Installation Manual For Electric Wiring

5. Electric wiring

WARNING

DANGER OF BODILY INJURY OR DEATH

TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.

(1)Selection of size of power supply and interconnecting wires. Precautions for Electric wiring

Electric wiring work should be conducted only by authorized personnel.

Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires.

Use copper conductor only.

Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.)

Item

 

Circuit

breaker

Power source

Earth leakage breaker

 

 

 

 

 

Model

Phase

Switch breaker

Overcurrent protector

wire size

Switch

Leak

 

(A)

rated capacity (A)

(minimum)

breaker

current

HDU-42CF03/H

3

30

20

2.5mm2

30

30mA

HDU-42HF03/H

 

 

 

 

 

 

(2)Wiring connection

Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by terminals.

Note: remember to connect the black terminal of indoor unit with the black terminal of outdoor unit properly using the connecting wire in the accesory bag,and connect the blue terminal of indoor unit with the white terminal of out terminal as the same(For heat pump model).For cooling only unit,just connect the black terminalof indoor unit with the black terminal of outdoor unit properly.Otherwise the wired controller will display "E4" or "E6" malfunction refer to Page.16.

HDU-42CF03/H

OUTDOOR UNIT TERMINAL BLOCK

HDU-42HF03/H

Y/G OUTDOOR UNIT TERMINAL BLOCK Y/G

Y/G R S T N 1 2 3

POWER SUPPLY: 3N~,380-400V , 50Hz

1

2

3

4

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R S T N

POWER SUPPLY: 3N~,380-400V,50Hz

L N 3 4 5

1 2 3 4 5

INDOOR UNIT TERMINAL BLOCK

INDOOR UNIT TERMINAL BLOCK

32

Image 33
Contents Duct Type AIR Conditioner Table of Contents Disposal of the old air conditioner Make sure the system is grounded Safety PrecautionsDo not wash the air conditioner with water Machine is adaptive in following situation Parts and Functions Parts and Functions Operation Buttons and display of the wire controllerCool Fan operation Auto RUN, COOL,HEAT and DRY Timer operation Timer ON-OFF Cooling, dehumidifying mode Heating mode This series changeover switch is set 1. on 2.OFF 3.OFF 4.OFF Unit fails to start MalfunctionCooling or heating is not sufficient Cooling is not sufficientMalfunction Followings are not malfunction Points to observe Care and MaintenanceHOT KEEPis operated in the following cases For Preparation of HeatingHot KeepInstallation place Is The Unit Installed CorrectlyWhen you change your address or the installation place For inspection and maintenanceInstall wire controller Installation Manual For Wire ControllerWire size HintHint Safety precautions Installation Manual For Indoor UnitHeight of ceiling Choose installation placeHanger bolts installation Preparation before installationAdjusting to the levelness Installation of indoor unitDrain Piping Good pipingInstallation of air suction and discharging duct ProceduresDrainage Test Air volume Chosen chart of simple duct Examples of improper installation Operation method of fan controller Rotate this switchR0.4~0.8 Refrigerant pipeWiring connection Installation Manual For Electric WiringHaier Group