Chapter 2 – Applications

Fan Operation

The fan turns on when heating is required.

[insert TEC2567CD]

Application 2897 Slave Mode

Application 2897 is the slave mode application for the BACnet ATEC (see Ordering Notes [9] for product numbers). Slave mode is the default application that comes up when power is first applied to the controller. Slave mode provides no control. Its purpose is to allow the operator to perform equipment checkout before a control application is put into effect and to set some basic controller parameters (CTLR ADDRESS, APPLICATION, etc.). A controller in default state can also be used as a point extension device by unbundling spare I/O points at the field panel.

Using Auxiliary Points

It is possible to have extra points available on a BACnet VAV Controller — Electronic Output in addition to the ones used by the current application that is running in the controller. If these extra points are to be controlled by a field panel, then they must be unbundled at the field panel.

Using the Controller as a Point Extension Device

If the controller is only used as a point extension device, with no control application in affect, its application must be set to slave mode and points must be unbundled at the field panel. All points must be controlled from the field panel in order to be used.

22

Siemens Industry, Inc.

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

4/20/2010

Image 22
Contents Siemens BACnet Atec Siemens Industry, IncPage Copyright Notice Service StatementFCC Regulations To the Reader CreditsTable of contents Using the Controller as a Point Extension Device Manual Organization How To Use This ManualManual Conventions Where to Send Comments Manual SymbolsGetting Help BACnet Atec Electronic Output Applications Product OverviewOrdering Notes Application DescriptionAnalog Hardware InputsHardware Outputs DigitalPower Wiring ApplicationController LEDs Communication WiringController LED Indicators IndicationDuct Temperature Sensor Temperature SensorsRoom Temperature Sensor Related EquipmentApplications Basic OperationDamper Status Operation Heating and Cooling SwitchoverCalibration Fail-safe OperationHot Water Reheat Modulate Damper During Heating Mode optionalElectric Reheat Application 2860 VAV Cooling Only Application 2861 VAV Cooling or HeatingBaseboard Radiation Application 2863 VAV with Hot Water ReheatElectric Heat Interlock Application 2864 VAV Series Fan Powered with Electric Reheat Fan OperationInsert TEC2564CD Insert TEC2566CD Using the Controller as a Point Extension Device Application 2897 Slave ModeUsing Auxiliary Points Insert TEC2567CDApplications Point Database Descriptor Address Application DescriptionDescriptor Address1 Descriptor Address1 Application Description VLV1 POS MTR SetupVLV POS MTR2 TimingFlow Switch LimitSwitch Time CTL Flow MINCAL Timer Switch DbandCAL Setup SetupBasic Service Information Chaper 4 TroubleshootingPreventive Maintenance Safety Features Controller LEDsGlossary Lps Override switchField panel LoopoutTerminal Equipment Controller Slave modeStand-alone control UnbundleIndex Duct temperature sensor, 15 RTS Index Communication wiring Wiring Power wiring 125-5050, Rev. AA