| Chapter 3 – Point Database | |
|
|
|
| |
Descriptor | Address1 | Application | Description | |
|
|
| travel (for use as an auxiliary slave point). This value is | |
|
|
| calculated based on motor run time. See MTR2 TIMING. | |
VLV POS | {53} | 2565 | The current position of the valve in percent of full travel for | |
|
|
| applications using a water valve. This value is calculated | |
|
|
| based on motor run time. | |
VLV1 POS | {53} | 2563 | The current position of valve 1 in percent of full travel for | |
|
|
| applications using a water valve. This value is calculated | |
|
|
| based on motor run time. | |
MTR2 TIMING | 55 | All except | The time required for the Motor 2 actuator to travel from full | |
|
| 2562, 2564, 2566 | closed to the full open position. | |
DMPR ROT ANG | 56 | All except 2597 | The number of degrees the damper is free to travel. | |
|
|
|
| |
DPR1 ROT ANG | 56 | 2597 | The number of degrees that damper 1 is free to travel. | |
|
|
|
| |
DPR2 ROT ANG | 57 | 2597 | The number of degrees that damper 2, the hot duct damper, is | |
|
|
| free to travel. | |
MTR SETUP | 58 | All | The configuration setup code for Motors 1 and 2. This enables | |
|
|
| the motors individually and sets each motor to be either direct | |
|
|
| or reverse acting. | |
|
|
| Note: When a motor is enabled, its associated DOs are | |
|
|
| enabled. | |
DO DIR.REV | 59 | All | The configuration setup code for DOs. Allows the DOs to be | |
|
|
| direct or reverse acting (enabled equals energized or disabled | |
|
|
| equals | |
EHEAT FLOW | 60 | 2562 | The flow required before the electric heat will be enabled. | |
|
|
|
| |
COOL TEMP | 61 | 2561 | The discharge air temperature where the controller will switch | |
|
|
| from heating to cooling mode. Used only in applications with | |
|
|
| SUPPLY TEMP. | |
HEAT TEMP | 62 | 2561 | The discharge air temperature where the controller will switch | |
|
|
| from cooling to heating mode. Used only in applications with | |
|
|
| SUPPLY TEMP. | |
CLG P GAIN | 63 | All except 2597 | The proportional gain value for the cooling temperature | |
|
|
| control loop. | |
CLG l GAIN | 64 | All except 2597 | The integral gain value for the cooling temperature control | |
|
|
| loop. | |
CLG D GAIN | 65 | All except 2597 | The derivative gain value for the cooling temperature control | |
|
|
| loop. | |
CHK OUT | 66 | All | The procedure tests all of the necessary I/O and ensures the | |
|
|
| controller has the ability to operate within the set airflow | |
|
|
| range, between CLG FLOW MIN and CLG FLOW MAX. | |
HTG P GAIN | 67 | All except | The proportional gain value for the heating temperature | |
|
| 2560, 2597 | control loop. | |
HTG l GAIN | 68 | All except 2560, 2597 | The integral gain value for the heating temperature control | |
|
|
| loop. | |
HTG D GAIN | 69 | All except 2560, 2597 | The derivative gain value for the heating temperature control | |
|
|
| loop. | |
CHK STATUS | 70 | All | Displays the results of CHK OUT. | |
|
|
|
| |
FLOW P GAIN | 71 | All except 2597 | The proportional gain value for the flow control loop. | |
|
|
|
| |
FLOW l GAIN | 72 | All except 2597 | The integral gain value for the flow control loop. | |
|
|
|
| |
FLOW D GAIN | 73 | All except 2597 | The derivative gain value for the flow control loop. | |
|
|
|
| |
FLOW BIAS | 74 | All except 2597 | The biasing of the flow control loop. | |
|
|
|
|
|
|
|
| 27 |
|
|
|
|
|
|
Siemens Industry, Inc. |
|
| BACnet ATEC Owner's Manaul | |
|
| 4/20/2010 |
|