Trane PKGP-PRC003-EN manual Data5Ton, Table PD-12, Table PD-13, HP Standard Motor

Page 23

Performance

Data(5Ton)

Table PD-12 — Belt Drive Evaporator Fan Performance — 5 Ton — WSC060A3,A4,AW — Downflow Airflow

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

.10

 

.20

 

.30

.40

 

 

.50

 

.60

.70

 

 

.80

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

1-HP Standard Motor & Field Supplied Low Static Drive (1)

 

 

1-HP Standard Motor & Drive

 

 

 

1600

703

0.36

757

0.41

806

0.47

854

0.52

899

0.58

944

0.65

985

0.73

1023

0.79

1060

0.86

1800

706

0.42

760

0.47

815

0.54

861

0.60

904

0.66

947

0.72

988

0.78

1028

0.86

1067

0.94

1104

1.02

2000

773

0.57

821

0.62

873

0.69

918

0.76

958

0.83

998

0.90

1036

0.96

1073

1.02

1111

1.10

1147

1.19

2200

840

0.75

885

0.80

930

0.87

977

0.95

1016

1.03

1053

1.10

1089

1.17

1124

1.24

1158

1.31

1191

1.39

2400

909

0.96

950

1.02

990

1.08

1034

1.16

1074

1.25

1110

1.00

1143

1.42

1177

1.50

Table PD-12 — Continued

 

 

 

External Static Pressure (Inches of Water)

 

 

 

1.10

1.20

1.30

 

1.40

 

1.50

 

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

1600

1093

0.92

1126

0.99

1160

1.06

1190

1.13

1222

1.20

1800

1138

1.10

1171

1.17

1203

1.25

1232

1.32

1262

1.39

2000

1182

1.28

1215

1.37

1246

1.46

2200

1226

1.48

2400

For Standard Evaporator Fan Speed (RPM), reference Table PD-20. Notes:

Data includes pressure drop due to standardfilters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-23 to determine additional static pressure drop due to other options/accessories

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.

1.Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-13 — Belt Drive Evaporator Fan Performance — 5 Ton — WSC060A3,A4,AW — Horizontal Airflow

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

.10

 

 

.20

 

.30

.40

 

 

.50

 

.60

 

.70

 

.80

.90

 

1.00

CFM

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

1-HP Standard Motor & Field Supplied

 

 

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

 

 

 

Low Static Drive (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1600

707

0.35

774

0.42

837

0.50

898

0.57

953

0.65

1001

0.72

1045

0.80

1087

0.87

1129

0.95

1168

1.03

1800

778

0.48

 

840

0.56

897

0.64

953

0.72

1008

0.81

1058

0.89

1102

0.98

1143

1.06

1181

1.15

1219

1.23

2000

850

0.65

 

908

0.73

961

0.81

1012

0.90

1062

1.00

1111

1.09

1157

1.19

1198

1.28

1237

1.37

1274

1.47

2200

923

0.84

 

978

0.93

1028

1.02

1075

1.12

1120

1.22

1166

1.32

1211

1.43

2400

997

1.07

1049

1.17

1096

1.27

1140

1.37

1183

1.48

Table PD-13 — Continued

 

 

 

External Static Pressure (Inches of Water)

 

 

 

1.10

 

1.20

 

1.30

 

1.40

 

1.50

 

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

1-HP Standard Motor

 

 

 

 

 

1600

1206

1.12

1241

1.20

1275

1.28

1306

1.37

1338

1.46

1800

1256

1.32

1291

1.41

1326

1.50

2000

2200

2400

For Standard Evaporator Fan Speed (RPM), reference Table PD-20. Notes:

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-23 to determine additional static pressure drop due to other options/accessories

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.

