Heat Controller HTS SERIES manual Basic Troubleshooting Information

Page 35

T h e Q u a l i t y L e a d e r i n C o n d i t i o n i n g A i r

R e s i d e n t i a l S p l i t - 6 0 H z R 4 1 0 A

R e v. : 0 3 A u g u s t , 2 0 1 2

Basic Troubleshooting Information

General Troubleshooting

Basic DXM2 board troubleshooting in general is best summarized as simply verifying inputs and outputs. After this process has been verified, confidence in board operation is confirmed and the trouble must be else where. Below are some general guidelines required for developing training materials and procedures when applying the DXM2 Control.

DXM2 Field Inputs

All conventional inputs are 24VAC from the thermostat and can be verified using a voltmeter between C and Y1, Y2, W, O, and G.

Sensor Inputs

All sensor inputs are ‘paired wires’ connecting each component with the board. Therefore continuity on pressure switches can be checked at the board connector.

The thermistor resistance should be measured with the connector removed so that only the impedance of the thermistor is measured. If desired, this reading can be compared to the chart shown in the thermistor section of this manual based upon the actual temperature of the thermistor clip. An ice bath can be used to check calibration of a thermistor if needed.

DXM2 Outputs

The compressor relay is 24VAC and can be verified using a voltmeter. The Alarm Relay can either be 24VAC as shipped or dry contacts (measure continuity during fault) for use with DDC by clipping the J4 jumper. Electric heat outputs are 24VDC and require a voltmeter set for DC to verify operation. When troubleshooting, measure from 24VDC terminal to EH1 or EH2 terminals.

Test Mode

Test Mode can be entered for 20 minutes by pressing the Test button. For Diagnostic ease at a conventional thermostat, the Alarm Relay will also cycle during test mode. The Alarm Relay will cycle on and off similar to the Fault LED to indicate a code representing the last fault, at the thermostat. Test Mode can also be entered and exited by cycling the G input, 3 times within a 60 second time period.

Sensor: Nominal resistance at various temperatures

Temp (ºC)

Temp (ºF)

Resistance

Temp (ºC)

Temp (ºF)

Resistance

(kOhm)

(kOhm)

 

 

 

 

-17.8

0.0

85.34

55

131.0

2.99

-17.5

0.5

84.00

56

132.8

2.88

-16.9

1.5

81.38

57

134.6

2.77

-12

10.4

61.70

58

136.4

2.67

-11

12.2

58.40

59

138.2

2.58

-10

14.0

55.30

60

140.0

2.49

-9

15.8

52.38

61

141.8

2.40

-8

17.6

49.64

62

143.6

2.32

-7

19.4

47.05

63

145.4

2.23

-6

21.2

44.61

64

147.2

2.16

-5

23.0

42.32

65

149.0

2.08

-4

24.8

40.15

66

150.8

2.01

-3

26.6

38.11

67

152.6

1.94

-2

28.4

36.18

68

154.4

1.88

-1

30.2

34.37

69

156.2

1.81

0

32.0

32.65

70

158.0

1.75

1

33.8

31.03

71

159.8

1.69

2

35.6

29.50

72

161.6

1.64

3

37.4

28.05

73

163.4

1.58

4

39.2

26.69

74

165.2

1.53

5

41.0

25.39

75

167.0

1.48

6

42.8

24.17

76

168.8

1.43

7

44.6

23.02

77

170.6

1.39

8

46.4

21.92

78

172.4

1.34

9

48.2

20.88

79

174.2

1.30

10

50.0

19.90

80

176.0

1.26

11

51.8

18.97

81

177.8

1.22

12

53.6

18.09

82

179.6

1.18

13

55.4

17.26

83

181.4

1.14

14

57.2

16.46

84

183.2

1.10

15

59.0

15.71

85

185.0

1.07

16

60.8

15.00

86

186.8

1.04

17

62.6

14.32

87

188.6

1.01

18

64.4

13.68

88

190.4

0.97

19

66.2

13.07

89

192.2

0.94

20

68.0

12.49

90

194.0

0.92

21

69.8

11.94

91

195.8

0.89

22

71.6

11.42

92

197.6

0.86

23

73.4

10.92

93

199.4

0.84

24

75.2

10.45

94

201.2

0.81

25

77.0

10.00

95

203.0

0.79

26

78.8

9.57

96

204.8

0.76

27

80.6

9.16

97

206.6

0.74

28

82.4

8.78

98

208.4

0.72

29

84.2

8.41

99

210.2

0.70

30

86.0

8.06

100

212.0

0.68

31

87.8

7.72

101

213.8

0.66

32

89.6

7.40

102

215.6

0.64

33

91.4

7.10

103

217.4

0.62

34

93.2

6.81

104

219.2

0.60

35

95.0

6.53

105

221.0

0.59

36

96.8

6.27

106

222.8

0.57

37

98.6

6.01

107

224.6

0.55

38

100.4

5.77

108

226.4

0.54

39

102.2

5.54

109

228.2

0.52

40

104.0

5.33

110

230.0

0.51

41

105.8

5.12

111

231.8

0.50

42

107.6

4.92

112

233.6

0.48

43

109.4

4.72

113

235.4

0.47

44

111.2

4.54

114

237.2

0.46

45

113.0

4.37

115

239.0

0.44

46

114.8

4.20

116

240.8

0.43

47

116.6

4.04

117

242.6

0.42

48

118.4

3.89

118

244.4

0.41

49

120.2

3.74

119

246.2

0.40

50

122.0

3.60

120

248.0

0.39

51

123.8

3.47

121

249.8

0.38

52

125.6

3.34

122

251.6

0.37

53

127.4

3.22

123

253.4

0.36

54

129.2

3.10

 

