Linear VMC-1 manual Master Station Rough-In, VMC1MB Master Station Mounting Bracket

Page 10

Master Station Rough-In

VMC1MB Master Station Mounting Bracket

The VMC1MB mounts flush with the wall stud and holds the Master Station and Power Supply (See Figure 1). Position the VMC1MB at a suggested height of 4-1/2 to 5-1/2 feet from the floor to center of the unit. As all wiring from other stations is generally terminated at the rear of the Master Station, the wall should be no less than 3 inches deep. If required, install additional wood shims or metal rough-in enclosures to allow for adequate support of the Master Station.

IMPORTANT: Install the Master Station in a cavity wall to allow for the wiring behind it. Do not install in a brick wall. For wall tiling around the Master Station, ensure that it is mounted either completely within or clear of tile to avoid an uneven surface. Be sure to allow at least 10” of space below Master Station Bracket and firebreaks for Power Supply. This is also necessary for clearance when installing the Master Station Mounting Bracket into pre-cut drywall opening.

The VMC1MB has a correct orientation, so review Figures 1 and 2 to be sure it is right side up.

VMC1MB Installation - Unfinished Wall

Install the VMC1MB flush with the front of the wall stud and fasten in place with screws as shown. After drywall has been installed, cut out an opening to the inside dimensions of the VMC1MB (7-1/4” x 11.”).

 

WALL STUD

 

VMC1MB

MOUNT

MASTER STATION

BRACKET

BRACKET

 

FLUSH WITH

 

FRONT OF

POWER SUPPLY (TE6D)

WALL STUD

MOUNTS TO FLANGE ON

 

MASTER STATION BRACKET

BRACKET

MOUNT BRACKET AT LEAST

FLANGE

10” FROM ANY FIREBREAK

FRONT VIEW

 

TRACE THIS AREA AS A TEMPLATE FOR MASTER STATION OPENING ON DRYWALL (7-1/4” x 11”)

WALL STUDS

VMC1MB

MASTER STATION BRACKET

FIREBREAK

4’-5” to 5’-5” MOUNTING HEIGHT FROM FLOOR TO CENTER LINE OF BRACKET

Figure 1. Installing Bracket - Unfinished Wall

8

Image 10
Contents VMC1 Shock Hazard Important DO’S & DON’TS Table of Contents Block Diagram Introduction Rough-in KitMaterials Required ToolsOverview Maximum Length for Cable Runs Wiring InformationCables and Wiring Cable Type and ConfigurationMaster Station Rough-In VMC1MB Installation Unfinished WallVMC1MB Master Station Mounting Bracket VMC1MB Installation Finished Wall VMC1MBRoom Station Rough-In Room Station Installation Unfinished WallRoom Station Installation Finished Wall Room Station MountingDoor Station Rough-In VMC1VDS Door Station Rough-inPRE-DRYWALL Color Video Door Station POST-DRYWALL Color Video Door StationPower Supply Connections Power Supply Rough-InTE6D Power Supply PRE-WIRED Self Contained TE6D Power SupplyPower Supply Wiring Power Identification AT Master StationPull Wires Data Hub WiringH628 Data Hub AM Antenna Antenna InstallationRadio Antennas FM AntennaChime Activated Control Output Rough-In Auxiliary Output Rough-InDoor Release Rough-in VMC1VDS DRWAppendix a Available Components Appendix a Available Components MLTL2DN49IR For more parts and accessories, please go to Year Limited Warranty