Quantum Quantum Composers, 9412/9112 A warranty Cycles

Page 25

9412/9412A Communication Commands

Command Name

Parameters

 

Description

MODE

0

= Continuous mode

Sets the pulse generator mode.

 

1

= Burst mode

 

 

2

= Duty Cycle mode

 

 

3

= Single Shot mode

 

 

4

= External Trigger mode

 

GATE

0

= off

 

Enables the external trigger input to function as a gate

 

1

= active low

controlling all outputs. Cannot be used with external

 

2

= active high

trigger mode.

ToPer

1000 - 99999999 μs

Sets the To internal sync period, used only in Continu-

 

500 - 99999999 μs (400B)

ous, Burst and Duty Cycle modes.

DC:On

1

- 10000 Sec

 

Sets the on time, in seconds, for the Duty Cycle mode.

DC:Off

1

- 10000 Sec

 

Sets the off time, in seconds, for the Duty Cycle mode.

TRIG

0

= falling edge

Sets the active edge of the Ext/Gate signal when used as

 

1

= rising edge

an external trigger.

CYCLES

0

- 10000 cycles

Sets the number of cycles for the Duty Cycle mode.

#/BURST

1

- 50000 pulses

Sets the number pulses in the Burst mode.

T1:Wid

1

- 99999999 μs

Sets the pulse width, in microseconds, for Channel 1.

T1:Dly

0

- 99999999 μs

Sets the delay, in microseconds, for Channel 1.

T1:Pol

0

= Negative

(active low)

Sets the polarity of the output for Channel 1.

 

1

= Positive

(active high)

 

T2:Wid

1

- 99999999 μs

Sets the pulse width, in microseconds, for Channel 2.

T2:Dly

0

- 99999999 μs

Sets the delay, in microseconds, for Channel 2. Note:

 

 

 

 

The delay is relative to Channel 1.

T2:Pol

0

= Negative

(active low)

Sets the polarity of the output for Channel 2.

 

1

= Positive

(active high)

 

T2:Enable

0

= Off

 

Turns the output of Channel 2 on and off.

 

1

= On

 

 

T2:Gate

0

= Off

 

Enables the external input to act as a gate for Channel 2's

 

1

= Active low

output.

 

2

= Active high

 

T2:Wait

0

- 10000 pulses

Set the number of pulses to wait after starting T1 before

 

 

 

 

enabling T2. Note: This is used to allow time for the la-

 

 

 

 

ser to stabilize when T1 is used as a flashlamp trigger

 

 

 

 

and T2 is the Q-switch trigger.

T2*n

1

- 10000

 

Sets the period of T2 relative to T1. The period of T2 is

 

 

 

 

the period of T1 multiplied by n.

BEEP

1

- 1000

 

Beeps the buzzer inside the 9412/9412A the specified

 

 

 

 

number of times.

RUN

0

= Disable

 

Enable / disables the pulse generator output.

 

1

= Enable

 

 

25

Image 25
Contents Warranty Parts ListIntroduction Technical SupportCustom Modifications Safety IssuesPage Page Item Button Front Panel Controls and ConnectorsDisplay Control ButtonsBack Panel QC ConnectorsSerial Port Output Voltage AdjustmentAC Input Line Voltage SelectionPage Page Page Item Edit Mode Numeric Input ModeOperating Instructions OverviewMain Menu Mode Pulse ModesGate Gate Select Duty CycleTnDly Tn Delay Width and Delay MenusToPer To Period TnWid Tn Pulse WidthT2 Menus T2EnableT2Gate Store/Recall/Misc. Menus Store ConfigurationT2Wait T2*n T2 Period FactorVolume Recall ConfigurationShot Counter FmarkPage 3 2 Command Protocol Command LanguageComputer Interface Serial RS232 PinoutEcho Enabled Cycles ?crlf 100crlf Communication Protocol Following table summarizes all the commands Command ListCycles 9412/9412A Communication Commands Delays SpecificationsOutputs Replacing the Fuse MaintenancePage Custom Features