Installation Procedure

(2)Check if water drainage is smooth after installation.

(For series 242, 282, 362, 422, 482, 602 )

Charge, through air outlet or inspecting hole, 1200ccd water to see water drainage.

After wiring

Check water drainage in cooling operation.

When wiring is not complete

Remove cover of control box, connect 1PH power to terminal 1 and 2 on terminal block.,use remote controller to operate the unit.

Note, in this operation, fan will be running.

Upon confirmation of a smooth water drainage, be sure to cut off power supply.

Method of water charging

Self-provided stiff pipe

Maintenance

Water drainage port for

 

 

maintenance

 

Inspecting hole

 

 

(Drain water from

 

 

this hole)

 

 

100mm

Charge water from

inspecting hole

 

Watering can of plastic

Charge water from

pipe should be about

100 mm long

air outlet

 

Connect with

1

2

outdoor unit

3

 

D

Terminal block

PCB on indoor unit

Terminal block

Cover of controll box

(For series 242, 282 )

OUTDOOR UNIT TERMINAL BLOCK

INDOOR UNIT TERMINAL BLOCK

L N

1

2

Y/G

3

1 2 3 Y/G

POWER SUPPLY: 1PH,220-230V~,50Hz

(For series 362, 422, 482, 602 )

 

INDOOR UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y/G

 

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR UNIT

TERMINAL BLOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y/G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINAL BLOCK

 

 

R

S

 

T

N

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380-400V,3N~,50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

Image 27
Contents No.0010577963 Operation & Installation ManualContents Disposal of the old air conditioner For ERA series Applicable ambient temperature range For EAA seriesRefrigerating circuit is leak-proof Machine is adaptive in following situationSafety cautions Dont dismantle the outlet of the outdoor unit Wiring LocationOperating noise Drain Hose Swing fender Introduction to Spare PartsFor series 142 Suction grillClean indoor outdoor unit MaintenanceClean the unit Clean the air filterOpen inlet grill Install air filterClean For series 242Close inlet grill Take off air-filter Take of inlet grill CleanInstall inlet grill Install swing plateFor series 362, 422, 482 Clean the air filterInstruction Pre-season Care Seasonal Reserve Post-season CareFollowings are not malfuncition Trouble ShootingOFF Insufficient cooling When Trouble HappensCooled air blown out when heating Insufficient cooling or heatingOutdoor ambient temp. sensor failure Error display For ERA seriesError display For EAA series Using Directions Customer Need-to-knowCustomer Need-to-know Meanings of Warning and Cautions Installation ProcedureBefore Installation Selection of Installation PlaceDont discard any accessories until comp Installation example Preparation for the InstallationCase of ceiling already exists Installation of Indoor UnitAfter installation on the ceiling Case of new ceilingPipe Tighten Amm Flare shape Size Torque Installation of Water Drainage PipeLimits of panel board installation When wiring is not complete After wiringWiring Wiring ExampleInstallation of Ornament Panel Mounting on high ceiling Installation of inlet grill and cover plate Haier Group