Emerson Process Management 3051N manual Fast Key Sequences Hot Key options, Diagnostic Messages

Page 90

Rosemount 3051N

Reference Manual

00809-0100-4808, Rev CA June 2008

Fast Key Sequences

Hot Key options

DIAGNOSTIC

MESSAGES

The Fast Key sequence is a sequence of numerical button presses, corresponding to the menu options that lead you to a given task. Use Table A-1, an alphabetical listing of most on-line functions, to find the corresponding HART fast key sequences. These codes are applicable only to Rosemount 3051N transmitters and the HART Communicator.

The Hot Key menu is a user-definable menu that can store shortcuts for up to 20 of your most frequently performed tasks. For example, if you change device tags, and damping often, you can add options for these functions to the Hot Key menu. Once you are Online, the Hot Key will automatically appear in the toolbar. To add a custom option to the Hot Key menu, refer to the Rosemount 375 Communicator user manual.

To use a Hot Key option, you must first properly connect the Rosemount 375 Field Communicator to a device. You can access the Hot Key menu from any online window. To use a Hot Key option:

1.Connect the Rosemount 375 Field Communicator to a HART loop or device.

2.Tap the Hot Key. The Hot Key menu is displayed.

3.Double-tap the desired option.

The following pages contain a list of messages used by both of the Rosemount 275 and Rosemount 375 HART Communicators (HC) and their corresponding descriptions.

Variable parameters within the text of a message are indicated with <variable parameter>.

Reference to the name of another message is identified by [another message].

Message

 

Description

 

 

 

1k snsr EEPROM

 

Return to Rosemount Nuclear Instruments, Inc. for repair.

error-factory ON

 

 

 

 

 

1k snsr EEPROM

 

Use the HART communicator to reset the following parameters:

error-user-no out ON

 

remote seal isolator, remote seal fill fluid, flange material, o-ring

 

 

material, transmitter type, remote seal type, flange type, meter

 

 

type, number of remote seals.

 

 

 

1k snsr EEPROM

 

Perform a full trim to recalibrate the transmitter.

error-user ON

 

 

 

 

 

4k micro EEPROM

 

Return to Rosemount Nuclear Instruments, Inc. for repair.

error-factory ON

 

 

 

 

 

4k micro EEPROM

 

Use the HART communicator to reset the message field.

error-user-no out ON

 

 

 

 

 

4k micro EEPROM

 

Use the HART communicator to reset the following parameters:

error-user ON

 

units, range values, damping, analog output, transfer function,

 

 

tag, scaled meter values. Perform a d/a trim to ensure that the

 

 

error is corrected.

 

 

 

4k snsr EEPROM

 

Return to Rosemount Nuclear Instruments, Inc. for repair.

error-factory ON

 

 

 

 

 

4k snsr EEPROM

 

Use the HART communicator to reset the temperature units

error-user ON

 

and the calibration type.

 

 

 

