Heat Controller REG-71A, REG-123A service manual Capillary Tube

Page 20

Disassembly

16. Capillary Tube

1.Remove the cabinet. (Refer to section 2)

2.After discharging the refrigerant completely, unbraze the interconnecting tube at the capil- lary tube.(See caution above)

3.Remove the capillary tube.

4.Re-install the component by referring to notes.

NOTICE

Replacement of the refrigeration cycle.

1.When replacing the refrigeration cycle, be sure to Discharge the refrigerant system using a FreonTM recovery System.

If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.

2.After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes.

3.Solder service valves into the pinch-off tube ports, leaving the valves open.

4.Solder the pinch-off tubes with Service valves.

5.Evacuate as follows.

1)Connect the vacuum pump, as illustrated figure 31A.

2)Start the vacuum pump, slowly open manifold valves A and B with two full turns counterclock- wise and leave the valves open.

The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold and entire system.

CAUTION: If high vacuum equip- ment is used, just crack valves A

and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.

3)Operate the vacuum pump vaccum for 20 to 30 minutes, until 600 microns of vacuum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.

4)Remove the hose from the vacuum pump and place it on the charging cylinder. See figure 31B. Open valve C.

Discharge the line at the manifold connection.

5)The system is now ready for final charging.

6.Recharge as follows :

1)Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.

2)Connect the charging cylinder as shown in fig- ure 31B.

With valve C open, discharge the hose at the manifold connection.

3)Open valve A and allow the proper charge to enter the system. Valve B is still closed.

4)If more charge is required, the high-side will not take it. Close valve A.

5)With the unit running, open valve B and add the balance of the charge.

a.Do not add the liquid refrigerant to the Low- side.

b.Watch the Low-side gauge; allow pressure to rise to 30 lbs.

c.Turn off valve B and allow pressure to drop.

d.Repeat steps b. and c. until the balance of the charge is in the system.

6)When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos braze and braze pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leak- age of the pinch-off connection.

20Room Air Conditioner

Image 20
Contents +$7&21752//5,1& Table of Contents Safety Precautions Be sure not to do Be sure to follow the instructionThere is risk or fire or electric shock Outside Dimensions DimensionsSymbols Used in this Manual Product Specifications ItemsInstallation Installation CheckSelect the Best Location OptionalHow to InstallModels without Installation Kit When Using Installation Kits How to InstallModels with Installaion KitWhen Using Gasket REG-123A REG-71A Preparation of Chassis Cabinet InstallationSuggested Tool Requirements Indoor Slide the unit into the cabinet.See Fig Control Locations Function of Controls FeaturesOperation Disassembly Mechanical PartsFront Grille CabinetFAN Air Handling PartsAir Guide and Turbo Fan Electrical Parts ShroudOverload Protector CompressorThermistor Power CordCapacitor Evaporator Refrigerating CycleMotor Capillary Tube Pulling Vacuum Schematic Diagram Wiring DiagramTroubleshooting Guide Piping SystemTroubleshooting Guide Unit runs but poor coolingFails to Start Room Air Conditioner Voltage Limits Complaint Cause RemedyTroubleshooting Guide +$7&21752//5,1&

REG-123A, REG-71A specifications

The Heat Controller REG-71A and REG-123A are innovative climate control units designed to provide efficient heating and cooling solutions for residential and commercial spaces. These models are characterized by advanced technologies that enhance energy efficiency, user comfort, and operational convenience.

One of the standout features of the REG-71A and REG-123A is their inverter technology. This technology allows the units to adjust their cooling and heating output based on the real-time demand, resulting in reduced energy consumption. By maintaining the desired temperature with minimal fluctuations, these models not only save on energy bills but also create a more comfortable indoor environment.

Another critical characteristic of these heat controllers is their Eco-friendly refrigerant, R32. This refrigerant has a lower Global Warming Potential (GWP) compared to traditional refrigerants, making the REG-71A and REG-123A environmentally responsible choices. Users can enjoy climate control without compromising on sustainability.

The units are designed with a user-friendly interface, featuring an intuitive remote control that enables users to adjust temperature settings, fan speeds, and operating modes easily. Additionally, both models include a programmable timer that allows for automatic operation based on individual schedules, ensuring efficiency and convenience.

Moreover, the REG-71A and REG-123A are equipped with advanced air filtration systems. These systems help to purify the air, reducing allergens and pollutants, which is especially beneficial for individuals with respiratory sensitivities.

The sleek and modern design of both units makes them a stylish addition to any living or working space. They are available in various capacities to cater to different room sizes, providing versatility for any installation requirement.

Furthermore, the units are designed for quiet operation, making them suitable for use in settings where noise levels need to be kept to a minimum, such as bedrooms and offices.

In summary, the Heat Controller REG-71A and REG-123A stand out for their innovative inverter technology, eco-friendly refrigerant, user-friendly features, advanced air filtration, and stylish design. These models provide a compelling option for anyone seeking efficient and reliable heating and cooling solutions.