Siemens 125-5050 Switch Dband, CTL Stpt, Flow Stpt, Cal Air, CAL Setup, CAL Timer, Duct Area

Page 29

 

 

 

Chapter 3 – Point Database

 

 

 

 

Descriptor

Address1

Application

Description

 

 

 

OFF for 5 minutes, and Stage 3 is OFF.

SWITCH DBAND

90

All except

The temperature range in degrees which is compared to the

 

 

2560, 2561, 2597

difference between CTL TEMP and CTL STPT. The difference

 

 

 

must exceed this value for temperature control mode to

 

 

 

change over. Changeover is also subject to the active

 

 

 

temperature control loop output being below SWITCH LIMIT

 

 

 

(Point 85) and SWITCH TIME being expired.

CTL STPT

{92}

All except

The actual setpoint value being used as input for the active

 

 

2597

temperature control loop.

FLOW STPT

{93}

All except

The setpoint of the flow control loop.

 

 

2597

 

CAL AIR

{94}

All

YES commands the controller to go through calibration

 

 

 

sequence for the air velocity transducers. YES is also

 

 

 

displayed when the calibration sequence is started

 

 

 

automatically. CAL AIR automatically returns to NO after the

 

 

 

calibration sequence is completed. Valid input: YES or NO.

CAL SETUP

95

All

The configuration setup code for the calibration sequence

 

 

 

options.

CAL TIMER

96

All

Time interval, in hours, between the calibration sequence

 

 

 

initiations if a timed calibration option is selected in CAL

 

 

 

SETUP.

DUCT AREA

97

All

Area, in square feet (square meters), of the duct where the air

 

 

 

velocity sensor is located. This is a calculated value

 

 

 

(calculated by the field panel or computer being used) that

 

 

 

depends on duct shape and size. It is used in calculating all

 

 

 

points in units of CFM, CF, LPS and L.

 

 

 

Valid input: .025 ft2 (.002 m2) through 6.375 ft2 (.5923 m2).

LOOP TIME

98

All except

The time, in seconds, between control loop calculations.

 

 

2597

 

ERROR STATUS

{99}2

All

The status code indicating any errors detected during

 

 

 

controller power up. A status of 0 indicates there are no

 

 

 

problems.

UI 1 CFG

102

All

Configuration point for universal input 1 (digital, analog –

 

 

 

thermistor, 0 to 10V or 4 to 20mA).

PERCENT UI1

{103}

All

Universal input 1 when configured as 0 to 10V or 4 to 20 mA.

 

 

 

 

UI2 CFG

104

All

Configuration point for universal input 2 (digital, analog –

 

 

 

thermistor, 0 to 10V or 4 to 20 mA).

PERCENT UI2

{105}

All

Universal input 2 when configured as 0 to 10V or 4 to 20 mA.

 

 

 

 

AIR ALTITUDE

106

All

Optional correction factor for flow sensor based on altitude.

 

 

 

 

TUBE LEN

107

All

Optional correction factor for flow sensor based on tube length

 

 

 

of air tube pickup.

TUBE DIAMETE

108

All

Tube diameter (inside) of air tube pickup.

 

 

 

 

AUX TEMP UI2

{109}

All

Temperature sensor (when UI 2 is configured for 10K

 

 

 

thermistor).

STAT SUPV

126

All

Room unit configuration point, values are additive.

 

 

 

 

RM RH

127

All

Room humidity when room unit is provided with humidity

 

 

 

sensing.

1)

2)

Points not listed are not used in this application.

Point numbers that appear in brackets { } may be unbundled at the field panel.

29

Siemens Industry, Inc.

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

4/20/2010

Image 29
Contents Siemens Industry, Inc Siemens BACnet AtecPage FCC Regulations Service StatementCopyright Notice Credits To the ReaderTable of contents Using the Controller as a Point Extension Device Manual Conventions How To Use This ManualManual Organization Getting Help Manual SymbolsWhere to Send Comments Ordering Notes Product OverviewBACnet Atec Electronic Output Applications Application DescriptionHardware Outputs Hardware InputsAnalog DigitalApplication Power WiringController LED Indicators Communication WiringController LEDs IndicationRoom Temperature Sensor Temperature SensorsDuct Temperature Sensor Related EquipmentBasic Operation ApplicationsCalibration Heating and Cooling SwitchoverDamper Status Operation Fail-safe OperationElectric Reheat Modulate Damper During Heating Mode optionalHot Water Reheat Application 2861 VAV Cooling or Heating Application 2860 VAV Cooling OnlyElectric Heat Interlock Application 2863 VAV with Hot Water ReheatBaseboard Radiation Fan Operation Application 2864 VAV Series Fan Powered with Electric ReheatInsert TEC2564CD Insert TEC2566CD Using Auxiliary Points Application 2897 Slave ModeUsing the Controller as a Point Extension Device Insert TEC2567CDApplications Descriptor Address Application Description Point DatabaseDescriptor Address1 Descriptor Address1 Application Description VLV POS MTR SetupVLV1 POS MTR2 TimingSwitch Time Switch LimitFlow CTL Flow MINCAL Setup Switch DbandCAL Timer SetupPreventive Maintenance Chaper 4 TroubleshootingBasic Service Information Controller LEDs Safety FeaturesGlossary Field panel Override switchLps LoopoutStand-alone control Slave modeTerminal Equipment Controller UnbundleIndex Duct temperature sensor, 15 RTS Index Communication wiring Wiring Power wiring 125-5050, Rev. AA