Heat Controller MSH-01 2B/A, MSH-0186/A manual Refrigeration Cycle Diagram, Cooling Only Models

Page 9

"Refrigeration Cycle Diagram

"Cooling Only Models

INDOOR UNITOUTDOOR UNIT

t_CAPILIARYTUBE

LIQUID SIDE

 

t

HEAT

 

 

EXCHANGER

 

HEAT

(EVAPORATOR)

 

 

 

EXCHANGER

 

 

(CONDENSER)

 

GAS SIDE

COMPRESSOR

 

 

i

Pipe size(Diameter:o)

Piping length

Elevation

MODEL

 

Gas

Liquid

9k, 12k

112"

1/4'

(Cooling Only)

 

 

18k, 24k

 

 

(Cooling Only)

 

 

For installation over rated, "a proper an'

a proper quantity of refrigerant

3k, 12k

02 Oz

18k, 24k

0.3 Oz

RatedMax Rated Max

7.62m(25ft) 15m(5oft) 5m(16ft) 8m(26ft)

7.62m(25ft) 15M(Soft) 5m(16ft) 8m(26ftj

of refrigerant should be added for each 5 foot.

Ex) 18K: When installed at a distance of 30ft,1.5 Oz of refrigerant should be added.

(30.25) x 0.302 =1.5 Oz of refrigerant to add

Unit precharged for 25ft. line sets.

-9-

r-ý

LJ

Image 9
Contents Heat CONTROLLER, INC Contents Functions Indoor UnitAuto Wind Remote Controller Operation Owoff Operation Mode SelectionFan Speed Selection Power Supply 17Z,-W Product SpecificationsCooling OnlyAir Circulation Oumw 1 ,260Product SpecificationsCooling & Heating Indoor Unit Jzý, Installation plateTubing hole cover 9k, 12k 18k, 24kOutdoor Unit Gas sideModel DIM Cooling Only Models Refrigeration Cycle DiagramCamay a Heating Cooling & Heating ModelsHeat Evaporator I / \Indoor Wiring Diagram Indoor Wiring DiagramMSS-012, MSS-018, MS18, MSS-024, MSF4424 Iroom9k, 12k Outdoor Unit Cooling Only Models18k 24k LO.a12k 18k 24k Cooling Operation Mode Time delay Safety ControlFunction of main control Airflow Direction ControlAuto Operation Electronic control mode Intake AIR Temp Setting TEMP. +1FSetting TEMP. -10F MODE1rStart ModeoMODE2 MODE3 MODE4 Modes EndIntake AIR TE Soft Dry Operation ModeSelecting Low OFF CompressorSetting Temp Intake AIR Temp Setting TEMP. +60FHeating Operation Modeonly Heating Model IndoorPipe Temp Rý uDefrost OFF Defrost onSetting TEMP. -1F Cooling or Heating Mode with Sleep Mode Auto ControlForced Operation Setting TempCrank Case Heater Coil Controlonly Heating model ICJOutdoor IndoorSelf-diagnosis Function Display FunctionBuzzer Sound DiagnosisIs toxic when burned InstallationWhen connecting refrigerant tubing When servicingRoof Top Installations Selection of the best locationPiping length and the elevation Avoid areas where electrical wiring, conduits or Indoor Unit InstallationWire or gas line can cause death or injury Lower left and right side of Installation PlatePreparation of Pipings Piping and Drainage of Indoor UnitStarted Poo 113 H IW-0For right rear piping Connection of Pipings5kgm39.8ft.ibs LljFor the left pipings Tape the tubing, drain hose and the connecting Insert the connecting cable into the indoor unitIndoor unit installation Installation plate. Engage the two hooks of the rearDrain hose Taping Connecting Pipings and the cable to Outdoor unit Connecting the pipings to the Outdoor unitConnection of the cable 2sanoev Terminals and fasten the wire tightly with the fixing screwChecking the Drainage Attach the Grille onto the cabinet Connect the cable to the indoor unitForming the pipings BwidPage Page Temperature, Pressure, Ampere Chan Settfemont of Outdoor UnitEvaluation of theperformance MG OFF Timer Button Name and Function-Remote ControllerSleep Mode Auto Button Operation displayStart/Stop Button Qs Operation Mode Selection ButtonCooling & Heating Be careful not to lose the clip when reassem- blingRemove the securing screws To remove the Control BoxRemove 2 securing screws Page To remove the Control Box To remove the Grille from the ChassisTo remove the Evaporator To remove the Discharge GrilleRemove three screws fixing control box and motor Unhook the tab on the left inside edgeTo remove the Fan Motor To remove the Cross-Flow FanCycle Troubleshooting Guide Trouble analysisCause of Trouble Connector related to CN-POWER Connector related to CN-FAN Turn off Main Power Cý After 10 secondsDisplay PWB Assy Check Connector related to CN-DC/DC Does beeping sound is made from the Indoor Unit?R751K C711000PF Micom PIN Check Receiver Assy Product Is not operate with the remote controllerCompressor/Outdoor Fan are unable to drive Turn on Main PowerWhen Indoor Fan does not operate When Vertical Louver does not operate Operation indicator of Indoor unit blinks five times When a comunication error occursIndoor Unit Phenomena in case of connecting errorCN-UP/DOWN CN-TH+0 , ý CN-POWER RY-COMPOutdoor Unit CN-TRANS CN-FANVoltage of Connectors according to Indoor Fan Speed Optional Function Electronic Control DeviceMain PWB ASSYOutdoor Unit Optional Function Model1OK LDt ftn 18k, 24kASM LD2 LD4Schematic Diagram Page BA ýJ Remote Controller Plate InstallationHeat OTY Remark Parts Name ControllerIndoor Unit18k, 24k Motor Assy Chassis Assy Parts NameTom, .ý M m mm 7DDD \ , \Base Weld ASM Condenser Compressor ASM 9k, 12kReversing Valve Reversing Coil Front Panel AssyTOP Cover ASM Rear Panel Barrier31 CAP Capillary Final ASM HEATERCRANK-CASE1 Heat QTY RemarkOutdoor Unit18k `Ty MSS-018A MSH-018A L8k171 Reversing Coil QTY Remark PWB ASSY, Main SH-CAPACITORClamp Capacitor Controller Assy Check Valve CAPILLARY, Bent 29 CAP CAPILLARY, Bent Panel Cover ControlPANEL, Rear 2021-0024ICJ No Remark R means service parts9O2k MSS-009B MSS-012B 2021-0001MSS-0188 MSH-018B Plate Installation Holder Tube Motor Assy Chassis Assy2021-0001 2021-0074 2010-0003 2021-0069 2021-0005 FAN Assy CrossGQ 21k Service VALVE1/4 Service VALVE112Capillary TOP Cover ASMFinal ASM HEATERCRANK-CASEReversing Valve High Pressure S/WFAN Motor 2021-0024 I`JMSS-018A MSH-018A Support Valve High Pressure S/W Reversing Coil SAT City RemarkPWBASSY,MAIN 2035-0004 2035-0006 UTY Remark2021-0021 2050-0001 Extra FAN Barrier ASMHeat CONTROLLER, INC