 

 

www.heatcontroller.com

35

Image 35
Contents GeoLogix HTS Series Split System Two Stage, 2-5 Tons Table of Contents Model Nomenclature for Indoor Split Series Safety SafetyGeneral Information WDG/MWG Indoor Section Matches for Ahri Ratings Equipment SelectionGeneral Indoor Coil Selection HTS GeoLogixSelecting Air Handler Air Handler Selection ExampleIndoor Compressor Section Location InstallationRemoving Existing Condensing Unit Where Applicable Air Handler and Coil InstallationPiping Installation HTS InstallationAntifreeze Ground-Loop Heat Pump ApplicationsFlushing the Earth Loop Ethanol Approximate Fluid Volume U.S. gal. L per 100’ of PipeAntifreeze Percentages by Volume 100% USP food grade Propylene GlycolMotorized Modulating Water Control Valve Water Quality StandardsExpansion Tank and Pump Open Ground-Water Heat Pump Applications026-049 Sizes 064 ClosedWater Quality Standards Water Quality StandardsLine Set Installation Refrigeration InstallationEvacuation and Charging the Unit Installing the Indoor Coil and LinesetAdd-On Heat Pump Applications WDG Total Charge Method Evacuation Of The Lineset And CoilCharging The System Determining Sub-Cooling Checking Superheat and Subcooling Determining SuperheatHot Water Generator Typical HWG Installation Indoor Compressor SectionWater Tank Preparation InstallationHWG Water Piping Sizes and Length HWG Water PipingWater Tank Refill Initial Start-UpGeoMax 2 HTS Electrical Data Electrical Line VoltageTerminal Strip Low Water Temperature Cutout SelectionAccessory Connections Electrical Low VoltageThermostat Connections Electrical Thermostat WiringThermostat Installation Unit Operation DXM2 ControlsDXM2 Layout and Connections Indoor Split HTS024-060 Wiring Diagram 208-230-/60/1 DXM2 Commissioning Conditions Unit Commissioning And Operating ConditionsOperating Limits Building Operating LimitsUnit and System Checkout Unit Start-up ProcedureUnit Start-Up and Operating Conditions Manual Operation Unit Start-Up ProcedureGPM Unit Operating ConditionsTon Preventive Maintenance Sensor Nominal resistance at various temperatures Basic Troubleshooting InformationSystem Configuration Advanced Troubleshooting and Configuration InformationService Mode Start DXM2 Process Flow ChartFault Htg Clg Possible Cause Solution Functional TroubleshootingIFC Fault Code Symptom Htg Clg Possible Cause Solution Performance Troubleshooting\SH Troubleshooting FormS i d e n t i a l S p l i t 6 0 H z R 4 1 0 a Wellworth Ave., Jackson, Michigan 49203 Ph -0787-2100 Fax

HTS SERIES specifications

The Heat Controller HTS Series is a cutting-edge solution for climate control, designed to offer superior performance and unmatched comfort. This advanced heating and cooling system stands out in today's market due to its innovative technologies and user-friendly features.

One of the main features of the HTS Series is its energy efficiency. Equipped with the latest inverter technology, it adjusts the compressor speed to maintain the desired temperature while consuming less energy. This not only reduces operational costs but also minimizes the carbon footprint, making it an environmentally friendly choice.

Another standout characteristic of the HTS Series is its precise temperature control. The system utilizes advanced sensors to monitor indoor conditions in real-time, ensuring that you experience consistent comfort throughout your space. The ability to quickly react to changes in temperature helps maintain an optimal environment, regardless of external weather fluctuations.

The HTS Series also boasts a robust air filtration system. With multiple filter layers, including HEPA filters, it effectively captures dust, allergens, and other airborne pollutants. This feature makes the HTS Series an excellent choice for families with allergies or respiratory concerns, promoting a healthier indoor atmosphere.

Furthermore, the heat pump technology incorporated in the HTS Series allows for both heating and cooling capabilities. In cooler months, it efficiently extracts heat from the outside air to warm your living spaces, while during the summer, it reverses the process to provide refreshing cool air. This dual functionality enhances versatility, making it suitable for various climates.

User convenience is paramount in the HTS Series design. It comes with a smart thermostat that enables remote operation via a mobile app, providing users with flexible control over their environment. Additionally, the intuitive interface and programmable settings allow for seamless customization, adapting to your daily schedule and preferences.

Durability and quiet operation are also key attributes of the HTS Series. Built with high-quality materials and components, it ensures long-lasting performance, while its sound-dampening technologies provide whisper-quiet operation, enhancing the comfort of your home or office space.

In summary, the Heat Controller HTS Series represents the pinnacle of home heating and cooling technology. With its energy efficiency, precise temperature control, superior air filtration, dual functionality, and user-friendly features, it stands as a leading choice for those seeking reliable and effective climate solutions. This series not only enhances comfort but also supports a sustainable lifestyle for the future.