Heat Controller REG-71A, REG-123A Room Air Conditioner Voltage Limits, Complaint Cause Remedy

Page 26

Troubleshooting Guide

Room AirConditioner VoltageLimits

 

NAME PLATE RATING

 

MINIMUM

 

MAXIMUM

 

 

208~230±10%

 

 

187V

 

253V

 

 

115±10%

 

 

104V

 

126V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPLAINT

CAUSE

 

 

REMEDY

 

 

 

 

 

 

 

 

 

 

Fan motor will not run.

No power

 

Check voltage at outlet. Correct if necessary.

 

 

 

 

 

 

 

 

 

 

 

Power supply cord

 

Check voltage to rotary switch. If none, check power

 

 

 

 

 

 

supply cord. Replace cord if circuit is open.

 

 

 

 

 

 

 

 

 

 

 

Rotary switch

 

Check switch continuity. Refer to wiring diagram for

 

 

 

 

 

 

terminal identification. Replace switch if defective.

 

 

 

 

 

 

 

 

 

 

Wire disconnected or con-

Connect wire. Refer to wiring diagram for terminal

 

 

 

nection loose

 

identification. Repair or replace loose terminal.

 

 

 

 

 

 

 

 

 

 

 

 

Capacitor (Discharge

 

Test capacitor.

 

 

 

 

capacitor before testing.)

Replace if not within ±10% of manufacturer's rating.

 

 

 

 

 

 

Replace if shorted, open, or damaged.

 

 

 

 

 

 

 

 

 

 

 

Will not rotate

 

Fan blade hitting shroud or blower wheel hitting

 

 

 

 

 

 

scroll. Realign assembly.

 

 

 

 

 

 

 

Units using slinger ring for condenser fan must have

 

 

 

 

 

 

1/4 to 5/16 inch clearance to the base. If it hits the

 

 

 

 

 

 

base, shim up the bottom of the fan motor with

 

 

 

 

 

 

mounting screw(s).

 

 

 

 

 

 

 

Check fan motor bearings; if motor shaft will not

 

 

 

 

 

 

rotate, replace the motor.

 

 

 

 

 

 

 

 

 

 

 

Fan motor runs

Revolves on overload.

 

Check voltage. If not within limits, call an electrician.

 

 

intermittently

 

 

 

Test capacitor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check bearings. Does the fan blade rotate freely?

 

 

 

 

 

 

If not, replace fan motor.

 

 

 

 

 

 

 

Pay attention to any change from high speed to

 

 

 

 

 

 

low speed. If the speed does not change, replace the

 

 

 

 

 

 

motor.

 

 

 

Fan motor noise.

Fan

 

If cracked, out of balance, or partially missing,

 

 

 

 

 

replace it.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blower

 

If cracked, out of balance, or partially missing,

 

 

 

 

 

 

replace it.

 

 

 

 

 

 

 

 

 

 

 

 

 

Loose clamper

 

Tighten it.

 

 

 

 

 

 

 

 

 

 

 

 

Worn bearings

 

If knocking sounds continue when running or loose,

 

 

 

 

 

 

replace the motor. If the motor hums or noise

 

 

 

 

 

 

appears to be internal while running, replace motor.

 

 

 

 

 

 

 

 

 

 

 

Compressor will not run,

Voltage

 

Check voltage.

 

 

 

but fan motor runs.

 

 

 

If not within limits, call an electrician.

 

 

 

 

 

 

 

 

 

 

 

Wiring

 

Check the wire connections, if loose, repair or

 

 

 

 

 

 

replace the terminal. If wires are off, refer to wiring

 

 

 

 

 

 

diagram for identification, and replace. Check wire

 

 

 

 

 

 

locations. If not per wiring diagram, correct.

 

 

 

 

 

 

 

 

 

 

 

Rotary

 

Check for continuity, refer to the wiring diagram for

 

 

 

 

 

 

terminal identification. Replace the switch if circuit is

 

 

 

 

 

 

open.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26Room Air Conditioner

Image 26
Contents +$7&21752//5,1& Table of Contents Safety Precautions Be sure not to do Be sure to follow the instructionThere is risk or fire or electric shock Outside Dimensions DimensionsSymbols Used in this Manual Product Specifications ItemsSelect the Best Location InstallationInstallation Check OptionalHow to InstallModels without Installation Kit When Using Installation Kits How to InstallModels with Installaion KitWhen Using Gasket REG-123A REG-71A Preparation of Chassis Cabinet InstallationSuggested Tool Requirements Indoor Slide the unit into the cabinet.See Fig Control Locations Function of Controls FeaturesOperation Front Grille DisassemblyMechanical Parts CabinetFAN Air Handling PartsAir Guide and Turbo Fan Overload Protector Electrical PartsShroud CompressorThermistor Power CordCapacitor Evaporator Refrigerating CycleMotor Capillary Tube Pulling Vacuum Schematic Diagram Wiring DiagramTroubleshooting Guide Piping SystemTroubleshooting Guide Unit runs but poor coolingFails to Start Room Air Conditioner Voltage Limits Complaint Cause RemedyTroubleshooting Guide +$7&21752//5,1&

REG-123A, REG-71A specifications

The Heat Controller REG-71A and REG-123A are innovative climate control units designed to provide efficient heating and cooling solutions for residential and commercial spaces. These models are characterized by advanced technologies that enhance energy efficiency, user comfort, and operational convenience.

One of the standout features of the REG-71A and REG-123A is their inverter technology. This technology allows the units to adjust their cooling and heating output based on the real-time demand, resulting in reduced energy consumption. By maintaining the desired temperature with minimal fluctuations, these models not only save on energy bills but also create a more comfortable indoor environment.

Another critical characteristic of these heat controllers is their Eco-friendly refrigerant, R32. This refrigerant has a lower Global Warming Potential (GWP) compared to traditional refrigerants, making the REG-71A and REG-123A environmentally responsible choices. Users can enjoy climate control without compromising on sustainability.

The units are designed with a user-friendly interface, featuring an intuitive remote control that enables users to adjust temperature settings, fan speeds, and operating modes easily. Additionally, both models include a programmable timer that allows for automatic operation based on individual schedules, ensuring efficiency and convenience.

Moreover, the REG-71A and REG-123A are equipped with advanced air filtration systems. These systems help to purify the air, reducing allergens and pollutants, which is especially beneficial for individuals with respiratory sensitivities.

The sleek and modern design of both units makes them a stylish addition to any living or working space. They are available in various capacities to cater to different room sizes, providing versatility for any installation requirement.

Furthermore, the units are designed for quiet operation, making them suitable for use in settings where noise levels need to be kept to a minimum, such as bedrooms and offices.

In summary, the Heat Controller REG-71A and REG-123A stand out for their innovative inverter technology, eco-friendly refrigerant, user-friendly features, advanced air filtration, and stylish design. These models provide a compelling option for anyone seeking efficient and reliable heating and cooling solutions.