Charging

Charging

Each outdoor unit is factory charged (see rating plate) for the evaporator as well as a 7.5 m (25 ft) line set for each indoor line.

Any time total line set is used either shorter or longer then the nominal, which is for Single Zone = 7.5m, Dual Zone = 15m, and Tri-Zone = 22.5 (Single Zone = 25ft, Dual Zone = 50ft, and Tri Zone = 75 ft), the line set length the refrigerant charge has to be adjusted.

Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added or removed based on 20 g (0.22 oz) of R410A per meter(foot).

 

Max total

Max length of

Min length of

Max Elevation

Max elevation

Additional

 

between each

between

Capacity

length of all

each pipe

each pipe

indoor unit and

indoor units

Refrigerant

 

pipes (A+B+C)

(A/B/C)

(A/B/C)

 

outdoor unit (h1)

(h2)

 

 

 

 

 

 

 

 

 

 

 

 

 

18K BTU/h

30 m (100 ft)

15 m (50 ft)

3 m (10 ft)

7.5 m (25 ft)

7.5 m (25 ft)

20 g/m (0.22 oz/ft)

 

 

 

 

 

 

 

24K BTU/h

30 m (100 ft)

15 m (50 ft)

3 m (10 ft)

7.5 m (25 ft)

7.5 m (25 ft)

20 g/m (0.22 oz/ft)

 

 

 

 

 

 

 

36K BTU/h

45 m (150 ft)

15 m (50 ft)

3 m (10 ft)

7.5 m (25 ft)

7.5 m (25 ft)

20 g/m (0.22 oz/ft)

 

 

 

 

 

 

 

Example: A 80 ft line set is used for tri - zone 5 additional ft X 0.22 ounces per foot= add 1.1 ounces of R410A

Important:

If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the charge amount specified on the unit's rating plate, adjusting for line sets longer or shorter than 7.5 m(25 ft) for each indoor unit.

26Wall Mounted Multi-Zone Split System Air Conditioner

Image 26
Contents Heat CONTROLLER, INC Table of Contents 36K BTU/h Installation Parts Provided18/24K BTU/h There is risk of fire or electric shock Safety PrecautionsBe sure not to do Be sure to follow the instruction For electrical work, contactRun for a long time when Do not modify or extend the power cableDo not let the air conditioner Humidity is very high and aAway properly Bad connection may cause Install the drain hose to Keep level even whenInstalling the product Water leakage LeakageSelect the best location Installation of Indoor, Outdoor UnitRooftop Installations Indoor unitSeaside Applications and Installation Selecting the locationOutdoor Unit18/24K BTU/h 36K BTU/h Piping length and elevationMulti-Zone Piping Recommendations Mounting Installation Plate Drilling the hole in the wallBurrs removal Flaring workCut the pipes Putting flare nuts onIndoor Connecting the PipingCheck Foamed polyethylene or equivalent is recommendedIndoor unit installation Wrap the insulation material around all connectionsFor left rear piping Wrap the insulation material around the connecting portion Indoor unit installationBest Practice Worst PracticeOutdoor Outside diameter TorqueConnect the cable to the Indoor unit RecommendationConnect the cable to the Outdoor unit Outdoor unitFor strand wiring Methods of connecting the cableHow to connect wiring to the terminals High voltage Strand wireModel Drain piping Checking the drainageTo check the drainage Pour a glass of water into the evaporator Insulating the Pipe and Special Piping Applications Preparation Air Purging and EvacuationLeak Checking Leakage testFinishing the job Repeat evacuation procedure for each indoor unitEvacuation Capacity ChargingMax total Evaluation of the performance Prepare remote controlTest Running 03-18-08 No. MFL39059502