Heat Controller HTS SERIES Installing the Indoor Coil and Lineset, Add-On Heat Pump Applications

Page 16

HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS

R e s i d e n t i a l S p l i t - 6 0 H z R 4 1 0 A

R e v. : 0 3 A u g u s t , 2 0 1 2

Refrigeration Installation

Figure 10: Braze Instructions

Figure 11: Air Coil Connection

Bulb (Must be

 

TXV (‘IN’ toward

Equalizer

compressor section)

Installed and

Line

 

Insulated)

 

Vapor

Fully Insulated

Suction Line

Suction Line

FP2

Sensor

Fully Insulated

Liquid Line

Nitrogen Braze

Replace Caps after adjusting

service valves

CCW

CCW

Rev. 05/31/00

Service ports for

gauges

Figure 5: Service Valve Positions

Position

Description

System

Service

 

 

 

Port

CCW - Full Out

Operation Position

Open

Closed

CCW -Full Out 1/2

Service Position

Open

Open

turn CW

 

 

 

CW - Full in

Shipping Position

Closed

Open

Installing the Indoor Coil and Lineset

Figure 11 shows the installation of the lineset and TXV to a typical indoor coil. An indoor coil or air handler (fan coil) with a TXV is required. Coils with cap tubes may not be used.

If coil includes removable fixed orifice, the orifice must be removed and a TXV must be installed as shown in Figure

11.Fasten the copper line set to the coil. Nitrogen should be circulated through the system at 2-3 psi [13.8-20.7 kPa] to prevent oxidation inside the refrigerant tubing. Use a low silver phos-copper braze alloy on all brazed connections.

TXV has internal

check valve

Liquid Line

Add-On Heat Pump Applications

The HWG Series indoor coil should be located in the supply side of the furnace to avoid condensation damage to the furnace heat exchanger for add-on heat pump applications. A high temperature limit switch should be installed as shown in Figures 12b and 13b just upstream of the coil to de-energize the compressor any time the furnace is energized to avoid blowing hot air directly into the coil, elevating refrigerant pressures during operation. The heat pump will trip out on high pressure lockout without some method of disengaging the compressor during furnace operation. Alternatively, some thermostats with “dual fuel” mode will automatically de- energize the compressor when second stage (backup) heat is required.

The TXV should be brazed into place as shown in Figure 11, keeping the “IN” side toward the compressor section. The TXV has an internal check valve and must be installed in the proper direction for operation. Always keep the valve body cool with a brazing shield and wet rags to prevent damage to the TXV. Attach the bulb to the suction line using the supplied hose clamp. Be careful not to overtighten the clamp and deform the bulb.

NOTICE! The air coil should be thoroughly washed with a filming agent, (dishwasher detergent like Cascade) to help condensate drainage. Apply a 20 to 1 solution of detergent and water. Spray both sides of coil, repeat and rinse thoroughly with water.

Evacuation and Charging the Unit

LEAK TESTING - The refrigeration line set must be pressurized and checked for leaks before evacuating and charging the unit. To pressurize the line set, attach refrigerant gauges to the service ports and add an inert gas (nitrogen or dry carbon dioxide) until pressure reaches 60-90 psig [413- 620 kPa]. Never use oxygen or acetylene to pressure test. Use a halogen leak tester or a good quality bubble solution to detect leaks on all connections made in the field. Check the service valve ports and stem for leaks. If a leak is found, repair it and repeat the above steps. For safety reasons do not pressurize system above 150 psig [1034 kPa]. System is now ready for evacuation and charging.

