Trane PKGP-PRC003-EN manual Data4Ton, Table PD-10, Table PD-11, HP Standard Motor & Field Supplied

Page 22

Performance

Data(4Ton)

Table PD-10— Belt Drive Evaporator Fan Performance — 4 Ton — WSC048A3,A4,AW — Downflow Airflow

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

.10

 

.20

 

.30

 

.40

 

.50

 

.60

.70

 

.80

 

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

1-HP Standard Motor & Field Supplied

 

 

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

 

 

Low Static Drive (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1280

616

0.22

677

0.26

734

0.31

787

0.37

834

0.42

878

0.48

919

0.53

959

0.59

997

0.64

1440

596

0.23

663

0.29

719

0.33

772

0.38

823

0.44

871

0.51

914

0.57

954

0.63

993

0.69

1029

0.75

1600

647

0.31

711

0.37

764

0.42

813

0.47

860

0.53

906

0.59

951

0.66

992

0.74

1029

0.80

1065

0.87

1760

701

0.41

758

0.46

811

0.52

856

0.58

901

0.64

944

0.70

986

0.77

1027

0.85

1066

0.93

1102

1.00

1920

755

0.52

807

0.57

859

0.64

903

0.71

945

0.77

985

0.83

1024

0.89

1063

0.97

1101

1.05

1137

1.14

Table PD-10 — Continued

 

 

 

External Static Pressure (Inches of Water)

 

 

 

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

1280

1033

0.70

1069

0.77

1103

0.83

1136

0.89

1170

0.96

1440

1066

0.81

1099

0.87

1133

0.94

1165

1.01

1196

1.08

1600

1099

0.93

1132

1.00

1166

1.07

1196

1.14

1228

1.21

1760

1136

1.08

1168

1.15

1200

1.22

1229

1.29

1920

1172

1.23

1205

1.31

1236

1.39

For Standard Evaporator Fan Speed (RPM), reference Table PD-20. Notes:

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-23 to determine additional static pressure drop due to other options/accessories.

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.

1.Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-11 — Belt Drive Evaporator Fan Performance — 4 Ton — WSC048A3,A4,AW — Horizontal Airflow

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

.10

 

.20

 

.30

 

.40

 

.50

 

.60

 

.70

 

.80

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

1-HP Standard Motor & Field Supplied

 

 

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

 

 

 

Low Static Drive (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1280

604

0.20

683

0.26

756

0.32

816

0.39

869

0.45

920

0.51

967

0.57

1011

0.64

1052

0.71

1090

0.79

1440

660

0.28

731

0.34

800

0.41

862

0.48

914

0.54

963

0.61

1009

0.68

1053

0.76

1094

0.83

1133

0.91

1600

717

0.36

783

0.43

846

0.51

907

0.58

961

0.66

1008

0.73

1053

0.81

1095

0.89

1135

0.97

1174

1.05

1760

774

0.47

837

0.54

894

0.62

952

0.70

1006

0.79

1054

0.87

1098

0.95

1139

1.04

1178

1.12

1216

1.21

1920

833

0.59

892

0.67

946

0.76

998

0.85

1050

0.94

1100

1.03

1144

1.12

1185

1.21

1224

1.30

1259

1.39

Table PD-11 — Continued

 

 

 

External Static Pressure (Inches of Water)

 

 

 

1.10

1.20

1.30

 

1.40

 

1.50

 

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

1280

1125

0.86

1160

0.94

1192

1.01

1223

1.08

1254

1.15

1440

1169

0.98

1204

1.07

1237

1.15

1269

1.23

1300

1.32

1600

1211

1.13

1247

1.21

1280

1.30

1312

1.39

1343

1.48

1760

1253

1.30

1289

1.39

1322

1.47

1920

1295

1.48

1-HP Standard Motor &Field Supplied High Static Drive (2)

1-HP Standard Motor &Field Supplied High Static Drive (2)

For Standard Evaporator Fan Speed (RPM), reference Table PD-20. Notes:

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-23 to determine additional static pressure drop due to other options/accessories

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.

1.Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.

