Panasonic CU-S9NKU-1, CS-S18NKU-1, CS-S12NKUW-1, CS-S22NKU-1, CS-S9NKUW-1, CU-S12NKU-1, CU-S22NKU-1

Page 4

WARNING

During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refrigeration

19.piping and valves at opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.).

During pump down operation, stop the compressor before remove the refrigeration piping. (Removal of refrigeration piping while

20.compressor is operating and valves are opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.)..

21.After completion of installation or service, confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant contacts with fire.

22.Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fire.

23. Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury

24.Must not use other parts except original parts describe in catalog and manual.

25.Using of refrigerant other than the specified type may cause product damage, burst and injury etc.

CAUTION

1.Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire.

2.Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.

3.Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may break and cause refrigerant gas leakage.

4. Do not touch outdoor unit air inlet and aluminium fin. It may cause injury.

5.Select an installation location which is easy for maintenance.

Pb free solder has a higher melting point than standard solder; typically the melting point is 50°F – 70°F (30°C – 40°C) higher. Please use

6.a high temperature solder iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C). Pb free solder will tend to splash when heated too high (about 1100°F / 600°C).

Power supply connection to the air conditioner. Connect the power supply cord of the air conditioner to the mains using one of the following methods.

Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency. In some countries, permanent connection of this room air conditioner to the power supply is prohibited.

7.i. Power supply connection to the receptacle using a power plug.

Use an approved 15/16A (1.0 ~ 1.75HP) or 16A (2.0HP) or 20A (2.5HP), power plug with earth pin for the connection to the socket.

ii.Power supply connection to a circuit breaker for the permanent connection.

Use an approved 16A (1.0 ~ 2.0HP) or 20A (2.5HP), circuit breaker for the permanent connection. It must be a double pole switch with a minimum 3.0 mm contact gap.

8.Do not release refrigerant during piping work for installation, servicing, reinstallation and during repairing a refrigerant parts. Take care of the liquid refrigerant, it may cause frostbite.

9.Installation or servicing work: It may need two people to carry out the installation or servicing work.

10. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.

