Goodman Mfg service manual GSX13018-601B

Page 7

CONDENSING UNIT SPECIFICATIONS

GSX130[18-60]1B*

 

GSX130181B*

GSX130241B*

GSX130301B*

 

 

 

 

 

 

 

 

Cooling Capacity, BTUH

18,000

24,000

30,000

 

 

Compressor

 

 

 

 

 

R.L. Amps

9.00

13.5

12.8

 

 

L.R. Amps

48.0

58.3

64.0

 

 

High Pressure Switch

 

 

 

 

 

Open

N/A

N/A

N/A

 

 

Close

N/A

N/A

N/A

 

 

Condenser Fan Motor

 

 

 

 

 

Horsepower

1/6

1/6

1/6

 

 

F.L. Amps

1.10

1.10

1.10

 

 

Liquid Line, Inches O.D.*

3/8"

3/8"

3/8"

 

 

Suction Line, Inches O.D.*

3/4"

3/4"

3/4"

 

 

Refrigerant Charge

72.0

79.0

81.0

 

 

Power Supply

208/230-60-1

208/230-60-1

208/230-60-1

 

 

Minimum Circuit Ampacity(1)

12.4

18.0

17.1

 

 

Maximum Overcurrent Device(2)

20

30

30

 

 

Electrical Conduit Size

 

 

 

 

 

Power Supply (Inches)

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

 

 

Approximate Shipping Weight

149

151

152

 

 

 

 

 

 

 

 

 

GSX130361B*

GSX130421B*

GSX130481B*

GSX130601B*

 

 

 

 

 

 

 

Cooling Capacity, BTUH

36,000

42,000

48,000

60,000

 

Compressor

 

 

 

 

 

R.L. Amps

16.7

17.9

19.9

25.0

 

L.R. Amps

79.0

112.0

109.0

134.0

 

High Pressure Switch

 

 

 

 

 

Open

N/A

N/A

N/A

N/A

 

Close

N/A

N/A

N/A

N/A

 

Condenser Fan Motor

 

 

 

 

 

Horsepower

1/6

1/4

1/4

1/4

 

F.L. Amps

1.10

1.50

1.50

1.50

 

Liquid Line, Inches O.D.*

3/8"

3/8"

3/8"

3/8"

 

Suction Line, Inches O.D.*

3/4"

7/8"

7/8"

7/8"

 

Refrigerant Charge

92.0

124.0

128.0

125.0

 

Power Supply

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

 

Minimum Circuit Ampacity(1)

22.0

23.9

26.4

32.8

 

Maximum Overcurrent Device(2)

35

40

45

50

 

Electrical Conduit Size

 

 

 

 

 

Power Supply (Inches)

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

 

Approximate Shipping Weight

159

194

195

200

 

 

 

 

 

 

 

(1)Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

(2)Maximum Overcurrent Protection Device: MUST use time delay fuses or HACR-type Circuit Breakers of the same size as noted.

NOTES:

*Always check the S&R plate for electrical data on the unit being installed.

*Installer will need to supply 7/8" to 1 1/8" adapters for suction line connections.

*Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.

*Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT NOT THE INDOOR COIL.

NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.

7

Image 7
Contents Technical Manual Product Identification 024GSX130363A AA AA Product DesignDimensions 208/230-60-1 Condensing Unit SpecificationsOr 3/4 GSX13018-601B GSX130181C GSX13036-603,4 VSX130361A VSX130421A VSX130481A VSX130181A VSX130241A VSX130301AVSX13018 & 601B GSX130181A Cooling Performance DataModel GSX130181AA / CA*F1824*6** / ZP16K5E-PFV Bulb Temperature105 115 21.3 Entering Indoor Wet Bulb Temperature22.0 359GSX130241A 105 115 Entering Indoor Wet Bulb TemperatureModel GSX130241AA / CA*F1824*6** / ZP20K5-PFV 132 Airflow27.1 379400 GSX130301AModel GSX130301AA / CA*F3030*6** / ZP24K5E-PFV 28.4GSX130361A 390 Model GSX130361AA / CA*F4860*6** / ZP31K5E-PFV35.0 11.9133 38.213.3 37213.8 GSX130421AModel GSX130421AA / CA*F4860*6** / ZP34K5-PFV 40.042.6 43.915.1 13615.7 GSX130481AModel GSX13048-1AA / CA*F4860*6** / ZP39K5E-PFV 46.0GSX130601A Model GSX130601AA / CA*F4860*6**/ ZP51K5E-PFV Cooling Performance Data GSX130181B*/VSX130181A 18.0 16.9 Cooling Performance Data GSX130181C*/VSX130181B376 397 414 140 153 163 Entering Indoor Dry Bulb Temperature11.7 11.6 12.8 13.0 13.222.2 Cooling Performance Data GSX130241B*/VSX130241A363 Cooling Performance Data GSX130301B*/VSX130301A 136 114 122 10.4 10.8381 410 432 451 478 49832.8 Cooling Performance Data GSX130361B*/VSX130361A373 38.0 Cooling Performance Data GSX130421B*/VSX130421A14.7 41.0142 Cooling Performance Data GSX130481B*/VSX130481A 147 16.2Cooling Performance Data GSX130601B*/VSX130601B 454 479 500 145 158 168 Entering Indoor Dry Bulb Temperature20.2 20.9 21.7 21.4 22.2 23.0GSX130363A KW =Total system powerCooling Operation 346 GSX130483A380 GSX130484A Cooling Performance Data 52.8 GSX130603A399 391 GSX130604A430 Performance Test Performance DataDiagrams WiringGSX13018-601B*/GSX130181C* VSX13018-601A Wiring DiagramsVSX130181B GSX13036-603,4A