Heat Controller MSS-024B/A, MSH-0186/A manual Connecting Pipings and the cable to Outdoor unit

Page 33

"

(4) Connecting Pipings and the cable to Outdoor unit

1) Connecting the pipings to the Outdoor unit

1.Align the center of the pipings and sufficiently tighten the flare nut with fingers.

2.

Finally, tighten the flare nut with torque wrench

Outdoor unit

 

until the wrench clicks.

 

 

" When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench.

 

Pipe Size

Torque

9k,

Liquid Side (1/4')

1.8kg-m(13ft.ibs)

12k

Gas Side (1/2')

5.5kg-m(39.8ft.lbs)

18k, Liquid Side

4.2kg"m(28.9ft.lbs)

24k

Gas Side (518")

6.6kg"m(47.7ft.lbs)

Gas side piping (Bigger Dia.)

Torque wrench

2) Connection of the cable

1. Remove the control cover from the unit by loosening the 3

screws.

2. Dismount caps on the conduit panel.

3. Temporarily mount the conduit tubes on the conduit panel.

4. Property connect both the power supply and low voltage lines to the corresponding terminals on the terminal block.

 

5. Ground the unit in accordance with local codes.

"

6. Be sun; to size each wire allowing several inches longer

than the required length for wiring.

 

 

7. Use lock nuts to secure the condult tubes.

-41 " 011

Connector trade size for this unit is 1W.

Rater to'How to connect wiring to the terminals' for instructions on connecting depending on the wire type you are using.

Wiring Digram

connectin cable Low wRa

Indoor Una Outdoor Unit

TermMat TenNrel

(4P)(6P)

Power suppN

High Voltage

L1

L2

©.... , To

branch

]circuit

---"---°°>Ground

1.<::ý shmsfie(dw(dng.

2.Separe" wire the high and low vaboa Line.

3.Use hed1rad dectrice wiring cop" of withstanding temperatures Lip to 16rF.

4.Use ouldoa sndwaterproofconnection cable rated morednan300V for the connection between indoor and a,ldoor a&

"Be sure to comply with local codes while running the wire from the indoor unit to the outdoor unlt(stze of wire and whing method, etc}

"Every wire must be connected firmly.

Outdoor unit

Terminal *blork

"No wire should be allowed to touch refrigerant tubing, the compressor or any moving parts.

Prover Supply

4WG(MIN.) Fuse or breaker

Model Power source ® ® Capacny

9k 12k 1e 115V 14 18 154

18k 1e,230/LOaV 14 18 154

24k 1o,230/208V 14 18 20A

Over

 

5mm(21

uit panel

'

ting

 

supply

Cover control

 

