Basic Operation
The BACnet ATEC provides Direct Digital Control (DDC) for Variable Air Volume (VAV) terminal box applications. Temperature control varies with the application. If present, heating can be provided by hot water, up to three stages of electric reheat, or optional baseboard radiation.
Sequencing Logic (optional)
This application has the additional capability to sequence the flow and mechanical heating when heated supply air is available.
Control Temperature Setpoints
The controller maintains a specified temperature setpoint based on Day/Night mode, or the heating/cooling mode, or the setpoint dial (if used).
Day/Night Mode
The controller maintains the specified day setpoint temperature during daytime hours and the specified night setpoint at night.
Night Mode Override Switch
If the ROOM TEMPERATURE SENSOR has an override switch, it can be used to command the controller into day mode for an adjustable period of time. This only affects a controller in night mode.
Control Loops
| Temperature Loop – Heating Loop – Cooling Loop |
| Maintain temperature setpoint by changing the flow setpoint or modulating the heat |
| source (valve/electric heat). |
| Flow Loop |
| Maintains flow setpoint by modulating the damper actuator. |
14 |
|
|
|
Siemens Industry, Inc. | BACnet ATEC Owner's Manaul |
4/20/2010 |