Electrical Wiring of Fan Motor and Accessories

Installation of a vibration cut-out switch is recommended. (Refer to tower accessories available).

All electrical work should be performed only by qualified personnel and in accordance to prevailing electrical codes, practices and safety standards.

The motor starter should be sized on voltage, nominal horsepower, and maximum full load current. This current value can be found on the motor nameplate. If the starter cannot accept the maximum full load motor current, the next size should be used.

Motor heaters should be selected on the basics of maximum full load current and service factors based on the motor nameplate.

Standard “Cooling Tower Service” motors are supplied with a minimum of a 1.15 Service Factor.

Optional two speed motors are single winding variable torque.

Run flexible conduit with some slack from the motor conduit box to terminal box outside the tower where rigid conduit can be used.

Conduit holding clip screws can be tapped directly into the tower wall. Use maximum 3/8” long screws.

For the typical wiring schematic of fan motor and tower accessories, see Delta dwg. DT –B-78-001, included with these instructions.

Location, Piping and Connections

Piping should be adequately sized in accordance with accepted standard practices.

Gravity drain to indoor storage sump requires proper head differential and piping design considerations. Allowance must be made for flow, pipe size, piping layout and distance of cooling tower from the indoor storage sump.

On multiple cell installations, valving and/or pipe sizing should balance pressure drops to provide equal inlet pressures. Equalizing fittings are provided in the sumps of each cell and can piped together to balance sump water level. Each cell should be valved separately to allow for flow balancing or isolation from service.

Prior to start-up check that the PVC locknuts on all bulkhead fittings are properly tightened to prevent nuisance leaks. A chain wrench can be used to check and tighten the locknuts.

Check that the SS hexagonal nuts on the inlet and outlet PVC flanges are properly tightened to prevent nuisance leaks. While tightening the nuts, do not allow the bolt to rotate. This could damage the rubber seal under the flat washer on the bolt head located inside the cooling tower.

All supply and return piping must be independently supported.

Revised 1-8-2007

9

Image 10
Contents Delta Cooling Towers, Inc Table of Contents Principle of Cooling Towers Delta Cooling TowersCooling Tower Terms and Definitions General Information SafetyWater Treatment Approximate Weights Dimensions and Other Physical DataOffloading Handling and Installation of Your TM Series Cooling TowerOn -Site Inspection Lifting with craneInstalling Revised Anchoring Electrical Wiring of Fan Motor and Accessories Location, Piping and ConnectionsPVC Solvent Cementing Instructions Safety in Operation of the Fan Operation and Maintenance of Your TM Series Cooling TowerWater Distribution System Safety Fan and Mechanical Drive System and Its MaintenanceMotor Tower Model # Operating level from Water Level in Tower SumpSeparate Indoor Sump Cold Weather OperationCold Weather Protection Electric Immersion HeaterPiping PVC Distribution SystemOperation at Sub-freezing Ambients Problem Possible Causes Corrective Actions Install an air bleed valve at highest point Motor Trouble Shooting Guide General TM Series Optional Accessories TM Series Recommended Replacement PartsPreventative Maintenance Checklist Procedure Monthly Every Months