A-14

Image 90
Contents Reference Manual Page Rosemount 3051N Return of Material Changes from June 2006 to June OldChanges Rosemount 3051N Table of Contents Installation TroubleshootingSpecifications Reference Data Options Appendix aHart Communicator Glossary Index Using this Manual Section IntroductionRosemount 3051N Overview Safety Messages Transmitter FunctionsAlarm Level Verification TransmitterSecurity Configuring Transmitter Alarm and Security Jumper Procedure Physical Removal Local Zero and Span Local KeysElectronics Board Setting the Loop to Manual Wiring Diagrams Bench Hook-up Wiring Diagrams Field Hook-up Review Configuration Data Check OutputProcess Variables Set Process Variable Units Sensor TemperatureBasic Setup Set OutputRerange Rerange with a Communicator OnlyRerange with a Pressure Input Source and a Communicator Span and Zero Adjustment Buttons Detailed Setup Diagnostics ServiceTransmitter Test Loop TestCalibration Transmitter Bench Calibration Tasks Field Calibration Tasks Configure the Analog Output Parameters Calibration OverviewSensor Trim URVZero Trim Typical Zero vs Non-zero-Based Application IllustrationsFull Trim Digital Trim Connection Drawing 4-20 mA TransmittersRecall Factory Trim- Analog Output Digital-to-Analog Trim Using Other ScaleRecall Factory Trim Recall Factory Trim- Sensor Trim Analog Output TrimZero Effect HTc = URV + S URV Ps Rosemount 3051N Section Installation Rosemount 3051N Typical Installation Flowchart General Considerations Special Draft Range ConsiderationsMechanical Considerations 156 181 16 x 11/4 Bolts for Mounting to 54.1 Transmitter 120 127 66.8 Traditional Flange Option Code H2 Dimensional Drawing Mounting Rosemount 3051N GAS or Liquid Service GAS Service Steam Service Process Connections Housing Rotation Power SupplyElectrical Considerations Wiring Power Supply Load LimitationsAccess Requirements Cover Installation Grounding the Transmitter CaseEnvironmental Considerations Troubleshooting Symptom Corrective Actions Returning Rosemount Products and MaterialsNuclear Specifications SeismicModel Range Code Hydrostatic Test Pressure Reference Accuracy Performance SpecificationsAmbient Temperature Effect12 DriftRange Code Overpressure Effect Power Supply Effect Load Effect Mounting Position EffectOverpressure Effect Static Pressure Effect Range Code Static Pressure Zero Effect1Temperature Limits Functional SpecificationsService OutputSpan and Zero, Zero Elevation, Suppression Range Minimum Span Upper URL Lower LRLRange Code Minimum Time Constant Tc Including Dead Time Td Static Pressure Limits Maximum WorkingPressure12 Overpressure Limits Burst PressurePhysical Specifications Materials of Construction Option Code Description Add Ordering Information Mounting Bracket Options Configuration InformationHousing Material Conduit Entry Size Meters optionalDate  On Rosemount 3051N Exploded View with Coplanar Process Flange Rosemount 3051N Rosemount 3051N Overview Safety Messages LCD Meter Section OptionsCustom Meter Configuration Installing the Meter Exploded View of the Rosemount 3051N with Optional LCD MeterRosemount 3051N Diagnostic Messages ErrorPress Limit Operation Mounting BracketsTraditional Flange H2 Transient Protection Terminal Block T1Transient Protection Terminal Block T1 Rosemount 3051N Introduction Safety Messages Appendix a Hart CommunicatorRosemount 3051N Online Menu Function Hart Fast Key Sequence Figure A-3. Rosemount Hart terminal access door Connections and HardwareFigure A-4. Bench Hook-up MA Transmitters Rosemount Communicator KeysAction Keys Function Keys Alphanumeric and Shift KeysData Entry Menus Functions Fast Key SequencesFast Key Sequence Conventions Fast Key Sequence Example Main MenuOnline Menu Touch Touch Screen Alphanumeric KeysMultifunction LED Multifunction LED Processing IndicationRosemount 3051N Diagnostic Messages Fast Key Sequences Hot Key optionsMessage Description Rosemount 3051N Uploadvariable Rosemount 3051N Rosemount 3051N Glossary Smart Family Index 00809-0100-4808, Rev CA June Security Page ¢00809-0100-4801V¤

3051N specifications

The Emerson Process Management 3051N is a state-of-the-art pressure transmitter that exemplifies precision and reliability in process automation. Designed for a wide range of industrial applications, the 3051N is celebrated for its advanced features, innovative technologies, and robust construction, catering to the evolving needs of process industries.

One of the standout features of the 3051N is its exceptional accuracy. With a standard accuracy rating of ±0.075% of span, it ensures precise pressure measurements, critical for maintaining optimal process conditions. This high level of accuracy makes it suitable for applications in industries such as oil and gas, chemicals, and water treatment, where even minor deviations can lead to significant operational issues.

The 3051N employs Smart Pressure Technology, integrating digital communication capabilities with traditional analog systems. This technology allows for seamless interoperability with existing process control systems, providing users with vital data for diagnostics, calibration, and configuration via HART, FOUNDATION fieldbus, or Profibus protocols. These capabilities lead to enhanced process efficiency and reduced downtime due to effective predictive maintenance.

Another notable characteristic of this transmitter is its robust design. The 3051N is built to endure harsh industrial environments, with a rugged housing that is resistant to corrosive and hazardous conditions. Its wide operating temperature range, typically from -40°C to 85°C, coupled with various diaphragm materials, ensures that it can function effectively across diverse applications.

Moreover, the Emerson 3051N incorporates advanced predictive diagnostics, enabling users to monitor the health of the transmitter continuously. This feature alerts operators to potential issues before they escalate, facilitating proactive maintenance strategies that can significantly lower operational costs.

The flexible configuration options offered by the 3051N also enhance its usability. Users can select from a variety of pressure ranges, process connection types, and electrical connections, making it easy to customize the transmitter to fit specific application needs.

In conclusion, the Emerson Process Management 3051N pressure transmitter is a versatile and highly efficient device that integrates advanced technology with robust design and exceptional accuracy. Its ability to adapt to various industrial demands while providing predictive diagnostics makes it a preferred choice for professionals seeking reliability and precision in process management.