2.Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

22

PKGP-PRC003-EN

Image 22
Contents Packaged Heat Pumps Introduction American Standard Inc. All Rights ReservedContents Factory Installed Options Field Installed Options Features BenefitsFactory or Field Installed Options Easy to Install, Service and Maintain Features and BenefitsQuality and Reliability Black Epoxy Pre-Coated Coils Clogged Filter/Fan Failure SwitchColoredAnd NumberedWiring Cabinet IntegrityQuick-Access Panels Phase MonitorPower Exhaust Option Quick-Adjust Idler ArmUnit Cabinet Rigorous TestingVentilation Override Accessory VariTracEasy to Install Added Efficiency Clearance Requirements Barometric ReliefCondensate Trap Unit PitchAir Delivery Selection Cooling CapacityHeating Capacity StepModel Number Description 036 11 12,13Data GeneralTable GD-1 General Data OutdoorSoundRatingdB3 Outdoor Coil -Type General DataTable GD-2 General Data Outdoor Fan TypeEER2 ½, 10TonTable GD-3 General Data Outdoor Fan- TypeMBH SHC Performance DataMBH SHC MBH SHC MBH SHC Ton Three Phase WSC060A1,A3, A4, AW PerformanceTon Three Phase ½ Ton Three PhaseMBH SHC MBH SHC MBH SHC MBH SHC MBH WSC048A WSC036AHorizontal WSC060ATable PD-8 Data3TonTable PD-9 Table PD-11 Data4TonTable PD-10 HP Standard Motor & Field SuppliedTable PD-13 Data5TonTable PD-12 HP Standard Motor & Drive Low Static DriveTable PD-14 Data6TonTable PD-15 Table PD-17 Data7½TonTable PD-16 HP Oversized Motor& Field Supplied Sheave2Table PD-19 Data10 TonTable PD-18 HP Standard Motor & Drive HP Oversized Motor & DriveWSC072A Table PD-20- Standard Motor & Sheave/Fan Speed RpmTable PD-22 Oversized Motor & Drive Sheave/Fan Speed Rpm WSC090ATable PD-25 Outdoor Sound Power Level dB ref -12Watts WSC072A WSC090A WSC120AHeating Capacities Net WSC036A1 At 1200 CFM At 1200 CFMHeating Capacities Net WSC048A1 At 1600 CFM At 1600 CFMHeating Capacities Net WSC60A1 At 2000 CFM At 2000 CFMWSC72A At 3000 CFM Downflow Configuration WSC120A Table PD-38 Auxiliary Electric Heat Capacity Nominal DistributionWS120A3,A4,AW 6Ton ½ Ton 10Ton 2000 3000 CFM14.2 18.00 28.5 19.0 27.00 42.7 21.3 36.00 56.9 37.9 54.00 Controls ReliaTel Controlled UnitsTable ED-1 Unit Wiring Electrical Data208/230 Volts Single Phase 208/230 Volts Three PhaseVolts Three Phase BAYHTR306A FLA LRA AMPS1 Amps Table ED-8 Electrical Characteristics Power ExhaustHP2 RPM RLA LRA Zone Sensors -Typical Number Of Wires Jobsite ConnectionsDimensional Data TonsDimensional DataDimensional Data 7½ Tons WSC072A and WSC090A Tons -WSC120ASupply Tons Unit Clearance and Roof OpeningTons Roof Curb Tons Downflow Duct Connections Field FabricatedTons Economizer, Manual, or Motorized Data AccessoriesSee Page 46 forThrough the Base Utilities Information Fresh Air DamperSee Page 48 forThrough the Base Utilities Information Weights Table W-2 Factory-installed Options Net Weights Lbs1,2Mechanical Specifications Factory Installed Options Factory or Field Installed OptionsField Installed Options PL-UN-PKGP-WSC 3-10TONS-PRC003-EN-09-04 PL-UN-PKGP-WSC 3-10TONS-PRC003-EN-02-04

PKGP-PRC003-EN specifications

The Trane PKGP-PRC003-EN is a high-performance packaged rooftop unit designed to provide efficient heating, cooling, and ventilation solutions for a wide variety of commercial applications. Its innovative design encompasses advanced technologies aimed at improving energy efficiency and overall operational efficiency.

One of the standout features of the PKGP-PRC003-EN is its highly efficient variable speed compressor. This technology allows the unit to modulate its capacity based on the specific needs of the environment, ensuring optimal comfort levels while reducing energy consumption. Coupled with a robust fan system, the unit can maintain precise temperature control in fluctuating weather conditions, providing reliable comfort year-round.

The unit's advanced controls use a user-friendly interface that simplifies operation and monitoring. These controls can be integrated with building management systems (BMS), allowing for seamless connectivity and enhanced control over the HVAC system. With the capability for remote monitoring, facility managers can track performance metrics and receive alerts for maintenance, ensuring that the unit operates efficiently and minimizes downtime.

In terms of design, the PKGP-PRC003-EN is equipped with durable construction materials that withstand outdoor environments, ensuring a long lifespan with minimal maintenance. The unit’s compact footprint allows it to fit in tight spaces on rooftops, making it an ideal choice for urban environments where space is limited.

Furthermore, the Trane PKGP-PRC003-EN incorporates advanced filtration systems to improve indoor air quality. These filters effectively capture dust, pollen, and other allergens, contributing to a healthier indoor environment. The unit is also designed with sound attenuation features, minimizing operational noise, which is particularly beneficial for installations in noise-sensitive areas.

Overall, the Trane PKGP-PRC003-EN sets a high standard in the realm of rooftop HVAC solutions. Its combination of energy efficiency, smart control capabilities, and robust construction makes it a reliable choice for businesses looking to enhance their indoor climate while being mindful of operational costs. The integration of advanced technologies ensures that it not only meets but exceeds the expectations of modern HVAC performance, all while maintaining user-friendly operation and maintenance.