Heat Controller HTS SERIES manual Unit Start-Up and Operating Conditions, Unit and System Checkout

Page 30

HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS

R e s i d e n t i a l S p l i t - 6 0 H z R 4 1 0 A

R e v. : 0 3 A u g u s t , 2 0 1 2

Unit Start-Up and Operating Conditions

Unit and System Checkout

BEFORE POWERING SYSTEM, please check the following:

UNIT CHECKOUT

Shutoff valves: Insure that all isolation valves are open.

Line voltage and wiring: Verify that voltage is within an acceptable range for the unit and wiring and fuses/breakers are properly sized. Verify that low voltage wiring is complete. Unit control transformer: Insure that transformer has the properly selected voltage tap. Residential 208-230V units are factory wired for 230V operation unless specified otherwise. Loop/water piping is complete and purged of air. Water/piping is clean.

Antifreeze has been added if necessary.

Entering water and air: Insure that entering water and air temperatures are within operating limits of Tables 9a and 9b. Low water temperature cutout: Verify that low water temperature cut-out on the DXM2 control is properly set. Unit fan: Manually rotate fan to verify free rotation and insure that blower wheel is secured to the motor shaft. Be sure to remove any shipping supports if needed. DO NOT oil motors upon start-up. Fan motors are pre-oiled at the factory. Check unit fan speed selection and compare to design requirements. Condensate line: Verify that condensate trap is installed and pitched.

HWG pump is disconnected unless piping is completed and air has been purged from the system.

Water flow balancing: Record inlet and outlet water temperatures for each heat pump upon startup. This check can eliminate nuisance trip outs and high velocity water flow that could erode heat exchangers.

Unit air coil and filters: Insure that filter is clean and accessible. Clean air coil of all manufacturing oils.

Unit controls: Verify that DXM2 field selection options are properly set. Low voltage wiring is complete.

Blower CFM and Water ∆T is set on communicating thermostats or diagnostic tool.

Service/access panels are in place.

SYSTEM CHECKOUT

System water temperature: Check water temperature for proper range and also verify heating and cooling set points for proper operation.

System pH: Check and adjust water pH if necessary to maintain a level between 6 and 8.5. Proper pH promotes longevity of hoses and fittings (see Table 4).

System flushing: Verify that all air is purged from the system. Air in the system can cause poor operation or system corrosion. Water used in the system must be potable quality initially and clean of dirt, piping slag, and strong chemical cleaning agents. Some antifreeze solutions may require distilled water.

Internal Flow Controller: Verify that it is purged of air and in operating condition.

System controls: Verify that system controls function and operate in the proper sequence.

Low water temperature cutout: Verify that low water temperature cut-out controls are set properly

(LT1 - JW3).

Miscellaneous: Note any questionable aspects of the installation.

CAUTION!

CAUTION! Verify that ALL water valves are open and allow water flow prior to engaging the compressor. Freezing of the coax or water lines can permanently damage the heat pump.

CAUTION!

CAUTION! To avoid equipment damage, DO NOT leave system filled in a building without heat during the winter unless antifreeze is added to the water loop. Heat exchangers never fully drain by themselves and will freeze unless winterized with antifreeze.

Unit Start-up Procedure

1.Turn the thermostat fan position to “ON.” Blower should start.

2.Balance air flow at registers.

3.Adjust all valves to their full open position. Turn on the line power to all heat pump units.

4.Room temperature should be within the minimum-maximum ranges of Table 9b. During start-up checks, loop water temperature entering the heat pump should be between 30°F [-1°C] and 95°F [35°C].

5.It is recommended that water-to-air units be first started in the cooling mode, when possible. This will allow liquid refrigerant to flow through the filter-drier before entering the TXV, allowing the filter-drier to catch any debris that might be in the system before it reaches the TXV.

6.Two factors determine the operating limits of geothermal heat pumps, (a) return air temperature, and (b) water temperature. When any one of these factors is at a minimum or maximum level, the other factor must be at normal level to insure proper unit operation.

6.Two factors determine the operating limits of geothermal heat pumps, (a) return air temperature, and (b) entering water temperature. When either of the factors is at a minimum or maximum level, the other factor must be at normal levels to insure proper unit operation.

a.Place the unit in Manual Operation. When in manual mode activate Y1,Y2, and O to initiate the cooling mode. Also manually increase CFM until desired cooling CFM is achieved. Next adjust pump speed % until desired loop temperature difference (leaving water temperature minus entering water temperature) is achieved. (For modulating valve adjust valve %).

