Linear VMC-1 Room Station Rough-In, Room Station Mounting, Room Station Auxiliary Activation

Page 12

Room Station Rough-In

Room Station Mounting

The Room Stations are normally mounted at a height from the floor of: 4-1/2’ to 5’.The Room Stations are not designed to be installed outdoors.

Room Station Installation - Unfinished Wall

For an unfinished wall it is recommended that the VMC1HR rough-in enclosure be used. Identify the location where the Room Station is to be installed.

Attach the Rough-In Enclosure to the stud using the two inner pre-punched holes (see Figure 3). The outside holes on the wings of the box are to be used to mount the room station and not to attach the Rough-in Enclosure to the stud.

Pull the Cat-5 wires through the hole in the back of the Rough- in Enclosure and make a knot so they do not fall back into the wall once the drywall is installed.

After drywall is installed, cut out an opening to the inside dimensions of the VMC1HR utilizing the inside of the box as a guide (see Figure 3 ).

Room Station Installation - Finished Wall

Identify the location where the Room Station is to be installed.

Cut a 3-1/2” x 7-3/4” rectangular hole in the drywall. When possible, one short edge should be situated against a wall stud to provide added support when installing the Room Station.

Pull the wire through the hole and attach to the drywall so it will not fall back into the wall cavity.

Room Station Auxiliary Activation

When operating in single digit mode, each Room Station can activate the Auxiliary Control Output (CO) triggers at the Master Station.

Pull a yellow 18 gauge wire from the VMC1MB to the Room Station location. Following this color convention will assist in the final installation of the VMC1 system.

Pull the yellow wire through the hole in the back of the Rough-In Enclosure and loop it through so it does not fall back into the wall once the drywall is installed.

USE INNER HOLES FOR

MOUNTING ROUGH-IN

ENCLOSURE TO STUD

VMC1RS-WH

ROOM STATION

MOUNTING PLATE

ELECTRONICS

PANEL

-

 

 

 

1

VOLUME

+

2

 

 

 

 

5

6

3

4

PRIV

 

7

 

 

MON

 

CLEAR

HOUSE

MUS

 

 

DOOR

 

 

 

 

 

 

 

AUX

ROOM STATION ROUGH-IN

ENCLOSURE (SEE DRAWING A)

7-3/4”

VMC1HR

3-1/2”

 

CAT5 CABLE LOOPED

 

WITH EXCESS AMOUNT

DRYWALL

 

4’-6” to 5’-0”

 

MOUNTING HEIGHT

 

FROM FLOOR LINE

 

STUDS

ROOM STATION ROUGH-IN ENCLOSURE VMC1HR

BEZEL

DRYWALL

DRAWING A

GRILLE

ANCHORS

PRE-DRYWALL ROOM STATION

INSTALLATION

VMC1RS-WH

-

 

 

1

2

+

 

 

5

 

3

PRIV

6

4

 

MON

7

CLEAR

HOUSE

MUS

 

DOOR

 

 

 

 

AUX

POST-DRYWALL ROOM STATION

INSTALLATION

Figure 3. Pre-Drywall and Post-Drywall Room Station Installation

10

Image 12
Contents VMC1 Shock Hazard Important DO’S & DON’TS Table of Contents Block Diagram Introduction Rough-in KitMaterials Required ToolsOverview Wiring Information Cables and WiringMaximum Length for Cable Runs Cable Type and ConfigurationVMC1MB Installation Unfinished Wall Master Station Rough-InVMC1MB Master Station Mounting Bracket VMC1MB Installation Finished Wall VMC1MBRoom Station Installation Unfinished Wall Room Station Installation Finished WallRoom Station Rough-In Room Station MountingDoor Station Rough-In VMC1VDS Door Station Rough-inPRE-DRYWALL Color Video Door Station POST-DRYWALL Color Video Door StationPower Supply Rough-In TE6D Power SupplyPower Supply Connections PRE-WIRED Self Contained TE6D Power SupplyPower Supply Wiring Power Identification AT Master StationData Hub Wiring Pull WiresH628 Data Hub Antenna Installation Radio AntennasAM Antenna FM AntennaAuxiliary Output Rough-In Door Release Rough-inChime Activated Control Output Rough-In VMC1VDS DRWAppendix a Available Components Appendix a Available Components MLTL2DN49IR For more parts and accessories, please go to Year Limited Warranty