Linear VMC-1 manual Power Supply Wiring, Power Identification AT Master Station

Page 16

Power Supply Rough-In

Power Supply Wiring

1.Run a 14 AWG 120 VAC power cable (including ground) from a dedicated 15-amp circuit breaker to the Master Station Mounting Bracket location. The VMC1 requires a dedicated power source so there’s no interference from other equipment.

2.Route incoming power cable into the Power Supply enclosure through the hole on the SIDE of the Power Supply.

3.Use wire nuts to connect the incoming power cable to the TE6D Power Supply BLACK (HOT) and WHITE (NEUTRAL) input wires.

4.Connect the GREEN (GROUND) wire to the ground conductor.

5.Secure all power cables entering the Power Supply enclosure with cable strain reliefs.

6.Tuck cables into the Power Supply enclosure.

7.Pull the Red and Black low voltage wires out of the top of the TE6D for later connection to the Master Station. Re-assemble theTE6D housing with the provided screws (See Figure 7).

8.Hook the power supply onto the flange of the VMC1MB and attach the it with screw provided (See Figure 7).

NOTE: Be sure all power cables entering the power supply enclosure are secured with cable strain reliefs.

PRE-WIRED SELF CONTAINED TE6D POWER SUPPLY

GROUND WIRE (GREEN)

NEUTRAL WIRE (WHITE)

WIRE NUTS

INSERT

WIRE FROM

BREAKER INTO

STRAIN RELIEF

STRAIN RELIEF

FEED WIRES THROUGH

HOT WIRE (BLACK)

BOTTOM HOUSING

PLUS 13V WIRE (RED)

NEGATIVE WIRE (BLACK)

TOP HOUSING

STRAIN RELIEFS ON TOP HOUSING AS SHOWN. CONNECT WIRES USING WIRE NUTS, THEN RE-INSTALL TOP HOUSING WITH 4 SCREWS

STRAIN RELIEF

POWER IDENTIFICATION

AT MASTER STATION

PLUS 13V

WIRE (RED)

NEGATIVE

WIRE (BLACK))

110/120V HIGH

VOLTAGE INPUT (BLACK)

RE-ASSEMBLED TE6D POWER SUPPLY WITH WIRES PROTRUDING

SCREW (PROVIDED)

NEUTRAL (WHITE)

TE6D POWER SUPPLY

GROUND (GREEN)

Figure 7 - TE6D Power Supply Wiring

14

Image 16
Contents VMC1 Shock Hazard Important DO’S & DON’TS Table of Contents Block Diagram Introduction Rough-in KitMaterials Required ToolsOverview Wiring Information Cables and WiringMaximum Length for Cable Runs Cable Type and ConfigurationMaster Station Rough-In VMC1MB Installation Unfinished WallVMC1MB Master Station Mounting Bracket VMC1MB Installation Finished Wall VMC1MBRoom Station Installation Unfinished Wall Room Station Installation Finished WallRoom Station Rough-In Room Station MountingDoor Station Rough-In VMC1VDS Door Station Rough-inPRE-DRYWALL Color Video Door Station POST-DRYWALL Color Video Door StationPower Supply Rough-In TE6D Power SupplyPower Supply Connections PRE-WIRED Self Contained TE6D Power SupplyPower Supply Wiring Power Identification AT Master StationPull Wires Data Hub WiringH628 Data Hub Antenna Installation Radio AntennasAM Antenna FM AntennaAuxiliary Output Rough-In Door Release Rough-inChime Activated Control Output Rough-In VMC1VDS DRWAppendix a Available Components Appendix a Available Components MLTL2DN49IR For more parts and accessories, please go to Year Limited Warranty