INSTALLER SETTINGS

THERMOSTAT CONFIG

SYSTEM CONFIG

ACCESSORY CONFIG

INPUT DEALER INFO

HUMIDITY CONFIG

TEMPERATURE ALGORITHM

DEMAND REDUCTION CNFG

SERVICE MODE

RESTORY DEFAULTS

ATC32U01

SELECT OPTION

PREVIOUS

30

Heat Controller, Inc. Water-Source Heating and Cooling Systems

Image 30
Contents GeoLogix HTS Series Split System Two Stage, 2-5 Tons Table of Contents Model Nomenclature for Indoor Split Series Safety SafetyGeneral Information Indoor Coil Selection HTS GeoLogix Equipment SelectionGeneral WDG/MWG Indoor Section Matches for Ahri RatingsAir Handler Selection Example Selecting Air HandlerAir Handler and Coil Installation InstallationRemoving Existing Condensing Unit Where Applicable Indoor Compressor Section LocationHTS Installation Piping InstallationGround-Loop Heat Pump Applications Flushing the Earth LoopAntifreeze 100% USP food grade Propylene Glycol Approximate Fluid Volume U.S. gal. L per 100’ of PipeAntifreeze Percentages by Volume EthanolWater Quality Standards Expansion Tank and PumpMotorized Modulating Water Control Valve Closed Ground-Water Heat Pump Applications026-049 Sizes 064 OpenWater Quality Standards Water Quality StandardsRefrigeration Installation Line Set InstallationInstalling the Indoor Coil and Lineset Add-On Heat Pump ApplicationsEvacuation and Charging the Unit WDG Evacuation Of The Lineset And Coil Charging The SystemTotal Charge Method Checking Superheat and Subcooling Determining Superheat Determining Sub-CoolingTypical HWG Installation Indoor Compressor Section Hot Water GeneratorInstallation Water Tank PreparationInitial Start-Up HWG Water PipingWater Tank Refill HWG Water Piping Sizes and LengthElectrical Line Voltage GeoMax 2 HTS Electrical DataElectrical Low Voltage Low Water Temperature Cutout SelectionAccessory Connections Terminal StripElectrical Thermostat Wiring Thermostat InstallationThermostat Connections DXM2 Controls Unit OperationDXM2 Layout and Connections Indoor Split HTS024-060 Wiring Diagram 208-230-/60/1 DXM2 Building Operating Limits Unit Commissioning And Operating ConditionsOperating Limits Commissioning ConditionsUnit Start-up Procedure Unit Start-Up and Operating ConditionsUnit and System Checkout Unit Start-Up Procedure Manual OperationUnit Operating Conditions GPMTon Preventive Maintenance Basic Troubleshooting Information Sensor Nominal resistance at various temperaturesAdvanced Troubleshooting and Configuration Information System ConfigurationService Mode DXM2 Process Flow Chart StartFunctional Troubleshooting Fault Htg Clg Possible Cause SolutionIFC Fault Code Performance Troubleshooting Symptom Htg Clg Possible Cause SolutionTroubleshooting Form \SHS i d e n t i a l S p l i t 6 0 H z R 4 1 0 a Wellworth Ave., Jackson, Michigan 49203 Ph -0787-2100 Fax

HTS SERIES specifications

The Heat Controller HTS Series is a cutting-edge solution for climate control, designed to offer superior performance and unmatched comfort. This advanced heating and cooling system stands out in today's market due to its innovative technologies and user-friendly features.

One of the main features of the HTS Series is its energy efficiency. Equipped with the latest inverter technology, it adjusts the compressor speed to maintain the desired temperature while consuming less energy. This not only reduces operational costs but also minimizes the carbon footprint, making it an environmentally friendly choice.

Another standout characteristic of the HTS Series is its precise temperature control. The system utilizes advanced sensors to monitor indoor conditions in real-time, ensuring that you experience consistent comfort throughout your space. The ability to quickly react to changes in temperature helps maintain an optimal environment, regardless of external weather fluctuations.

The HTS Series also boasts a robust air filtration system. With multiple filter layers, including HEPA filters, it effectively captures dust, allergens, and other airborne pollutants. This feature makes the HTS Series an excellent choice for families with allergies or respiratory concerns, promoting a healthier indoor atmosphere.

Furthermore, the heat pump technology incorporated in the HTS Series allows for both heating and cooling capabilities. In cooler months, it efficiently extracts heat from the outside air to warm your living spaces, while during the summer, it reverses the process to provide refreshing cool air. This dual functionality enhances versatility, making it suitable for various climates.

User convenience is paramount in the HTS Series design. It comes with a smart thermostat that enables remote operation via a mobile app, providing users with flexible control over their environment. Additionally, the intuitive interface and programmable settings allow for seamless customization, adapting to your daily schedule and preferences.

Durability and quiet operation are also key attributes of the HTS Series. Built with high-quality materials and components, it ensures long-lasting performance, while its sound-dampening technologies provide whisper-quiet operation, enhancing the comfort of your home or office space.

In summary, the Heat Controller HTS Series represents the pinnacle of home heating and cooling technology. With its energy efficiency, precise temperature control, superior air filtration, dual functionality, and user-friendly features, it stands as a leading choice for those seeking reliable and effective climate solutions. This series not only enhances comfort but also supports a sustainable lifestyle for the future.