PRODUCT DESIGN

GSX/VSX13 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications.

Select GSX13 models are available in 208/230 and 460 volt 3-phase applications. These models use R-410A refrigerant.

The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet.

These units are designed for free air discharge, so no addi- tional resistance like duct work shall be attached.

The suction and liquid line connections on present models are of the sweat type for field piping with refrigerant type cop- per. Front seating valves are factory installed to accept the field run copper. The total refrigerant charge for a normal in- stallation is factory installed in the condensing unit. GSX/ VSX units are charged for the matching evaporator coil and a 15 foot refrigerant line set.

Systems should be properly sized by heat gain and loss calculations made according to methods of the Air Condi- tioning Contractors Association (ACCA) or equivalent. It is the contractors responsibility to ensure the system has ad- equate capacity to heat or cool the conditioned space.

GSX/VSX models use the Copeland Scroll "Ultratech" Se- ries compressors which are specifically designed for R-410A refrigerant. There are a number of design characteristics which are different from the traditional reciprocating and/or scroll compressors.

"Ultratech" Series scroll compressors will not have a dis- charge thermostat, some of the early model scroll compres- sors required discharge thermostats.

Due to their design Scroll compressors are inherently more tolerant of small quantities of liquid refrigerant.

NOTE: Even though the compressor section of a Scroll com-

WARNING

To avoid possible injury, explosion or death, practice safe handling of refrigerants.

Special consideration must be given to location of the con- densing unit(s) in regard to structures, obstructions, other units, and any/all other factors that may interfere with air circulation. Where possible, the top of the unit should be completely unobstructed; however, if vertical conditions re- quire placement beneath an obstruction there should be a minimum of 60 inches between the top of the unit and the obstruction(s). The specified dimensions meet require- ments for air circulation only. Consult all appropriate regula- tory codes prior to determining final clearances.

Another important consideration in selecting a location for the unit(s) is the angle to obstructions. Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clear- ance. Corner installations are strongly discouraged.

DO NOT locate the unit:

Directly under a vent termination for a gas appliance.

Within 3 feet of a clothes dryer vent.

Where the refreezing of defrost water would create a hazard.

Where water may rise into the unit.

NOT

B

OK!

RECOMMENDED

pressor is more tolerant of liquid refrigerant, continued floodback or flooded start conditions may wash oil from the bearing surfaces causing premature bearing failure.

"Ultratech" Series scroll compressors use "POE" or polyolester oil which is NOT compatible with mineral oil based lubricants like 3GS. "POE" oil must be used if additional oil is required.

A

B

AA

C

AA

B

B

 

 

AA

 

C

 

OK!

AA

AA

OK!

OK!OK!

 

 

Operating pressures and amp draws may differ from stan- dard reciprocating and/or scroll compressors. This informa- tion may be found in the "Cooling Performance Data" sec- tion.

IMPORTANT NOTE: Because of the potential damage to compressors, do not allow suction pressure at service valve to drop below 20 PSIG when pumping unit system down for repair. Outdoor section, depending on line set length and amount of charge in system, may not be able to hold the entire system charge.

4

A AAAA

C C

Minimum Airflow Clearance

Model Type

A

B

C

AA

Residential

10"

10"

18"

20"

Light Commercial

12"

12"

18"

24"

Image 4
Contents Technical Manual 024 Product IdentificationGSX130363A Product Design AA AADimensions 208/230-60-1 Condensing Unit SpecificationsOr 3/4 GSX13018-601B GSX130181C GSX13036-603,4 VSX130181A VSX130241A VSX130301A VSX130361A VSX130421A VSX130481AVSX13018 & 601B Cooling Performance Data GSX130181AModel GSX130181AA / CA*F1824*6** / ZP16K5E-PFV Bulb Temperature105 115 Entering Indoor Wet Bulb Temperature 22.0359 21.3GSX130241A 105 115 Entering Indoor Wet Bulb TemperatureModel GSX130241AA / CA*F1824*6** / ZP20K5-PFV Airflow 27.1379 132GSX130301A Model GSX130301AA / CA*F3030*6** / ZP24K5E-PFV28.4 400GSX130361A Model GSX130361AA / CA*F4860*6** / ZP31K5E-PFV 35.011.9 39038.2 13.3372 133GSX130421A Model GSX130421AA / CA*F4860*6** / ZP34K5-PFV40.0 13.843.9 15.1136 42.6GSX130481A Model GSX13048-1AA / CA*F4860*6** / ZP39K5E-PFV46.0 15.7GSX130601A Model GSX130601AA / CA*F4860*6**/ ZP51K5E-PFV Cooling Performance Data GSX130181B*/VSX130181A 18.0 Cooling Performance Data GSX130181C*/VSX130181B 16.9140 153 163 Entering Indoor Dry Bulb Temperature 11.7 11.612.8 13.0 13.2 376 397 414Cooling Performance Data GSX130241B*/VSX130241A 22.2363 Cooling Performance Data GSX130301B*/VSX130301A 10.4 10.8 381 410 432 451478 498 136 114 122Cooling Performance Data GSX130361B*/VSX130361A 32.8373 Cooling Performance Data GSX130421B*/VSX130421A 38.014.7 41.0142 Cooling Performance Data GSX130481B*/VSX130481A 16.2 147Cooling Performance Data GSX130601B*/VSX130601B 145 158 168 Entering Indoor Dry Bulb Temperature 20.2 20.9 21.721.4 22.2 23.0 454 479 500KW =Total system power GSX130363ACooling Operation GSX130483A 346380 GSX130484A Cooling Performance Data GSX130603A 52.8399 GSX130604A 391430 Performance Data Performance TestWiring DiagramsWiring Diagrams GSX13018-601B*/GSX130181C* VSX13018-601AVSX130181B GSX13036-603,4A