16

Heat Controller, Inc. Water-Source Heating and Cooling Systems

Image 16
Contents GeoLogix HTS Series Split System Two Stage, 2-5 Tons Table of Contents Model Nomenclature for Indoor Split Series Safety SafetyGeneral Information Equipment Selection GeneralIndoor Coil Selection HTS GeoLogix WDG/MWG Indoor Section Matches for Ahri RatingsAir Handler Selection Example Selecting Air HandlerInstallation Removing Existing Condensing Unit Where ApplicableAir Handler and Coil Installation Indoor Compressor Section LocationHTS Installation Piping InstallationFlushing the Earth Loop Ground-Loop Heat Pump ApplicationsAntifreeze Approximate Fluid Volume U.S. gal. L per 100’ of Pipe Antifreeze Percentages by Volume100% USP food grade Propylene Glycol EthanolExpansion Tank and Pump Water Quality StandardsMotorized Modulating Water Control Valve Ground-Water Heat Pump Applications 026-049 Sizes 064Closed OpenWater Quality Standards Water Quality StandardsRefrigeration Installation Line Set InstallationAdd-On Heat Pump Applications Installing the Indoor Coil and LinesetEvacuation and Charging the Unit WDG Charging The System Evacuation Of The Lineset And CoilTotal Charge Method Checking Superheat and Subcooling Determining Superheat Determining Sub-CoolingTypical HWG Installation Indoor Compressor Section Hot Water GeneratorInstallation Water Tank PreparationHWG Water Piping Water Tank RefillInitial Start-Up HWG Water Piping Sizes and LengthElectrical Line Voltage GeoMax 2 HTS Electrical DataLow Water Temperature Cutout Selection Accessory ConnectionsElectrical Low Voltage Terminal StripThermostat Installation Electrical Thermostat WiringThermostat Connections DXM2 Controls Unit OperationDXM2 Layout and Connections Indoor Split HTS024-060 Wiring Diagram 208-230-/60/1 DXM2 Unit Commissioning And Operating Conditions Operating LimitsBuilding Operating Limits Commissioning ConditionsUnit Start-Up and Operating Conditions Unit Start-up ProcedureUnit and System Checkout Unit Start-Up Procedure Manual OperationUnit Operating Conditions GPMTon Preventive Maintenance Basic Troubleshooting Information Sensor Nominal resistance at various temperaturesAdvanced Troubleshooting and Configuration Information System ConfigurationService Mode DXM2 Process Flow Chart StartFunctional Troubleshooting Fault Htg Clg Possible Cause SolutionIFC Fault Code Performance Troubleshooting Symptom Htg Clg Possible Cause SolutionTroubleshooting Form \SHS i d e n t i a l S p l i t 6 0 H z R 4 1 0 a Wellworth Ave., Jackson, Michigan 49203 Ph -0787-2100 Fax

HTS SERIES specifications

The Heat Controller HTS Series is a cutting-edge solution for climate control, designed to offer superior performance and unmatched comfort. This advanced heating and cooling system stands out in today's market due to its innovative technologies and user-friendly features.

One of the main features of the HTS Series is its energy efficiency. Equipped with the latest inverter technology, it adjusts the compressor speed to maintain the desired temperature while consuming less energy. This not only reduces operational costs but also minimizes the carbon footprint, making it an environmentally friendly choice.

Another standout characteristic of the HTS Series is its precise temperature control. The system utilizes advanced sensors to monitor indoor conditions in real-time, ensuring that you experience consistent comfort throughout your space. The ability to quickly react to changes in temperature helps maintain an optimal environment, regardless of external weather fluctuations.

The HTS Series also boasts a robust air filtration system. With multiple filter layers, including HEPA filters, it effectively captures dust, allergens, and other airborne pollutants. This feature makes the HTS Series an excellent choice for families with allergies or respiratory concerns, promoting a healthier indoor atmosphere.

Furthermore, the heat pump technology incorporated in the HTS Series allows for both heating and cooling capabilities. In cooler months, it efficiently extracts heat from the outside air to warm your living spaces, while during the summer, it reverses the process to provide refreshing cool air. This dual functionality enhances versatility, making it suitable for various climates.

User convenience is paramount in the HTS Series design. It comes with a smart thermostat that enables remote operation via a mobile app, providing users with flexible control over their environment. Additionally, the intuitive interface and programmable settings allow for seamless customization, adapting to your daily schedule and preferences.

Durability and quiet operation are also key attributes of the HTS Series. Built with high-quality materials and components, it ensures long-lasting performance, while its sound-dampening technologies provide whisper-quiet operation, enhancing the comfort of your home or office space.

In summary, the Heat Controller HTS Series represents the pinnacle of home heating and cooling technology. With its energy efficiency, precise temperature control, superior air filtration, dual functionality, and user-friendly features, it stands as a leading choice for those seeking reliable and effective climate solutions. This series not only enhances comfort but also supports a sustainable lifestyle for the future.