1.Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

PKGP-PRC003-EN

23

Image 23
Contents Packaged Heat Pumps American Standard Inc. All Rights Reserved IntroductionContents Factory or Field Installed Options Features BenefitsFactory Installed Options Field Installed Options Quality and Reliability Features and BenefitsEasy to Install, Service and Maintain Cabinet Integrity Clogged Filter/Fan Failure SwitchColoredAnd NumberedWiring Black Epoxy Pre-Coated CoilsQuick-Adjust Idler Arm Phase MonitorPower Exhaust Option Quick-Access PanelsVariTrac Rigorous TestingVentilation Override Accessory Unit CabinetEasy to Install Added Efficiency Unit Pitch Barometric ReliefCondensate Trap Clearance RequirementsStep Cooling CapacityHeating Capacity Air Delivery Selection036 11 12,13 Model Number DescriptionTable GD-1 General Data GeneralData Outdoor Fan Type General DataTable GD-2 General Data OutdoorSoundRatingdB3 Outdoor Coil -TypeOutdoor Fan- Type ½, 10TonTable GD-3 General Data EER2MBH SHC MBH SHC MBH SHC Performance DataMBH SHC Performance Ton Three Phase WSC060A1,A3, A4, AWMBH SHC MBH SHC MBH SHC MBH SHC MBH ½ Ton Three PhaseTon Three Phase WSC060A WSC036AHorizontal WSC048ATable PD-9 Data3TonTable PD-8 HP Standard Motor & Field Supplied Data4TonTable PD-10 Table PD-11HP Standard Motor & Drive Low Static Drive Data5TonTable PD-12 Table PD-13Table PD-15 Data6TonTable PD-14 HP Oversized Motor& Field Supplied Sheave2 Data7½TonTable PD-16 Table PD-17HP Standard Motor & Drive HP Oversized Motor & Drive Data10 TonTable PD-18 Table PD-19WSC090A Table PD-20- Standard Motor & Sheave/Fan Speed RpmTable PD-22 Oversized Motor & Drive Sheave/Fan Speed Rpm WSC072AWSC072A WSC090A WSC120A Table PD-25 Outdoor Sound Power Level dB ref -12WattsAt 1200 CFM Heating Capacities Net WSC036A1 At 1200 CFMAt 1600 CFM Heating Capacities Net WSC048A1 At 1600 CFMAt 2000 CFM Heating Capacities Net WSC60A1 At 2000 CFMWSC72A At 3000 CFM Downflow Configuration WSC120A Nominal Distribution Table PD-38 Auxiliary Electric Heat Capacity14.2 18.00 28.5 19.0 27.00 42.7 21.3 36.00 56.9 37.9 54.00 6Ton ½ Ton 10Ton 2000 3000 CFMWS120A3,A4,AW ReliaTel Controlled Units ControlsElectrical Data Table ED-1 Unit Wiring208/230 Volts Three Phase 208/230 Volts Single PhaseVolts Three Phase BAYHTR306A FLA LRA HP2 RPM RLA LRA Table ED-8 Electrical Characteristics Power ExhaustAMPS1 Amps Jobsite Connections Zone Sensors -Typical Number Of WiresData Tons DimensionalData Dimensional7½ Tons WSC072A and WSC090A Tons -WSC120A Dimensional DataTons Unit Clearance and Roof Opening SupplyTons Downflow Duct Connections Field Fabricated Tons Roof CurbFresh Air Damper Data AccessoriesSee Page 46 forThrough the Base Utilities Information Tons Economizer, Manual, or MotorizedSee Page 48 forThrough the Base Utilities Information Table W-2 Factory-installed Options Net Weights Lbs1,2 WeightsMechanical Specifications Factory or Field Installed Options Factory Installed OptionsField Installed Options PL-UN-PKGP-WSC 3-10TONS-PRC003-EN-02-04 PL-UN-PKGP-WSC 3-10TONS-PRC003-EN-09-04

PKGP-PRC003-EN specifications

The Trane PKGP-PRC003-EN is a high-performance packaged rooftop unit designed to provide efficient heating, cooling, and ventilation solutions for a wide variety of commercial applications. Its innovative design encompasses advanced technologies aimed at improving energy efficiency and overall operational efficiency.

One of the standout features of the PKGP-PRC003-EN is its highly efficient variable speed compressor. This technology allows the unit to modulate its capacity based on the specific needs of the environment, ensuring optimal comfort levels while reducing energy consumption. Coupled with a robust fan system, the unit can maintain precise temperature control in fluctuating weather conditions, providing reliable comfort year-round.

The unit's advanced controls use a user-friendly interface that simplifies operation and monitoring. These controls can be integrated with building management systems (BMS), allowing for seamless connectivity and enhanced control over the HVAC system. With the capability for remote monitoring, facility managers can track performance metrics and receive alerts for maintenance, ensuring that the unit operates efficiently and minimizes downtime.

In terms of design, the PKGP-PRC003-EN is equipped with durable construction materials that withstand outdoor environments, ensuring a long lifespan with minimal maintenance. The unit’s compact footprint allows it to fit in tight spaces on rooftops, making it an ideal choice for urban environments where space is limited.

Furthermore, the Trane PKGP-PRC003-EN incorporates advanced filtration systems to improve indoor air quality. These filters effectively capture dust, pollen, and other allergens, contributing to a healthier indoor environment. The unit is also designed with sound attenuation features, minimizing operational noise, which is particularly beneficial for installations in noise-sensitive areas.

Overall, the Trane PKGP-PRC003-EN sets a high standard in the realm of rooftop HVAC solutions. Its combination of energy efficiency, smart control capabilities, and robust construction makes it a reliable choice for businesses looking to enhance their indoor climate while being mindful of operational costs. The integration of advanced technologies ensures that it not only meets but exceeds the expectations of modern HVAC performance, all while maintaining user-friendly operation and maintenance.