11. Do not sit or step on the unit, you may fall down accidentally.

12. Do not touch the sharp aluminum fins , sharp parts may cause injury.

4

Image 4
Contents CU-S12NKU-1 Indoor Unit Outdoor UnitCS-S18NKU-1 CU-S18NKU-1 CS-S22NKU-1 CU-S22NKU-1 Table of Contents Safety Precautions Items to be followed are classified by the symbolsPage Specification CU-S9NKU-1 CU-S12NKU-1 ARIDRY Bulb WET Bulb CS-S18NKU-1 CS-S22NKU-1 Piping Indoor Unit Outdoor Unit Remote Control Location of Controls and ComponentsIndoor Unit DimensionsCS-S9NKUW-1 CS-S12NKUW-1 CS-S18NKU-1 CS-S22NKU-1 CU-S9NKU-1 CU-S12NKU-1 CU-S18NKU-1 CU-S22NKU-1 Refrigeration Cycle Diagram CS-S18NKU-1 CU-S18NKU-1 CS-S22NKU-1 CU-S22NKU-1 Block Diagram CS-S18NKU-1 CU-S18NKU-1 CS-S22NKU-1 CU-S22NKU-1 Wiring Connection Diagram CS-S18NKU-1 CS-S22NKU-1 CU-S9NKU-1 CU-S12NKU-1 CU-S18NKU-1 CU-S22NKU-1 Electronic Circuit Diagram CS-S18NKU-1 CS-S22NKU-1 Outdoor Unit CU-S18NKU-1 CU-S22NKU-1 Printed Circuit Board Main Printed Circuit BoardPower Printed Circuit Board Indicator Printed Circuit Board CU-S9NKU-1 CU-S12NKU-1 CU-S18NKU-1 CU-S22NKU-1 Installation Instruction Indoor/Outdoor Unit Installation Diagram10.1 S9NKUW-1 S12NKUW-1 Select the Best LocationHow to Fix Installation Plate Indoor UnitThis can be used for left rear piping and bottom piping also Connect the Cable to the Indoor Unit Page Install the Outdoor Unit Outdoor UnitGas leak checking Piping Insulation 10.2 S18NKU-1 S22NKU-1 How to Fix Installation Plate This can be used for left rear piping and bottom piping also Connect the Cable to the Indoor Unit Page Model S18NKU-1 Evacuation of the equipment Piping Insulation Internal Setting Temperature Operation ControlBasic Function Cooling OperationIndoor Fan Motor Operation Outdoor Fan Motor Operation For S9NK and S12NKOutdoor Fan Motor Operation For S18NK and S22NK Airflow Direction11.5.1 Vertical Airflow Quiet Operation Cooling Mode/Cooling Area of Dry ModeHorizontal Airflow Powerful Mode Operation Timer ControlOn Timer Control OFF Timer ControlLED Power Timer Quiet Powerful Indication PanelRestart Control Time Delay Safety Control IPM Power Transistor Prevention ControlProtection Control 12.2 30 Seconds Forced OperationLow Frequency Protection Control Low Pressure Protection Control Gas Leakage Detection12.4.2 S18NK, S22NK Outdoor Air Temperature Control Cooling Overload ControlFreeze Prevention Control Dew Prevention ControlServicing Mode Auto Off/On ButtonRemote Control Button Reset RCReset AC TimerTroubleshooting Guide Refrigeration Cycle SystemCondition Cooling Mode Air conditioner To Display Memorized Error Code Protective Operation Breakdown Self Diagnosis FunctionSelf Diagnosis Function Three Digits Alphanumeric Code To Make a DiagnosisError Code Table Abnormality / Protection controlTroubleshooting Flowchart 14.4.1 H11 Indoor/Outdoor Abnormal Communication14.4.2 H12 Indoor/Outdoor Capacity Rank Mismatched 14.4.3 H14 Indoor Intake Air Temperature Sensor Abnormality 14.4.4 H15 Compressor Temperature Sensor Abnormality 14.4.5 H16 Outdoor Current Transformer Open Circuit 14.4.6 H19 Indoor Fan Motor DC Motor Mechanism Locked 14.4.7 H23 Indoor Pipe Temperature Sensor Abnormality 14.4.8 H27 Outdoor Air Temperature Sensor Abnormality 14.4.9 H28 Outdoor Pipe Temperature Sensor Abnormality Malfunction Decision Conditions 14.4.11 H33 Unspecified Voltage between Indoor and Outdoor 14.4.12 H97 Outdoor Fan Motor DC Motor Mechanism Locked 14.4.13 H98 Indoor High Pressure Protection Malfunction Decision Conditions 14.4.15 F11 Indoor Pipe Temperature Sensor Abnormality 14.4.16 F90 Power Factor Correction Protection 14.4.17 F91 Refrigeration Cycle Abnormality 14.4.18 F93 Compressor Rotation Failure 14.4.19 F95 Cooling High Pressure Abnormality 14.4.20 F96 IPM Overheating 14.4.21 F97 Compressor Overheating 14.4.22 F98 Input Over Current Detection 14.4.23 F99 Output Over Current Detection Disassembly and Assembly Instructions To remove front grilleTo remove discharge grille Page Page Operation Characteristics Technical DataCS-S9NKUW-1 CU-S9NKU-1 Page CS-S12NKUW-1 CU-S12NKU-1 Page CS-S18NKU-1 CU-S18NKU-1 Page CS-S22NKU-1 CU-S22NKU-1 Page Exploded View and Replacement Parts List CS-S12NKUW-1 Remark CS-S18NKU-1 CS-S22NKU-1 CS-S22NKU-1 Remark Outdoor Unit CU-S12NKU-1 Remark CU-S18NKU-1 CU-S22NKU-1 CU-S22NKU-1 Remark
Related manuals
Manual 103 pages 20.36 Kb

CS-S9NKUW-1, CS-S22NKU-1, CU-S18NKU-1, CS-S18NKU-1, CS-S12NKUW-1 specifications

Panasonic has long been a leader in the HVAC industry, and its latest range of air conditioning units—including the CU-S9NKU-1, CU-S12NKU-1, CU-S22NKU-1, CS-S12NKUW-1, and CS-S18NKU-1—showcases innovative features and robust technologies designed to enhance home comfort while reducing energy consumption.

The CU-S9NKU-1 model is notable for its compact design, making it ideal for smaller spaces without sacrificing performance. It boasts advanced inverter technology, enabling precise temperature control and energy efficiency. The built-in air purification system ensures that indoor air quality remains high, filtering out allergens and pollutants.

Similarly, the CU-S12NKU-1 variant provides a balance of power and efficiency for medium-sized rooms. This model incorporates a quiet operation feature, making it a perfect choice for bedrooms and living areas where noise levels need to be minimized. The adjustable airflow louvers ensure that air is distributed evenly throughout the space.

For larger spaces, the CU-S22NKU-1 stands out with its high cooling and heating capacity. This model is equipped with a dual inverter compressor that enhances both efficiency and performance, providing rapid cooling or heating when needed. The user-friendly remote control and smart connectivity options allow homeowners to adjust settings conveniently, even when they’re away from home.

The CS-S12NKUW-1 model features a sleek design and additional functionalities like the Eco Mode and Sleep Mode. Eco Mode adjusts the power consumption based on the user’s preferences, while Sleep Mode operates at low noise levels, promoting a restful environment during nighttime hours.

Lastly, the CS-S18NKU-1 combines innovative technology with aesthetic appeal. Its modern design is meant to complement contemporary interiors, and its high seasonal energy efficiency ratio (SEER) indicates strong performance in cooling seasons. Additionally, this model includes several energy-saving modes that adapt to changing thermal loads, ensuring that energy wastage is minimized.

Overall, Panasonic’s CU and CS series air conditioning units offer an impressive blend of technology and design, making them suitable for various needs and spaces while focusing on energy efficiency and user comfort. Whether for residential or light commercial use, these models provide reliable, effective solutions for climate control.