10.1.4Outdoor Unit

10.1.4.1Install the Outdoor Unit

After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram. 1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø13/32”).

2 When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails.

Model

A

B

C

D

S9NKUW-1,

22 7/16”

4 1/8”

23/32”

12 19/32”

S12NKUW-1

 

 

 

 

10.1.4.2Connect the Piping

10.1.4.2.1Connecting the piping to indoor

Please make flare after inserting flare nut (locate at joint portion of tube assembly) onto the copper pipe. (In case of using long piping)

Connect the piping

Align the center of piping and sufficiently tighten the flare nut with fingers.

Further tighten the flare nut with torque wrench in specified torque as stated in the table.

10.1.4.2.2Connecting the piping to outdoor

Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge.

Make flare after inserting the flare nut (locate at valve) onto the copper pipe.

Align center of piping to valve and then tighten with torque wrench to the specified torque as stated in the table.

Do not over tighten, over tightening may cause gas leakage.

Piping size

Torque

1/4”

13.3 lbf.ft

3/8”

31.0 lbf.ft

1/2”

40.6 lbf.ft

5/8”

47.9 lbf.ft

3/4”

73.8 lbf.ft

10.1.4.2.3Connecting the piping to outdoor multi

Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut (locate at valve) onto the copper pipe.

Align center of piping to valve and then tighten with torque wrench to the specified torque as stated in the table.

36

Image 36
Contents Indoor Unit Outdoor Unit CU-S12NKU-1CS-S18NKU-1 CU-S18NKU-1 CS-S22NKU-1 CU-S22NKU-1 Table of Contents Safety Precautions Items to be followed are classified by the symbolsPage Specification CU-S9NKU-1 CU-S12NKU-1 ARIDRY Bulb WET Bulb CS-S18NKU-1 CS-S22NKU-1 Piping Indoor Unit Outdoor Unit Remote Control Location of Controls and ComponentsDimensions Indoor UnitCS-S9NKUW-1 CS-S12NKUW-1 CS-S18NKU-1 CS-S22NKU-1 CU-S9NKU-1 CU-S12NKU-1 CU-S18NKU-1 CU-S22NKU-1 Refrigeration Cycle Diagram CS-S18NKU-1 CU-S18NKU-1 CS-S22NKU-1 CU-S22NKU-1 Block Diagram CS-S18NKU-1 CU-S18NKU-1 CS-S22NKU-1 CU-S22NKU-1 Wiring Connection Diagram CS-S18NKU-1 CS-S22NKU-1 CU-S9NKU-1 CU-S12NKU-1 CU-S18NKU-1 CU-S22NKU-1 Electronic Circuit Diagram CS-S18NKU-1 CS-S22NKU-1 Outdoor Unit CU-S18NKU-1 CU-S22NKU-1 Printed Circuit Board Main Printed Circuit BoardPower Printed Circuit Board Indicator Printed Circuit Board CU-S9NKU-1 CU-S12NKU-1 CU-S18NKU-1 CU-S22NKU-1 Installation Instruction Indoor/Outdoor Unit Installation Diagram10.1 S9NKUW-1 S12NKUW-1 Select the Best LocationHow to Fix Installation Plate Indoor Unit This can be used for left rear piping and bottom piping also Connect the Cable to the Indoor Unit Page Install the Outdoor Unit Outdoor UnitGas leak checking Piping Insulation 10.2 S18NKU-1 S22NKU-1 How to Fix Installation Plate This can be used for left rear piping and bottom piping also Connect the Cable to the Indoor Unit Page Model S18NKU-1 Evacuation of the equipment Piping Insulation Internal Setting Temperature Operation ControlBasic Function Cooling OperationIndoor Fan Motor Operation Outdoor Fan Motor Operation For S9NK and S12NKOutdoor Fan Motor Operation For S18NK and S22NK Airflow DirectionQuiet Operation Cooling Mode/Cooling Area of Dry Mode 11.5.1 Vertical AirflowHorizontal Airflow Powerful Mode Operation Timer ControlOn Timer Control OFF Timer ControlLED Power Timer Quiet Powerful Indication PanelRestart Control Time Delay Safety Control IPM Power Transistor Prevention ControlProtection Control 12.2 30 Seconds Forced OperationLow Pressure Protection Control Gas Leakage Detection Low Frequency Protection Control12.4.2 S18NK, S22NK Outdoor Air Temperature Control Cooling Overload ControlFreeze Prevention Control Dew Prevention ControlServicing Mode Auto Off/On ButtonRemote Control Button Reset RCReset AC TimerTroubleshooting Guide Refrigeration Cycle SystemCondition Cooling Mode Air conditioner To Display Memorized Error Code Protective Operation Breakdown Self Diagnosis FunctionSelf Diagnosis Function Three Digits Alphanumeric Code To Make a DiagnosisError Code Table Abnormality / Protection controlTroubleshooting Flowchart 14.4.1 H11 Indoor/Outdoor Abnormal Communication14.4.2 H12 Indoor/Outdoor Capacity Rank Mismatched 14.4.3 H14 Indoor Intake Air Temperature Sensor Abnormality 14.4.4 H15 Compressor Temperature Sensor Abnormality 14.4.5 H16 Outdoor Current Transformer Open Circuit 14.4.6 H19 Indoor Fan Motor DC Motor Mechanism Locked 14.4.7 H23 Indoor Pipe Temperature Sensor Abnormality 14.4.8 H27 Outdoor Air Temperature Sensor Abnormality 14.4.9 H28 Outdoor Pipe Temperature Sensor Abnormality Malfunction Decision Conditions 14.4.11 H33 Unspecified Voltage between Indoor and Outdoor 14.4.12 H97 Outdoor Fan Motor DC Motor Mechanism Locked 14.4.13 H98 Indoor High Pressure Protection Malfunction Decision Conditions 14.4.15 F11 Indoor Pipe Temperature Sensor Abnormality 14.4.16 F90 Power Factor Correction Protection 14.4.17 F91 Refrigeration Cycle Abnormality 14.4.18 F93 Compressor Rotation Failure 14.4.19 F95 Cooling High Pressure Abnormality 14.4.20 F96 IPM Overheating 14.4.21 F97 Compressor Overheating 14.4.22 F98 Input Over Current Detection 14.4.23 F99 Output Over Current Detection Disassembly and Assembly Instructions To remove front grilleTo remove discharge grille Page Page Technical Data Operation CharacteristicsCS-S9NKUW-1 CU-S9NKU-1 Page CS-S12NKUW-1 CU-S12NKU-1 Page CS-S18NKU-1 CU-S18NKU-1 Page CS-S22NKU-1 CU-S22NKU-1 Page Exploded View and Replacement Parts List CS-S12NKUW-1 Remark CS-S18NKU-1 CS-S22NKU-1 CS-S22NKU-1 Remark Outdoor Unit CU-S12NKU-1 Remark CU-S18NKU-1 CU-S22NKU-1 CU-S22NKU-1 Remark