15.3.Error Codes Table
Diagnosis | Abnormality / | Abnormality | Protection | Problem | Check location | |
display | Protection control | Judgement | operation | |||
|
| |||||
|
|
|
|
|
| |
H00 | No memory of failure | — | Normal operation | — | — | |
|
|
|
|
|
| |
H11 | Indoor/outdoor | After operation for | Indoor fan only | Indoor/outdoor | • Indoor/outdoor wire terminal | |
| abnormal | 1 minute | operation can | communication not establish | • Indoor/outdoor PCB | |
| communication |
| start by entering |
| • Indoor/outdoor connection wire | |
|
|
| into force cooling |
|
| |
|
|
| operation |
|
| |
|
|
|
|
|
| |
H14 | Indoor intake air | Continuous for 5s | — | Indoor intake air temperature | • Indoor intake air temperature | |
| temperature sensor |
|
| sensor open or short circuit | sensor lead wire and connector | |
| abnormality |
|
|
|
| |
|
|
|
|
|
| |
H15 | Compressor | Continuous for 5s | — | Compressor temperature | • Compressor temperature sensor | |
| temperature sensor |
|
| sensor open or short circuit | lead wire and connector | |
| abnormality |
|
|
|
| |
|
|
|
|
|
| |
H16 | Outdoor current | — | — | Current transformer faulty or | • Outdoor PCB faulty or | |
| transformer (CT) |
|
| compressor faulty | compressor faulty | |
| abnormality |
|
|
|
| |
|
|
|
|
|
| |
H19 | Indoor fan motor | Continuous | — | Indoor fan motor lock or | • Fan motor lead wire and | |
| merchanism lock | happen for 7 times |
| feedback abnormal | connector | |
|
|
|
|
| • Fan motor lock or block | |
|
|
|
|
|
| |
H23 | Indoor heat exchanger | Continuous for 5s | — | Indoor heat exchanger | • Indoor heat exchanger | |
| temperature sensor |
|
| temperature sensor open or | temperature sensor lead wire and | |
| abnormality |
|
| short circuit | connector | |
|
|
|
|
|
| |
H27 | Outdoor air temperature | Continuous for 5s | — | Outdoor air temperature | • Outdoor air temperature sensor | |
| sensor abnormality |
|
| sensor open or short circuit | lead wire and connector | |
|
|
|
|
|
| |
H28 | Outdoor heat exchanger | Continuous for 5s | — | Outdoor heat exchanger | • Outdoor heat exchanger | |
| temperature sensor 1 |
|
| temperature sensor 1 open | temperature sensor 1 lead wire | |
| abnormality |
|
| or short circuit | and connector | |
|
|
|
|
|
| |
H30 | Outdoor discharge pipe | Continuous for 5s | — | Outdoor discharge pipe | • Outdoor discharge pipe | |
| temperature sensor |
|
| temperature sensor open or | temperature sensor lead wire and | |
| abnormality |
|
| short circuit | connector | |
|
|
|
|
|
| |
H33 | Indoor / outdoor | — | — | Indoor and outdoor rated | • Indoor and outdoor units check | |
| misconnection |
|
| voltage different |
| |
| abnormality |
|
|
|
| |
|
|
|
|
|
| |
H38 | Indoor/Outdoor | — | — | Brand code not match | • Check indoor unit and outdoor | |
| mismatch (brand code) |
|
|
| unit. | |
|
|
|
|
|
| |
H97 | Outdoor fan motor | 2 times happen | — | Outdoor fan motor lock or | • Outdoor fan motor lead wire and | |
| mechanism lock | within 30 minutes |
| feedback abnormal | connector | |
|
|
|
|
| • Fan motor lock or block | |
|
|
|
|
|
| |
H98 | Indoor high pressure | — | — | Indoor high pressure | • Check indoor heat exchanger | |
| protection |
|
| protection (Heating) | • Air filter dirty | |
|
|
|
|
| • Air circulation short circuit | |
|
|
|
|
|
| |
H99 | Indoor operating unit | — | — | Indoor freeze protection | • Check indoor heat exchanger | |
| freeze protection |
|
| (Cooling) | • Air filter dirty | |
|
|
|
|
| • Air circulation short circuit | |
|
|
|
|
|
| |
F11 | 4 times happen | — | • | |||
| abnormality | within 30 minutes |
| abnormal | • Lead wire and connector. | |
|
|
|
|
|
| |
F90 | Power factor correction | 4 times happen | — | Power factor correction | • Outdoor PCB faulty | |
| (PFC) circuit protection | within 10 minutes |
| circuit abnormal |
| |
|
|
|
|
|
| |
F91 | Refrigeration cycle | 2 times happen | — | Refrigeration cycle abnormal | • Insufficient refrigerant or valve | |
| abnormality | within 20 minutes |
|
| close | |
|
|
|
|
|
| |
F93 | Compressor abnormal | 4 times happen | — | Compressor abnormal | • Power transistor module faulty or | |
| revolution | within 20 minutes |
| revolution | compressor lock | |
|
|
|
|
|
| |
F95 | Outdoor cooling high | 4 times happen | — | Cooling high pressure | • Check refrigeration system | |
| pressure protection | within 20 minutes |
| protection | • Outdoor air circuit | |
|
|
|
|
|
| |
F96 | Power transistor module | 4 times happen | — | Power transistor module | • PCB faulty | |
| overheating protection | within 30 minutes |
| overheat | • Outdoor air circuit (fan motor) | |
|
|
|
|
|
|
43