Installation Procedure

3. PREPARATION FOR THE INSTALLATION

(1) Position of ceiling opening between unit and suspending bolt.

Indoor unit 570mm

Ceiling opening 650mm

Ornament panel 700mm

Distance between

 

 

suspending bolts 535mm

 

 

Indoor unit 570mm

 

 

Ceiling opening 650mm

 

 

Ornament panel 700mm

 

 

(For series 142, 182 )

Overlap between ceiling and ornament panel shall be 25mm

Suspending bolts

 

 

150mm

320mm

Ceiling

Ornament panel

60mm

 

 

 

 

 

 

 

 

(For series 242, 282 )

950(Ornament panel)

890(Ceiling opening)

840(Indoor unit)

 

Refrigerant pipe

780

Suspending bolts

(Distancesuspendingbetweenbolts)

A (Distance between suspending bolts)

840(Indoor unit)

890(Ceiling opening)

950(Ornament panel)

A

Suspending bracket

(For series 362, 422, 482, 602 ) 060710**

1280(Ceiling opening)

1270 (Distance between suspending bolts)

515

060608**

suspending bolts)

opening)

780 (Distance between

860(Ceiling

515

 

Note:

Dimension of ceiling opening marked with * can be as large as 910mm, but the matching part of ceiling with ornament panel shall be over 20mm.

(160)

CeilingA

(2)Cut an opening in ceiling for installation if necessary. (when ceiling already exists.) Refer to paper pattern for dimension of ceiling hole.

20 Over

Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation.

Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration. Contact your real estate dealer

(3) Install a suspending bolt. (Use a M10 bolt)

To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new ceiling, use built-in type bolt or parts prepared in the field.

Before going on installing adjust space between ceiling.

<Installation example>

50~100

Roof

Anchor bolt

Long nut

Suspending bolt

Ceiling

Note: All the above mentioned parts shall be prepared in field.

21

Image 23
Contents No.0010577963 Operation & Installation ManualContents Disposal of the old air conditioner For ERA series Applicable ambient temperature range For EAA seriesRefrigerating circuit is leak-proof Machine is adaptive in following situationSafety cautions Dont dismantle the outlet of the outdoor unit Operating noise WiringLocation Drain Hose Swing fender Introduction to Spare PartsFor series 142 Suction grillClean indoor outdoor unit MaintenanceClean the unit Clean the air filterOpen inlet grill Install air filterClean For series 242Close inlet grill Take off air-filter Take of inlet grill CleanInstall inlet grill Install swing plateFor series 362, 422, 482 Clean the air filterInstruction Pre-season Care Seasonal Reserve Post-season CareFollowings are not malfuncition Trouble ShootingOFF Insufficient cooling When Trouble HappensCooled air blown out when heating Insufficient cooling or heatingOutdoor ambient temp. sensor failure Error display For ERA seriesError display For EAA series Customer Need-to-know Using DirectionsCustomer Need-to-know Meanings of Warning and Cautions Installation ProcedureDont discard any accessories until comp Before InstallationSelection of Installation Place Installation example Preparation for the InstallationCase of ceiling already exists Installation of Indoor UnitAfter installation on the ceiling Case of new ceilingPipe Tighten Amm Flare shape Size Torque Installation of Water Drainage PipeLimits of panel board installation When wiring is not complete After wiringInstallation of Ornament Panel WiringWiring Example Mounting on high ceiling Installation of inlet grill and cover plate Haier Group