GAS SUPPLY

 

 

c). If the remote LP cylinder enclosure has four sides, a top and a bottom, and is intended for installation in a built-in “island” enclosure;

1). At least one ventilation opening (a hole or group of holes, for the purpose of ventilation) needs to be on one side of the enclosure that communicates with the outside of the “island” structure. If a gas leak should occur or the LP cylinder should vent in the LP cylinder enclosure, the gas should not be allowed to vent or migrate into the empty or “hollow” area of the “island”. Ventilation openings should only communicate with the outside of the “island” structure, so that the gas can dissipate outside of the “island” structure. The ventilation opening should be located within 5 inches (127mm) of the top of the enclosure, and should have a total free area of 20 square inches. (This relates to 1 square inch of ventilation area, per pound of stored fuel).

2). At least one ventilation opening (a hole or group of holes, for the purpose of ventilation) needs to be on one side of the enclosure that communicates with the outside of the “island” structure, at the bottom. If a gas leak should occur or the LP cylinder should vent in the LP cylinder enclosure, the gas should not be allowed to vent or migrate into the empty or “hollow” area of the “island”. Ventilation openings should only communicate with the outside of the “island” structure, so that the gas can dissipate outside of the “island” structure. The ventilation opening should be located within 5 inches (127mm) of the bottom of the enclosure, and should have a total free area of 10 square inches. (This relates to 1/4 square inch of ventilation area, per pound of stored fuel).

3). The minimum size of the ventilation hole (s) should not be less than 1/4 inch (6.35mm).

d). The remote LP cylinder enclosure should be constructed with non-combustible materials. The remote LP cylinder enclosure should isolate the LP cylinder from the burner compartment, so that it provides shielding from radiation, be a fl ame barrier and provide protection from foreign material such as hot drippings.

e). There should be a minimum of 2 inches (50.8mm) between the ground and the fl oor of the remote LP cylinder enclosure.

f). The LP cylinder valve should be readily accessible for hand operation. A door on the remote LP cylinder enclosure to gain access to the LP cylinder valve is acceptable, provided it is non-locking and can be opened without the use of tools.

DANGER

Use of any other hose and regulator assembly could be dangerous, and may not provide adequate gas supply to the Summit® Built-In gas grill, and could result in a fire or an explosion causing serious bodily injury or death, and damage to property.

DANGER

Failure to use the Summit® Built-In Tank Cabinet for a 20 lb cylinder or failure to build a LP cylinder enclosure for a 20 lb cylinder following the requirements for ventilation, cylinder retention and separation of the LP cylinder from a heat source, listed in the ANSI Standard for Outdoor Cooking Gas Appliances, ANSI Z21.58 CSA 1.6, could be dangerous, and could result in a fire or an explosion causing serious bodily injury or death and damage to property.

If you do not follow the DANGER statements exactly, the Warranty on the Summit® Built- In gas grill will be voided.

BUILT-IN TANK ENCLOSURE INSTRUCTIONS

OPERATING

WARNING: Only use the Weber® Tank Enclosure Kit outdoors in a well-ventilated area. Do not use in a garage, building, breezeway or any other enclosed area.

WARNING: Your Weber® Tank Enclosure Kit shall not be used under an unprotected combustible roof or overhang. WARNING: Your Weber® Tank Enclosure Kit is not intended to be installed in or on recreational vehicles and/or boats. WARNING: Keep any electrical supply cord and the fuel supply hose away from any heated surface.

WARNING: Never store an extra (spare) LP cylinder under or near the Weber® gas barbecue.

WARNING: Keep the ventilation openings of the cylinder enclosure free and clear of debris.

WARNING: Turn off the gas at the LP gas supply cylinder when the outdoor cooking gas appliance is not in use. WARNING: Never store an outdoor cooking gas appliance indoors unless the LP cylinder is disconnected and removed from the outdoor cooking gas appliance.

WARNING: LP Cylinders must be stored outdoors out of the reach of children and must not be stored in a building, garage, or any other enclosed area.

WARNING: The LP pressure regulator and hose assembly supplied with the Weber® Tank Enclosure Kit must be used. Replacement LP pressure regulators and hoses must be obtained from Weber-Stephen Product Co.

WWW.WEBER.COM®

Image 22
Contents GAS Grill Locating Your Grill BUILT-IN Cutout Dimensions2WARNINGS Clearance from Surfaces or StructuresTolerances General Construction DetailsParts List 640440 640 Assembly ASSEMBLY7 8ASSEMBLY Assembly Inch overhang. Notch front edge for frame to fully slide ASSEMBLY11 6.35 mm Drill Bit12ASSEMBLY ASSEMBLY13 S440 S640 S440 Assembly S440 S640 440 ASSEMBLY19 GAS Supply General Specifications for PipingDimensions Silver Gold TolerancesGAS Line Piping Typical 20 LP Propane GAS Supply InstallationTest Connections BUILT-IN Tank Enclosure Instructions OperatingLocating Your LP Tank Enclosure KIT General InstructionsClearance from Combustible Surfaces or Structures Parts List / Assembly Parts ListASSEMBLY25 Mounting the LP Tank BracketConnection Chart Connect GAS SupplyVentilation WEBER-STEPHEN Products CO