Emerson Process Management 3051N manual Press Limit

Page 72

Rosemount 3051N

Reference Manual

00809-0100-4808, Rev CA June 2008

Some non-volatile memory faults are user-addressable. Use a HART Communicator to diagnose the error and determine if it is repairable. Any error message that ends in “FACTORY” is not repairable. In cases of non user-addressable errors, you must replace the transmitter. Contact Rosemount Nuclear Instruments Inc. at (952) 949-5210 if you need assistance.

 

FAIL ELECT

 

The transmitter electronics board is malfunctioning due to an internal fault.

 

Some of the FAIL ELECT errors are user-addressable. Use a HART

 

Communicator to diagnose the error and determine if it is repairable. Any

 

error message that ends in “FACTORY” is not repairable. In cases of non

 

user-repairable errors, you must replace the transmitter. Contact Rosemount

 

Nuclear Instruments, Inc. at (952) 949-5210 if you need assistance.

 

FAIL CONFIG

 

A memory fault has been detected in a location that could effect transmitter

 

operation, and is user-addressable. To correct this problem, use a HART

 

Communicator to interrogate and reconfigure the appropriate portion of the

 

transmitter memory. Contact Rosemount Nuclear Instruments, Inc. at

 

(952) 949-5210 if you need assistance.

Warnings

Warnings appear on the LCD meter display to alert you of user-repairable

 

problems with the transmitter, or current transmitter operations. Warnings

 

appear alternately with other transmitter information until the warning

 

condition is corrected or the transmitter completes the operation that warrants

 

the warning message.

 

PRESS LIMIT

 

The process variable read by the transmitter is outside of the transmitter’s

 

range.

 

TEMP LIMIT

 

The secondary temperature variable read by the transmitter is outside of the

 

transmitter’s range.

 

CURR SATURD

 

The pressure read by the module is outside of the specified range, and the

 

analog output has been driven to saturation levels. See “Failure Mode Alarm”

 

in Section 2.

 

LOOP TEST

 

A loop test is in progress. During a loop test or 4–20 mA trim, the analog

 

output is set to a fixed value. The meter display alternates between the

 

current selected in milliamps and “LOOP TEST.”

 

XMTR INFO

 

A non-volatile memory fault has been detected in the transmitter memory by

 

the memory verification routine. The memory fault is in a location containing

 

transmitter information. To correct this problem, use a HART Communicator to

 

interrogate and reconfigure the appropriate portion of the transmitter memory.

 

This warning does not effect the transmitter operation. Contact Rosemount

 

Nuclear Instruments Inc. at (952) 949-5210 if you need assistance.

