaching Downflow Ductwork to Roof CurbCondensate Drain Piping Duct Attachment MethodsFilter Installation Electrical WiringWCY-G Field Wiring Diagram Start UP Sequence of Operation ICM FAN ControlFault Detection Demand Defrost SystemDefrost Control Symptoms Checks YES/NO Actions Demand Defrost Control CheckoutMaintenance Limited Warranty High Efficiency Heat Pump WCZ, WCY and WCX Maintenance sectionTrane Company