Trouble Shooting

 

FAILURE CODE

 

TROUBLE SHOOTING

(TIMER LED OF INDOOR

POSSIBLE REASONS

 

RECEIVER BOARD FLASHES

 

 

TIMES)

 

Faulty temperature sensor Tai

ONCE

Sensor disconnected, or broken, or at wrong

position, or short circuit

 

 

 

 

 

Faulty temperature sensor Tc1

TWICE

Sensor disconnected, or broken, or at wrong

position, or short circuit

 

 

Faulty temperature sensor Tc2

3 TIMES

Sensor disconnected, or broken, or at wrong

position, or short circuit

 

 

 

 

 

Faulty temperature sensor Tm

4 TIMES

Sensor disconnected, or broken, or at wrong

position, or short circuit

 

 

Faulty EEPROM on indoor

5 TIMES

Faulty indoor unit PCB

unit PCB

 

 

Abnormal communication

 

Wrong connection, or the wires be disconnected,

6 TIMES

or wrong address setting of indoor units, or faulty

between indoor and outdoor unit

 

power supply or faulty PCB

 

 

 

Abnormal communication

7 TIMES

Wrong connection, or use the wired controllerbe

 

between wired controller and

 

disconnected, faulty PCB

 

indoor unit PCB

 

 

 

 

 

 

 

 

 

 

 

Pump motor disconnected, or at wrong

 

Drainage system abnormal

8 TIMES

position, or the float switch broken down

 

 

 

or the float switch disconnected,or at

 

 

 

wrong position

 

 

 

 

 

 

Indoor unit address repeated

9 TIMES

Wrong setting of indoor unit address

 

 

 

 

 

 

Central control address repeated

10 TIMES

Wrong setting of centralized control indoor unit

 

address

 

 

 

 

 

 

 

 

 

Faulty indoor unit fan motor

11 TIMES

Fan is blocked, or the terminal is disconnected

 

from the PCB, or faulty indoor unit PCB

 

 

 

 

 

 

 

 

 

Faulty driver of indoor unit

12 TIMES

Faulty indoor unit PCB

 

fan motor

 

 

 

 

 

 

 

 

 

 

Abnormal communication

14 TIMES

Faulty indoor unit PCB

 

between chip TMP/807 and

 

 

 

 

 

chip TMP/846

 

 

 

Malfunction on outdoor unit

20 TIMES

Check the outdoor unit failure code

Note:

1.Please contact the installers or distributors when trouble happens to repair it.

2.Turn the power off and power on again, if the failure code recurs, please inform the franchiser.

3.Failrue codes maked with are resumable.

22

Image 24
Contents No.0010577258 Contents Disposal of the old air conditioner Applicable ambient temperature range Refrigerating circuit is leak-proofRemote Control Main Points of OperationOperation of Air Conditioner Minute Protection FunctionPrevent Cool Air Blowing Off Defrosting FunctionHints Parts and Functions Swing louverOperating Control Panel Air Inlet GrilleSafety Cautions Dont operate the air conditioner with damp hands Maintenance Clean the unitClean the air filter Clean indoor outdoor unitSeasonal Reserve Post-season Care Pre-season CareWhen Trouble Happens Cooled air blown out when heatingInsufficient cooling or heating Insufficient coolingUsing Directions Customer Need-to-knowCustomer Need-to-know Installation Procedures Selection of Installation PlaceInstallation Preparation Installation of indoor unit After installation on the ceilingCase of ceiling already exists Installation of water drainage pipe Less than 75mm Less than 500mmInstallation of Ornament Panel Install ornament panel on indoor unitPiping Connection AB092XCERA AB122XCERAElectrical Wiring Wiring methods Wiring method of ring terminalInstructions to installation Indoor unit communication addresses settingIndoor Trouble Shooting Followings are not malfuncitionOFF Abnormal communication Haier Group