Chapter 2 – Applications

Calibration

Air Velocity Sensor

Calibration of the controller's internal air velocity sensor is periodically required to maintain accurate air velocity readings. Calibration may be set to take place automatically or manually.

Autozero Module (AZM)

Used when damper cannot be closed and constant airflow is needed.

For a controller used with an AZM, calibration occurs without closing the damper. Application 6520, 6521, 6522, 6523.

For a controller used without an AZM, the damper is briefly commanded closed to get a zero airflow reading and an accurate damper position during calibration. Application 6520, 6521, 6522, 6523.

Hot Water Valve

Calibration of a hot water valve (if used) is done by briefly commanding the valve closed. Application 2863, 2865, 2867.

Damper Status Operation

It is possible, after a period of operation, for the calculated damper position to differ from the actual (physical) damper position.

If this occurs, the controller will automatically compensate for any difference by readjusting the calculated damper position. This calculated position may not match the actual position.

Fail-safe Operation

If the air velocity sensor fails, the controller uses pressure dependent control. The temperature loop controls the operation of the damper.

If the room temperature sensor fails, then the controller operates using the last known temperature value.

Heating and Cooling Switchover

The heating/cooling switchover determines whether the controller is in heating or cooling mode by monitoring the room temperature and the demand for heating and cooling (as determined by the temperature control loops).

 

15

 

 

Siemens Industry, Inc.

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

4/20/2010

Image 15
Contents Siemens Industry, Inc Siemens BACnet AtecPage Service Statement Copyright NoticeFCC Regulations Credits To the ReaderTable of contents Using the Controller as a Point Extension Device How To Use This Manual Manual OrganizationManual Conventions Manual Symbols Where to Send CommentsGetting Help Application Description Product OverviewOrdering Notes BACnet Atec Electronic Output ApplicationsDigital Hardware InputsHardware Outputs AnalogApplication Power WiringIndication Communication WiringController LED Indicators Controller LEDsRelated Equipment Temperature SensorsRoom Temperature Sensor Duct Temperature SensorBasic Operation ApplicationsFail-safe Operation Heating and Cooling SwitchoverCalibration Damper Status OperationModulate Damper During Heating Mode optional Hot Water ReheatElectric Reheat Application 2861 VAV Cooling or Heating Application 2860 VAV Cooling OnlyApplication 2863 VAV with Hot Water Reheat Baseboard RadiationElectric Heat Interlock Fan Operation Application 2864 VAV Series Fan Powered with Electric ReheatInsert TEC2564CD Insert TEC2566CD Insert TEC2567CD Application 2897 Slave ModeUsing Auxiliary Points Using the Controller as a Point Extension DeviceApplications Descriptor Address Application Description Point DatabaseDescriptor Address1 Descriptor Address1 Application Description MTR2 Timing MTR SetupVLV POS VLV1 POSCTL Flow MIN Switch LimitSwitch Time FlowSetup Switch DbandCAL Setup CAL TimerChaper 4 Troubleshooting Basic Service InformationPreventive Maintenance Controller LEDs Safety FeaturesGlossary Loopout Override switchField panel LpsUnbundle Slave modeStand-alone control Terminal Equipment ControllerIndex Duct temperature sensor, 15 RTS Index Communication wiring Wiring Power wiring 125-5050, Rev. AA