Page 40

2.2 Installation of the Hybrid IP-PBX

2.2.5Frame Ground Connection

IMPORTANT

Connect the frame of the Hybrid IP-PBX to ground.

1.

Loosen the screw.

Screw

2.

Insert a grounding wire (user-supplied)*.

 

3.Tighten the screw.

4. Connect the grounding wire to ground.

Grounding wire

To ground

*For grounding wire, green-and-yellow insulation is required, and the cross-sectional area of the conductor must be more than 0.75 mm2 or 18 AWG.

Be sure to comply with applicable local regulations (e.g., laws, guidelines).

Proper grounding (connection to ground) is very important to protect the Hybrid IP-PBX from the bad effects of external noise or to reduce the risk to the user of electrocution in the case of a lightning strike.

The ground wire of the AC cable has an effect against external noise and lightning strikes, but it may not be enough to protect the Hybrid IP-PBX. A permanent connection between ground and the ground terminal of the Hybrid IP-PBX must be made.

In most of the continental United States, the ground provided by the "Third wire ground" at the commercial power outlet will be satisfactory. However, in a small percentage of cases this ground may be installed incorrectly. Therefore, the following test procedure should be performed.

Test Procedure

1.Obtain a suitable voltmeter and set it for a possible reading of up to 250 V AC.

2.Connect the meter probes between the 2 main AC voltage points on the wall outlet. The reading obtained should be 108 V AC to 132 V AC.

3.Move one of the meter probes to the 3rd prong terminal (GND). Either the same reading or a reading of 0 volt should be obtained.

4.If a reading of 0 volt at one terminal and a reading of 108 V AC to 132 V AC at the other terminal is not obtained, the outlet is not properly grounded.

This condition should be corrected by a qualified electrician (per article 250 of the National Electrical Code).

5.If a reading of 0 volt at one terminal and a reading of 108 V AC to 132 V AC at the other terminal is obtained, then set the meter to the "OHMS/RX1" scale, place one probe at the GND Terminal and the other probe at the terminal which gave a reading of 0 volt.

A reading of less than 1 ohm should be obtained. If the reading is not obtained, the outlet is not adequately grounded. See qualified electrician.

