Chapter 3 – Point Database

Chapter 3 – Point Database

Chapter 3 presents a description of the BACnet VAV Controller — Electronic Output point database, including point descriptors, point addresses, and a listing of applications in which each point is found.

Descriptor

Address1

Application

Description

CTLR ADDRESS

01

All

Identifies the controller on the FLN trunk.

 

 

 

 

APPLICATION

02

All

Identification number of the program running in the controller.

 

 

 

 

RMTMP OFFSET

03

All

Compensates for deviations between the value of ROOM

 

 

 

TEMP and the actual room temperature. This corrected value

 

 

 

is displayed in CTL TEMP. RMTMP OFFSET + ROOM TEMP

 

 

 

= CTL TEMP

ROOM TEMP

{04}2

All

Actual reading from the room temperature sensor.

 

 

 

 

HEAT.COOL

{05}

All except

Current mode of operation for applications that can be in

 

 

2560, 2597

either a heating mode or a cooling mode.

DAY CLG STPT

06

All except 2597

The temperature setpoint in degrees that the controller

 

 

 

maintains during day periods in cooling mode if a room

 

 

 

temperature sensor setpoint dial is not present or is not used.

 

 

 

See STPT DIAL.

DAY HTG STPT

07

All except 2560, 2597

The temperature setpoint in degrees that the controller

 

 

 

maintains during day periods in heating mode if a room

 

 

 

temperature sensor setpoint dial is not present or is not used.

 

 

 

See STPT DIAL.

NGT CLG STPT

08

All except 2597

The temperature setpoint in degrees that the controller

 

 

 

maintains during the night periods in cooling mode.

NGT HTG STPT

09

All except 2560, 2597

The temperature setpoint in degrees that the controller

 

 

 

maintains during the night periods in heating mode.

RM STPT MIN

11

All except 2597

The minimum temperature setpoint in degrees that the

 

 

 

controller can use from the setpoint dial. This overrides any

 

 

 

temperature setpoint from the setpoint dial that falls below this

 

 

 

minimum.

RM STPT MAX

12

All except 2597

The maximum temperature setpoint in degrees that the

 

 

 

controller can use from the setpoint dial. This overrides any

 

 

 

temperature setpoint from the setpoint dial that falls above this

 

 

 

maximum.

RM STPT DIAL

{13}2

All

The temperature setpoint in degrees from the room

 

 

 

temperature sensor (not available on all temperature sensor

 

 

 

models). This setpoint will be used for control in day mode

 

 

 

(heating or cooling) when enabled by STPT DIAL.

STPT DIAL

14

All except 2597

YES indicates that there is a room setpoint dial on the room

 

 

 

temperature sensor and it should be used as the temperature

 

 

 

setpoint for control in day/occupied mode. NO indicates that

 

 

 

the appropriate preset setpoint will be used as the

 

 

 

temperature setpoint for control in day/occupied heating or

 

 

 

cooling mode. Valid input: YES or NO.

AUX TEMP UI 1

{15}

All except 2561

Actual reading from a 10K thermistor connected to the

 

 

 

controller's Ul 1 input. When a thermistor is connected at Ul 1,

 

 

 

UI 1 is not available. See UI 1.

SUPPLY TEMP

{15}

2561

Actual reading from a 10K thermistor connected to the

 

 

 

 

 

24

 

 

 

 

 

 

 

 

 

Siemens Industry, Inc.

 

 

BACnet ATEC Owner's Manaul

125-5050, Rev. AA

 

 

4/20/2010

 

Image 24
Contents Siemens BACnet Atec Siemens Industry, IncPage Service Statement Copyright NoticeFCC Regulations To the Reader CreditsTable of contents Using the Controller as a Point Extension Device How To Use This Manual Manual OrganizationManual Conventions Manual Symbols Where to Send CommentsGetting Help Product Overview Ordering NotesBACnet Atec Electronic Output Applications Application DescriptionHardware Inputs Hardware OutputsAnalog DigitalPower Wiring ApplicationCommunication Wiring Controller LED IndicatorsController LEDs IndicationTemperature Sensors Room Temperature SensorDuct Temperature Sensor Related EquipmentApplications Basic OperationHeating and Cooling Switchover CalibrationDamper Status Operation Fail-safe OperationModulate Damper During Heating Mode optional Hot Water ReheatElectric Reheat Application 2860 VAV Cooling Only Application 2861 VAV Cooling or HeatingApplication 2863 VAV with Hot Water Reheat Baseboard RadiationElectric Heat Interlock Application 2864 VAV Series Fan Powered with Electric Reheat Fan OperationInsert TEC2564CD Insert TEC2566CD Application 2897 Slave Mode Using Auxiliary PointsUsing the Controller as a Point Extension Device Insert TEC2567CDApplications Point Database Descriptor Address Application DescriptionDescriptor Address1 Descriptor Address1 Application Description MTR Setup VLV POSVLV1 POS MTR2 TimingSwitch Limit Switch TimeFlow CTL Flow MINSwitch Dband CAL SetupCAL Timer SetupChaper 4 Troubleshooting Basic Service InformationPreventive Maintenance Safety Features Controller LEDsGlossary Override switch Field panelLps LoopoutSlave mode Stand-alone controlTerminal Equipment Controller UnbundleIndex Duct temperature sensor, 15 RTS Index Communication wiring Wiring Power wiring 125-5050, Rev. AA