Siemens 125-5050 Vlv Pos, VLV1 POS, MTR2 Timing, Dmpr ROT ANG, DPR1 ROT ANG, DPR2 ROT ANG

Page 27

 

 

 

Chapter 3 – Point Database

 

 

 

 

Descriptor

Address1

Application

Description

 

 

 

travel (for use as an auxiliary slave point). This value is

 

 

 

calculated based on motor run time. See MTR2 TIMING.

VLV POS

{53}

2565

The current position of the valve in percent of full travel for

 

 

 

applications using a water valve. This value is calculated

 

 

 

based on motor run time.

VLV1 POS

{53}

2563

The current position of valve 1 in percent of full travel for

 

 

 

applications using a water valve. This value is calculated

 

 

 

based on motor run time.

MTR2 TIMING

55

All except

The time required for the Motor 2 actuator to travel from full

 

 

2562, 2564, 2566

closed to the full open position.

DMPR ROT ANG

56

All except 2597

The number of degrees the damper is free to travel.

 

 

 

 

DPR1 ROT ANG

56

2597

The number of degrees that damper 1 is free to travel.

 

 

 

 

DPR2 ROT ANG

57

2597

The number of degrees that damper 2, the hot duct damper, is

 

 

 

free to travel.

MTR SETUP

58

All

The configuration setup code for Motors 1 and 2. This enables

 

 

 

the motors individually and sets each motor to be either direct

 

 

 

or reverse acting.

 

 

 

Note: When a motor is enabled, its associated DOs are

 

 

 

enabled.

DO DIR.REV

59

All

The configuration setup code for DOs. Allows the DOs to be

 

 

 

direct or reverse acting (enabled equals energized or disabled

 

 

 

equals de-energized).

EHEAT FLOW

60

2562

The flow required before the electric heat will be enabled.

 

 

 

 

COOL TEMP

61

2561

The discharge air temperature where the controller will switch

 

 

 

from heating to cooling mode. Used only in applications with

 

 

 

SUPPLY TEMP.

HEAT TEMP

62

2561

The discharge air temperature where the controller will switch

 

 

 

from cooling to heating mode. Used only in applications with

 

 

 

SUPPLY TEMP.

CLG P GAIN

63

All except 2597

The proportional gain value for the cooling temperature

 

 

 

control loop.

CLG l GAIN

64

All except 2597

The integral gain value for the cooling temperature control

 

 

 

loop.

CLG D GAIN

65

All except 2597

The derivative gain value for the cooling temperature control

 

 

 

loop.

CHK OUT

66

All

The procedure tests all of the necessary I/O and ensures the

 

 

 

controller has the ability to operate within the set airflow

 

 

 

range, between CLG FLOW MIN and CLG FLOW MAX.

HTG P GAIN

67

All except

The proportional gain value for the heating temperature

 

 

2560, 2597

control loop.

HTG l GAIN

68

All except 2560, 2597

The integral gain value for the heating temperature control

 

 

 

loop.

HTG D GAIN

69

All except 2560, 2597

The derivative gain value for the heating temperature control

 

 

 

loop.

CHK STATUS

70

All

Displays the results of CHK OUT.

 

 

 

 

FLOW P GAIN

71

All except 2597

The proportional gain value for the flow control loop.

 

 

 

 

FLOW l GAIN

72

All except 2597

The integral gain value for the flow control loop.

 

 

 

 

FLOW D GAIN

73

All except 2597

The derivative gain value for the flow control loop.

 

 

 

 

FLOW BIAS

74

All except 2597

The biasing of the flow control loop.

 

 

 

 

 

 

 

 

27

 

 

 

 

 

 

Siemens Industry, Inc.

 

 

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

 

 

4/20/2010

 

Image 27
Contents Siemens Industry, Inc Siemens BACnet AtecPage Service Statement Copyright NoticeFCC Regulations Credits To the ReaderTable of contents Using the Controller as a Point Extension Device How To Use This Manual Manual OrganizationManual Conventions Manual Symbols Where to Send CommentsGetting Help Application Description Product OverviewOrdering Notes BACnet Atec Electronic Output ApplicationsDigital Hardware InputsHardware Outputs AnalogApplication Power WiringIndication Communication WiringController LED Indicators Controller LEDsRelated Equipment Temperature SensorsRoom Temperature Sensor Duct Temperature SensorBasic Operation ApplicationsFail-safe Operation Heating and Cooling SwitchoverCalibration Damper Status OperationModulate Damper During Heating Mode optional Hot Water ReheatElectric Reheat Application 2861 VAV Cooling or Heating Application 2860 VAV Cooling OnlyApplication 2863 VAV with Hot Water Reheat Baseboard RadiationElectric Heat Interlock Fan Operation Application 2864 VAV Series Fan Powered with Electric ReheatInsert TEC2564CD Insert TEC2566CD Insert TEC2567CD Application 2897 Slave ModeUsing Auxiliary Points Using the Controller as a Point Extension DeviceApplications Descriptor Address Application Description Point DatabaseDescriptor Address1 Descriptor Address1 Application Description MTR2 Timing MTR SetupVLV POS VLV1 POSCTL Flow MIN Switch LimitSwitch Time FlowSetup Switch DbandCAL Setup CAL TimerChaper 4 Troubleshooting Basic Service InformationPreventive Maintenance Controller LEDs Safety FeaturesGlossary Loopout Override switchField panel LpsUnbundle Slave modeStand-alone control Terminal Equipment ControllerIndex Duct temperature sensor, 15 RTS Index Communication wiring Wiring Power wiring 125-5050, Rev. AA