40

Installation Manual

Image 40
Contents Hybrid IP-PBX Model No. KX-TDA50Compatible Panasonic Proprietary Telephones Incompatible Panasonic Proprietary Telephones List of AbbreviationsImportant Safety Instructions Installation Manual Precaution Installation Manual Password Security Product Service When you ship the productFor Future Reference Structure of this Manual About the Other ManualsAbout the software version of your Hybrid IP-PBX TrademarksNotification to the Telephone Company Ringer Equivalence Number RENIncidence of Harm to the Telephone Lines Trouble with this equipmentCombined Use with Alarm Equipment Keep the Software UP to Date with the Latest DataFor Cell Station Table of Contents Power Failure Connections 124 116Connection of Peripherals 120 Starting the Hybrid IP-PBX 125Installation Manual Section System Outline Networking Features Built-in Small Call Center FeaturesComputer Telephony Integration CTI Features System HighlightsVoice Mail Features Paralleled Telephone FeaturesPortable Station PS Features Hospitality FeaturesMain Unit Basic System ConstructionConstruction of Main Unit System Connection Diagram Hybrid IP-PBXHybrid IP-PBX Optional Equipment Optional EquipmentModel No Model Name Description Maximum Quantity Model No Model Name Description Maximum Quantity Specifications General DescriptionWeight when fully mounted DimensionExtension Connection Cable Characteristics System Capacity Maximum CO Line and VoIP LineMaximum Terminal Equipment Line Type Maximum NumberMEC Card Calculation MEC Card CalculationCalculation Example Equipment Type MEC FigureAC Adaptor Selection Section Installation Before Installation Before InstallationSafety Installation Instructions Installation PrecautionsBefore Installation Installation of the Hybrid IP-PBX UnpackingNames and Locations Opening/Closing the Covers Opening the CoversRemoving the Front Cover Removing/Attaching the Front CoverAttaching the Front Cover Closing the Covers LED Indications Installation of the SD Memory CardIndication Color Description Frame Ground Connection Test ProcedureConnect the frame of the Hybrid IP-PBX to ground Installing/Removing the Optional Service Cards Slot PositionSlot Restrictions Card Slot Number Type MaxInstalling Optional Service Cards Card Slot Number TypeInstallation of the Hybrid IP-PBX Installation of the Hybrid IP-PBX To detach the LED holder To attach the LED holderInstallation of the Hybrid IP-PBX Cable Handling Installation of the Hybrid IP-PBX Installation of the Hybrid IP-PBX Removing the Optional Service Cards Types of Connectors Connector Type Pin Number Used forWall Mounting KX-TDA50 Mounting on Wooden WallMounting on Concrete or Mortar Wall Installation of the Hybrid IP-PBX Attaching a Ferrite Core Attaching to an RJ45 ConnectorFor the IP-EXT4 Card Wall Mounting AC Adaptor Mounting on Concrete or Mortar Wall Install a screw here 110 mm Reference for Wall MountingInstallation Surge Protector InstallationOverview Outside Installation Installation of a Ground RodInstallation of the Hybrid IP-PBX Information about the CO Line Cards LCOT4 Card KX-TDA5180Function Pin AssignmentsAccessories included none User-supplied not included none 2 CID4 Card KX-TDA5193User-supplied not included RJ45 connector IP-GW4 Card KX-TDA5480RJ45 Connector 10BASE-T/100BASE-TX Signal Name Input I/Output O FunctionInformation about the Extension Cards 1 HLC4 Card KX-TDA51702 DLC4 Card KX-TDA5171 3 SLC4 Card KX-TDA5173 4 PLC4 Card KX-TDA5175 5 DLC8 Card KX-TDA5172 6 SLC8 Card KX-TDA5174 7 PLC8 Card KX-TDA5176 RJ45 Connector 100BASE-TX IP-EXT4 Card KX-TDA5470LED Indications Information about the Other Cards User-supplied not included Copper wire1 DPH4 Card KX-TDA5161 Pin Terminal Block Connection Diagram for External Sensors and External Relays 100 ΩECHO8 Card KX-TDA5166 3 MSG2 Card KX-TDA5191 4 SVM2 Card KX-TDA5192 EXT-CID Card KX-TDA5168 MEC Card KX-TDA5105 Removing the MEC Card RMT Card KX-TDA5196 Removing the RMT Card Connection of Extensions PT-interface CS DSS ConsoleKX-T7600 series Other With APT Parallel Connection of the ExtensionsWith DPT Using an EXtra Device Port Using a Modular T-AdaptorWith KX-T7600 Series DPT With Other DPT DptsltWith KX-T7600 Series DPT Digital EXtra Device Port Digital XDP ConnectionBack View of DPTs To TEL To Main Unit First Party Call Control CTI Connection Connection of 2.4 GHz Portable Stations OverviewCS Cell Station KX-T0141 PS 2.4 GHz Portable Station KX-TD7680/KX-TD7690Procedure Overview Investigate the installation sitePrepare the CS for site survey Conduct the site surveyFinish the site survey Mount the CS on the wallSite Planning Characteristics of Radio WavesUnderstanding the Radio Waves Object Material Transmission Tendency CS Coverage Area Radio Signal Strength LevelsSite Survey Preparation CS installation plan Example Installing in a Room Separated by Interior WallsThings to take note DIP Switch Setting and Installing the CS Temporarily for Site SurveyBefore Site Survey Connection of 2.4 GHz Portable Stations Testing the Radio Signal Strength Site SurveyPS CS NO.1 LEVEL12 Referring to the Stored Scan Data Deleting the Stored Scan Data After Site Survey Connecting a Cell Station to the Hybrid IP-PBX Accessories and User-supplied Items for the CSConnecting the CS Entering the System Programming Mode Registering the PSSetting the System Lock When the PS has not been registered yet690 PS RegistrationSystem Lock Password Setting the PIN for Hybrid IP-PBXSetting the PIN for PS Using the KX-TD7680 692691 Testing the OperationPS Termination Wall Mounting 71 mm 13/16 Install a screw here Installing the Doorphone KX-T30865 Maximum Cabling DistanceInstallation Manual Connection of Doorphones DoorphoneDoor Opener External Sensor External Relay Device Connection of Peripherals Connection of PeripheralsConnection Charts PagerPC/Printer via RS-232C Pin AssignmentsFor connecting a printer/PC with a 25-pin RS-232C connector RS-232C SignalsSignal Ground SG Receive Data RXD…inputPC/CTI Server via USB version Power Failure Connections Power Failure ConnectionsUsing Analog CO Line Card and Super Hybrid Ports Starting the Hybrid IP-PBX System Initialization ProcedureStarting the Hybrid IP-PBX Starting the Hybrid IP-PBX Starting the Hybrid IP-PBX Confirming the CO Line Connection Turning off the Hybrid IP-PBXSection Guide for the Hybrid IP-PBX PC Programming Software KX-TDA50 Maintenance Console*1 OverviewConnection ConnectionSerial Interface Connection LAN Connection via IP-GW4 CardExternal Modem Connection Installation of the Hybrid IP-PBX PC Programming Software Installing and Starting the KX-TDA50 Maintenance ConsoleInstalling the KX-TDA50 Maintenance Console System RequirementsStart the KX-TDA50 Maintenance Console from the Start menu InstallerInstallation of the Hybrid IP-PBX PC Programming Software Installation of the Hybrid IP-PBX PC Programming Software Section Troubleshooting Troubleshooting InstallationProblem Probable Cause Solution Cause CO line is connected to the T2/R1 Operation Problem Probable Cause Solution Using the Reset Button OperationError Log Display Format Troubleshooting by Error LogDescription Description Section Appendix Changed Contents Revision HistoryPsmpr Software File Version New OptionsPsmpr Software File Version Psmpr Software File Version System Capacity IP-GW4 Card KX-TDA5480 Connection Revision History Index Numerics MOH Index Reference for Wall Mounting Panasonic Puerto Rico, Inc Copyright