6-6

Image 72
Contents Reference Manual Page Rosemount 3051N Return of Material Changes from June 2006 to June OldChanges Rosemount 3051N Table of Contents Installation TroubleshootingSpecifications Reference Data Options Appendix aHart Communicator Glossary Index Using this Manual Section IntroductionRosemount 3051N Overview Safety Messages Transmitter FunctionsAlarm Level Verification TransmitterSecurity Configuring Transmitter Alarm and Security Jumper Procedure Physical Removal Local Zero and Span Local KeysElectronics Board Setting the Loop to Manual Wiring Diagrams Bench Hook-up Wiring Diagrams Field Hook-up Review Configuration Data Check OutputProcess Variables Sensor Temperature Basic SetupSet Process Variable Units Set OutputRerange Rerange with a Communicator OnlyRerange with a Pressure Input Source and a Communicator Span and Zero Adjustment Buttons Detailed Setup Diagnostics ServiceTransmitter Test Loop TestCalibration Transmitter Bench Calibration Tasks Field Calibration Tasks Configure the Analog Output Parameters Calibration OverviewSensor Trim URVZero Trim Typical Zero vs Non-zero-Based Application IllustrationsFull Trim Digital Trim Connection Drawing 4-20 mA TransmittersDigital-to-Analog Trim Using Other Scale Recall Factory Trim Recall Factory Trim- Sensor TrimRecall Factory Trim- Analog Output Analog Output TrimZero Effect HTc = URV + S URV Ps Rosemount 3051N Section Installation Rosemount 3051N Typical Installation Flowchart General Considerations Special Draft Range ConsiderationsMechanical Considerations 156 181 16 x 11/4 Bolts for Mounting to 54.1 Transmitter 120 127 66.8 Traditional Flange Option Code H2 Dimensional Drawing Mounting Rosemount 3051N GAS or Liquid Service GAS Service Steam Service Process Connections Housing Rotation Power SupplyElectrical Considerations Wiring Power Supply Load LimitationsAccess Requirements Cover Installation Grounding the Transmitter CaseEnvironmental Considerations Troubleshooting Symptom Corrective Actions Returning Rosemount Products and MaterialsNuclear Specifications SeismicModel Range Code Hydrostatic Test Pressure Performance Specifications Ambient Temperature Effect12Reference Accuracy DriftPower Supply Effect Load Effect Mounting Position Effect Overpressure Effect Static Pressure EffectRange Code Overpressure Effect Range Code Static Pressure Zero Effect1Functional Specifications ServiceTemperature Limits OutputSpan and Zero, Zero Elevation, Suppression Range Minimum Span Upper URL Lower LRLRange Code Minimum Time Constant Tc Including Dead Time Td Maximum Working Pressure12Static Pressure Limits Overpressure Limits Burst PressurePhysical Specifications Materials of Construction Option Code Description Add Ordering Information Configuration Information Housing Material Conduit Entry SizeMounting Bracket Options Meters optionalDate  On Rosemount 3051N Exploded View with Coplanar Process Flange Rosemount 3051N Rosemount 3051N Overview Safety Messages LCD Meter Section OptionsCustom Meter Configuration Installing the Meter Exploded View of the Rosemount 3051N with Optional LCD MeterRosemount 3051N Diagnostic Messages ErrorPress Limit Operation Mounting BracketsTraditional Flange H2 Transient Protection Terminal Block T1Transient Protection Terminal Block T1 Rosemount 3051N Introduction Safety Messages Appendix a Hart CommunicatorRosemount 3051N Online Menu Function Hart Fast Key Sequence Figure A-3. Rosemount Hart terminal access door Connections and HardwareFigure A-4. Bench Hook-up MA Transmitters Rosemount Communicator KeysAction Keys Function Keys Alphanumeric and Shift KeysData Entry Fast Key Sequences Fast Key Sequence Conventions Fast Key Sequence ExampleMenus Functions Main MenuOnline Menu Touch Alphanumeric Keys Multifunction LEDTouch Screen Multifunction LED Processing IndicationRosemount 3051N Diagnostic Messages Fast Key Sequences Hot Key optionsMessage Description Rosemount 3051N Uploadvariable Rosemount 3051N Rosemount 3051N Glossary Smart Family Index 00809-0100-4808, Rev CA June Security Page ¢00809-0100-4801V¤

3051N specifications

The Emerson Process Management 3051N is a state-of-the-art pressure transmitter that exemplifies precision and reliability in process automation. Designed for a wide range of industrial applications, the 3051N is celebrated for its advanced features, innovative technologies, and robust construction, catering to the evolving needs of process industries.

One of the standout features of the 3051N is its exceptional accuracy. With a standard accuracy rating of ±0.075% of span, it ensures precise pressure measurements, critical for maintaining optimal process conditions. This high level of accuracy makes it suitable for applications in industries such as oil and gas, chemicals, and water treatment, where even minor deviations can lead to significant operational issues.

The 3051N employs Smart Pressure Technology, integrating digital communication capabilities with traditional analog systems. This technology allows for seamless interoperability with existing process control systems, providing users with vital data for diagnostics, calibration, and configuration via HART, FOUNDATION fieldbus, or Profibus protocols. These capabilities lead to enhanced process efficiency and reduced downtime due to effective predictive maintenance.

Another notable characteristic of this transmitter is its robust design. The 3051N is built to endure harsh industrial environments, with a rugged housing that is resistant to corrosive and hazardous conditions. Its wide operating temperature range, typically from -40°C to 85°C, coupled with various diaphragm materials, ensures that it can function effectively across diverse applications.

Moreover, the Emerson 3051N incorporates advanced predictive diagnostics, enabling users to monitor the health of the transmitter continuously. This feature alerts operators to potential issues before they escalate, facilitating proactive maintenance strategies that can significantly lower operational costs.

The flexible configuration options offered by the 3051N also enhance its usability. Users can select from a variety of pressure ranges, process connection types, and electrical connections, making it easy to customize the transmitter to fit specific application needs.

In conclusion, the Emerson Process Management 3051N pressure transmitter is a versatile and highly efficient device that integrates advanced technology with robust design and exceptional accuracy. Its ability to adapt to various industrial demands while providing predictive diagnostics makes it a preferred choice for professionals seeking reliability and precision in process management.