Panasonic CU-S9NKU-1, CS-S18NKU-1, CS-S12NKUW-1 Error Code Table, Abnormality / Protection control

Page 60

14.3

Error Code Table

 

 

Diagnosis

Abnormality / Protection control

Abnormality Judgment

Emergency

display

Operation

 

 

H00

 

No abnormality detected

-

Normal operation

H11

 

Indoor / Outdoor abnormal

> 1 min after starting

Indoor fan operation

 

communication

operation

only

 

 

H12

 

Connection capability rank abnormality

Continuously for 90 sec

-

 

after power supplied

 

 

 

 

H14

 

Indoor intake air temperature sensor

Continue for 5 sec.

-

 

abnormality

 

 

 

 

H15

 

Outdoor compressor temperature sensor

Continue for 5 sec.

-

 

abnormality

 

 

 

 

H16

 

Outdoor current transformer open circuit

-

-

 

 

 

 

 

H19

 

Indoor fan motor mechanism locked

7 occurrences

-

 

continuously

 

 

 

 

H23

 

Indoor heat exchanger temperature

Continue for 5 sec.

 

sensor abnormality

 

 

 

 

 

H27

 

Outdoor air temperature sensor

Continue for 5 sec.

 

abnormality

 

 

 

 

 

H28

 

Outdoor heat exchanger temperature

Continue for 5 sec.

 

sensor abnormality

 

 

 

 

 

 

 

 

 

 

H30

 

Discharge temperature sensor

Continue for 5 sec.

 

 

abnormality

 

 

 

 

 

H33

 

Indoor / outdoor wrong connection

-

-

H38

 

Indoor / outdoor mismatch (brand code)

-

-

H64

 

Outdoor high pressure sensor

Continue for 1 minutes

-

 

abnormality

 

 

 

 

H97

 

Outdoor fan lock abnormality

2 occurrences within 30

 

 

 

minutes

 

 

 

 

 

H98

 

Indoor temperature rise abnormality

-

-

 

 

 

 

 

H99

 

Indoor heat exchanger freeze prevention

-

-

 

protection

 

 

 

 

F11

 

4 way valve switching failure *

4 occurrences within 30

-

 

minutes

 

 

 

 

F17

 

Indoor standby units freezing abnormality

3 times happen within

-

 

40 minutes

 

 

 

 

 

 

 

 

 

F90

 

System and compressor microcomputer

2 occurrences within 5

-

 

communication error(for S10*** only)

seconds

 

 

 

F90

 

Power factor correction abnormality

4 occurrences within 20

-

 

minutes

 

 

 

 

F91

 

Refrigerant cycle abnormal

2 occurrences within 20

-

 

minutes

 

 

 

 

F93

 

Outdoor compressor abnormal revolution

4 occurrences within 20

-

 

minutes

 

 

 

 

F95

 

Cooling high pressure protection

4 occurrences within 20

-

 

minutes

 

 

 

 

F96

 

Intelligent power transistor overheating

-

-

 

protection

 

 

 

 

 

 

 

 

 

F97

 

Compressor temperature rise protection

4 times occurrence within

-

 

control

20 minutes

 

 

 

F98

 

Total running current protection

3 times occurrence within

-

 

20 minutes

 

 

 

 

F99

 

Outdoor direct current (DC) peak

7 times occurrence

-

 

detection

continuously

 

 

 

 

 

 

 

 

Primary location to verify

Internal / external cable connection

Indoor / outdoor PCB

-

Intake air temperature sensor (defective or disconnected)

Compressor temperature sensor (defective or disconnected)

Outdoor PCB

IPM (Power transistor) module

Indoor PCB

Fan motor

Heat exchanger temperature sensor (defective or disconnected)

Outdoor temperature sensor (defective or disconnected)

Outdoor heat exchanger temperature sensor (defective or disconnected)

Outdoor discharge temperature sensor (defective or disconnected)

Indoor / outdoor supply voltage

-

High pressure sensor

Lead wire and connector

Outdoor fan motor locked

Air filter dirty

Air circulation short circuit

Insufficient refrigerant

Air filter dirty

4-way valve

v-coil

Check indoor/outdoor connection wire and pipe

Indoor heat exchanger sensor lead wire and connector

Expansion valve lead wire and connector.

Compressor

Outdoor PCB

Outdoor PCB

No refrigerant ( 3-way valve is closed)

Outdoor compressor

Outdoor refrigerant circuit

Excess refrigerant

Improper heat radiation

IPM (Power transistor)

Insufficient refrigerant

Compressor

Excess refrigerant

Improper heat radiation

Outdoor PCB

IPM (Power transistor)

Compressor

Note:

“○” – Frequency measured and fan speed fixed

* ”– For cooling only model, it is the indication when indoor heat exchanger sensor or indoor air intake sensor has abnormality.

The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard following by pressing the CHECK button at remote control.

Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error Code Table) by using remote control or Auto OFF/ON button at indoor unit. However, the remote control signal receiving sound is changed from one “beep” to four “beep” sounds.