-33-

0

Image 33
Contents Heat CONTROLLER, INC Contents Functions Indoor UnitAuto Wind Remote Controller Operation Owoff Operation Mode SelectionFan Speed Selection Power Supply 17Z,-W Product SpecificationsCooling OnlyAir Circulation Oumw 1 ,260Product SpecificationsCooling & Heating Indoor Unit Jzý, Installation plateTubing hole cover 9k, 12k 18k, 24kOutdoor Unit Gas sideModel DIM Cooling Only Models Refrigeration Cycle DiagramCamay a Heating Cooling & Heating ModelsHeat Evaporator I / \Indoor Wiring Diagram Indoor Wiring DiagramMSS-012, MSS-018, MS18, MSS-024, MSF4424 Iroom9k, 12k Outdoor Unit Cooling Only Models18k 24k LO.a12k 18k 24k Cooling Operation Mode Time delay Safety ControlFunction of main control Airflow Direction ControlAuto Operation Electronic control mode Intake AIR Temp Setting TEMP. +1FSetting TEMP. -10F MODE1rStart ModeoMODE2 MODE3 MODE4 Modes EndIntake AIR TE Soft Dry Operation ModeSelecting Low OFF CompressorSetting Temp Intake AIR Temp Setting TEMP. +60FHeating Operation Modeonly Heating Model IndoorPipe Temp Rý uDefrost OFF Defrost onSetting TEMP. -1F Cooling or Heating Mode with Sleep Mode Auto ControlForced Operation Setting TempCrank Case Heater Coil Controlonly Heating model ICJOutdoor IndoorSelf-diagnosis Function Display FunctionBuzzer Sound DiagnosisIs toxic when burned InstallationWhen connecting refrigerant tubing When servicingRoof Top Installations Selection of the best locationPiping length and the elevation Avoid areas where electrical wiring, conduits or Indoor Unit InstallationWire or gas line can cause death or injury Lower left and right side of Installation PlatePreparation of Pipings Piping and Drainage of Indoor UnitStarted Poo 113 H IW-0For right rear piping Connection of Pipings5kgm39.8ft.ibs LljFor the left pipings Tape the tubing, drain hose and the connecting Insert the connecting cable into the indoor unitIndoor unit installation Installation plate. Engage the two hooks of the rearDrain hose Taping Connecting Pipings and the cable to Outdoor unit Connecting the pipings to the Outdoor unitConnection of the cable 2sanoev Terminals and fasten the wire tightly with the fixing screwChecking the Drainage Attach the Grille onto the cabinet Connect the cable to the indoor unitForming the pipings BwidPage Page Temperature, Pressure, Ampere Chan Settfemont of Outdoor UnitEvaluation of theperformance MG OFF Timer Button Name and Function-Remote ControllerSleep Mode Auto Button Operation displayStart/Stop Button Qs Operation Mode Selection ButtonCooling & Heating Be careful not to lose the clip when reassem- blingRemove the securing screws To remove the Control BoxRemove 2 securing screws Page To remove the Control Box To remove the Grille from the ChassisTo remove the Evaporator To remove the Discharge GrilleRemove three screws fixing control box and motor Unhook the tab on the left inside edgeTo remove the Fan Motor To remove the Cross-Flow FanCycle Troubleshooting Guide Trouble analysisCause of Trouble Connector related to CN-POWER Connector related to CN-FAN Turn off Main Power Cý After 10 secondsDisplay PWB Assy Check Connector related to CN-DC/DC Does beeping sound is made from the Indoor Unit?R751K C711000PF Micom PIN Check Receiver Assy Product Is not operate with the remote controllerCompressor/Outdoor Fan are unable to drive Turn on Main PowerWhen Indoor Fan does not operate When Vertical Louver does not operate Operation indicator of Indoor unit blinks five times When a comunication error occursIndoor Unit Phenomena in case of connecting errorCN-UP/DOWN CN-TH+0 , ý CN-POWER RY-COMPOutdoor Unit CN-TRANS CN-FANVoltage of Connectors according to Indoor Fan Speed Optional Function Electronic Control DeviceMain PWB ASSYOutdoor Unit Optional Function Model1OK LDt ftn 18k, 24kASM LD2 LD4Schematic Diagram Page BA ýJ Remote Controller Plate InstallationHeat OTY Remark Parts Name ControllerIndoor Unit18k, 24k Motor Assy Chassis Assy Parts NameTom, .ý M m mm 7DDD \ , \Base Weld ASM Condenser Compressor ASM 9k, 12kReversing Valve Reversing Coil Front Panel AssyTOP Cover ASM Rear Panel Barrier31 CAP Capillary Final ASM HEATERCRANK-CASE1 Heat QTY RemarkOutdoor Unit18k `Ty MSS-018A MSH-018A L8k171 Reversing Coil QTY Remark PWB ASSY, Main SH-CAPACITORClamp Capacitor Controller Assy Check Valve CAPILLARY, Bent 29 CAP CAPILLARY, Bent Panel Cover ControlPANEL, Rear 2021-0024ICJ No Remark R means service parts9O2k MSS-009B MSS-012B 2021-0001MSS-0188 MSH-018B Plate Installation Holder Tube Motor Assy Chassis Assy2021-0001 2021-0074 2010-0003 2021-0069 2021-0005 FAN Assy CrossGQ 21k Service VALVE1/4 Service VALVE112Capillary TOP Cover ASMFinal ASM HEATERCRANK-CASEReversing Valve High Pressure S/WFAN Motor 2021-0024 I`JMSS-018A MSH-018A Support Valve High Pressure S/W Reversing Coil SAT City RemarkPWBASSY,MAIN 2035-0004 2035-0006 UTY Remark2021-0021 2050-0001 Extra FAN Barrier ASMHeat CONTROLLER, INC