Haier AB092XCERA, AB182XCERA Electrical Wiring, Wiring methods Wiring method of ring terminal

Page 19

Installation Procedures

8.Electrical Wiring

Wiring methods:

1 Wiring method of ring terminal

For connecting line which end is a ring,its wiring method as shown in the right figure: remove wiring screw and pass it through the end ring of connecting line,then connect it to the terminal block and tighten screw.

Brazed seam

B

d

T

B=8.0-9.0(mm)

d=4.3-5.3(mm)

T=1.0-2.0(mm)Ring TerminalWiring method of ring terminal (For your referrence)

2 Wiring of indoor unit

The distance between the signal wires and the power cabes should be at least 50mm.

1(L)

2(N)

P

Q

A

B

C

1(L)

2(N)

P

Q

A

B

C

 

 

 

 

 

 

 

 

 

 

To

wired controller

To other

 

 

 

 

 

 

 

 

 

(In case of using wired

 

 

 

 

 

 

 

 

 

controller)

 

 

indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication cable (Shield wire):

 

 

 

 

 

 

 

H05RN-F 2X (0.75-1.5)mm2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L N

 

C1 C2

 

 

 

Power cable : H05RN-F 3G (1-2.5)mm2

To outdoor unit

 

WARNING

1.Incorrect address setting will cause abnormal to the system. 2.Communication cable must be use sheilded type.

3.Communication cable and power cable must be use ring terminal type.

17

Image 19
Contents No.0010577258 Contents Disposal of the old air conditioner Refrigerating circuit is leak-proof Applicable ambient temperature rangeMinute Protection Function Remote ControlMain Points of Operation Operation of Air ConditionerDefrosting Function Prevent Cool Air Blowing OffHints Air Inlet Grille Parts and FunctionsSwing louver Operating Control PanelSafety Cautions Dont operate the air conditioner with damp hands Clean indoor outdoor unit MaintenanceClean the unit Clean the air filterPre-season Care Seasonal Reserve Post-season CareInsufficient cooling When Trouble HappensCooled air blown out when heating Insufficient cooling or heatingCustomer Need-to-know Using DirectionsCustomer Need-to-know Selection of Installation Place Installation ProceduresInstallation Preparation After installation on the ceiling Installation of indoor unitCase of ceiling already exists Less than 75mm Less than 500mm Installation of water drainage pipeInstall ornament panel on indoor unit Installation of Ornament PanelAB092XCERA AB122XCERA Piping ConnectionWiring methods Wiring method of ring terminal Electrical WiringIndoor unit communication addresses setting Instructions to installationIndoor Followings are not malfuncition Trouble ShootingOFF Abnormal communication Haier Group