60

Image 60
Contents Indoor Unit Outdoor Unit CU-S12NKU-1CS-S18NKU-1 CU-S18NKU-1 CS-S22NKU-1 CU-S22NKU-1 Table of Contents Safety Precautions Items to be followed are classified by the symbolsPage Specification CU-S9NKU-1 CU-S12NKU-1 ARIDRY Bulb WET Bulb CS-S18NKU-1 CS-S22NKU-1 Piping Indoor Unit Outdoor Unit Remote Control Location of Controls and ComponentsDimensions Indoor UnitCS-S9NKUW-1 CS-S12NKUW-1 CS-S18NKU-1 CS-S22NKU-1 CU-S9NKU-1 CU-S12NKU-1 CU-S18NKU-1 CU-S22NKU-1 Refrigeration Cycle Diagram CS-S18NKU-1 CU-S18NKU-1 CS-S22NKU-1 CU-S22NKU-1 Block Diagram CS-S18NKU-1 CU-S18NKU-1 CS-S22NKU-1 CU-S22NKU-1 Wiring Connection Diagram CS-S18NKU-1 CS-S22NKU-1 CU-S9NKU-1 CU-S12NKU-1 CU-S18NKU-1 CU-S22NKU-1 Electronic Circuit Diagram CS-S18NKU-1 CS-S22NKU-1 Outdoor Unit CU-S18NKU-1 CU-S22NKU-1 Printed Circuit Board Main Printed Circuit BoardPower Printed Circuit Board Indicator Printed Circuit Board CU-S9NKU-1 CU-S12NKU-1 CU-S18NKU-1 CU-S22NKU-1 Installation Instruction Indoor/Outdoor Unit Installation Diagram10.1 S9NKUW-1 S12NKUW-1 Select the Best LocationHow to Fix Installation Plate Indoor UnitThis can be used for left rear piping and bottom piping also Connect the Cable to the Indoor Unit Page Install the Outdoor Unit Outdoor UnitGas leak checking Piping Insulation 10.2 S18NKU-1 S22NKU-1 How to Fix Installation Plate This can be used for left rear piping and bottom piping also Connect the Cable to the Indoor Unit Page Model S18NKU-1 Evacuation of the equipment Piping Insulation Internal Setting Temperature Operation ControlBasic Function Cooling OperationIndoor Fan Motor Operation Outdoor Fan Motor Operation For S9NK and S12NKOutdoor Fan Motor Operation For S18NK and S22NK Airflow DirectionQuiet Operation Cooling Mode/Cooling Area of Dry Mode 11.5.1 Vertical AirflowHorizontal Airflow Powerful Mode Operation Timer ControlOn Timer Control OFF Timer ControlLED Power Timer Quiet Powerful Indication PanelRestart Control Time Delay Safety Control IPM Power Transistor Prevention ControlProtection Control 12.2 30 Seconds Forced OperationLow Pressure Protection Control Gas Leakage Detection Low Frequency Protection Control12.4.2 S18NK, S22NK Outdoor Air Temperature Control Cooling Overload ControlFreeze Prevention Control Dew Prevention ControlServicing Mode Auto Off/On ButtonRemote Control Button Reset RCReset AC Timer Troubleshooting Guide Refrigeration Cycle SystemCondition Cooling Mode Air conditioner To Display Memorized Error Code Protective Operation Breakdown Self Diagnosis FunctionSelf Diagnosis Function Three Digits Alphanumeric Code To Make a DiagnosisError Code Table Abnormality / Protection controlTroubleshooting Flowchart 14.4.1 H11 Indoor/Outdoor Abnormal Communication14.4.2 H12 Indoor/Outdoor Capacity Rank Mismatched 14.4.3 H14 Indoor Intake Air Temperature Sensor Abnormality 14.4.4 H15 Compressor Temperature Sensor Abnormality 14.4.5 H16 Outdoor Current Transformer Open Circuit 14.4.6 H19 Indoor Fan Motor DC Motor Mechanism Locked 14.4.7 H23 Indoor Pipe Temperature Sensor Abnormality 14.4.8 H27 Outdoor Air Temperature Sensor Abnormality 14.4.9 H28 Outdoor Pipe Temperature Sensor Abnormality Malfunction Decision Conditions 14.4.11 H33 Unspecified Voltage between Indoor and Outdoor 14.4.12 H97 Outdoor Fan Motor DC Motor Mechanism Locked 14.4.13 H98 Indoor High Pressure Protection Malfunction Decision Conditions 14.4.15 F11 Indoor Pipe Temperature Sensor Abnormality 14.4.16 F90 Power Factor Correction Protection 14.4.17 F91 Refrigeration Cycle Abnormality 14.4.18 F93 Compressor Rotation Failure 14.4.19 F95 Cooling High Pressure Abnormality 14.4.20 F96 IPM Overheating 14.4.21 F97 Compressor Overheating 14.4.22 F98 Input Over Current Detection 14.4.23 F99 Output Over Current Detection Disassembly and Assembly Instructions To remove front grilleTo remove discharge grille Page Page Technical Data Operation CharacteristicsCS-S9NKUW-1 CU-S9NKU-1 Page CS-S12NKUW-1 CU-S12NKU-1 Page CS-S18NKU-1 CU-S18NKU-1 Page CS-S22NKU-1 CU-S22NKU-1 Page Exploded View and Replacement Parts List CS-S12NKUW-1 Remark CS-S18NKU-1 CS-S22NKU-1 CS-S22NKU-1 Remark Outdoor Unit CU-S12NKU-1 Remark CU-S18NKU-1 CU-S22NKU-1 CU-S22NKU-1 Remark