Goodman Mfg Goodman GSX Air Conditioners: Specifications for Optimal Cooling Efficiency

Page 9

CONDENSING UNIT SPECIFICATIONS

GSX130[36-60][3,4]* *

 

GSX130363A*

GSX130483A*

GSX130484A*

GSX130603A*

GSX130604A*

 

 

 

 

 

 

 

 

Cooling Capacity, BTUH

36,000

48,000

48,000

60,000

60,000

 

Decibels

74

76

76

77

77

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

R.L. Amps

10.40

13.1

6.1

15.9

7.1

 

L.R. Amps

73.0

83.1

41.0

110.0

52.0

 

Type

Scroll

Scroll

Scroll

Scroll

Scroll

 

Condenser Fan Motor

 

 

 

 

 

 

Horsepower

1/6

1/4

1/4

1/4

1/4

 

F.L. Amps

1.10

1.50

0.80

1.50

0.80

 

 

 

 

 

 

 

 

Refrigerant System

 

 

 

 

 

 

Liquid Line, Inches O.D.*

3/8"

3/8"

3/8"

3/8"

3/8"

 

Suction Line, Inches O.D.*

7/8"

1 1/8"

1 1/8"

1 1/8"

1 1/8"

 

Liquid Valve Connection, Inches O.D.*

3/8"

3/8"

3/8"

3/8"

3/8"

 

Suction Valve Connection, Inches O.D.* 3

3/4" 3

7/8" 4

7/8" 4

7/8" 4

7/8" 4

 

Refrigerant Charge

92.0

128.0

128.0

125.0

125.0

 

Piston Size

0.068

0.080

0.080

0.086

0.086

 

Power Supply

208/230-60-3

208/230-60-3

460-60-3

208/230-60-3

460-60-3

 

Minimum Circuit Ampacity(1)

14.1

17.9

8.4

21.4

9.7

 

Maximum Overcurrent Device(2)

20

30

15

35

15

 

Min / Max Volts

197 / 253

197 / 253

414 / 506

197 / 253

414 / 506

 

 

 

 

 

 

 

 

Electrical Conduit Size

 

 

 

 

 

 

Power Supply(Inches)

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

 

Approximate Shipping Weight

196

190

189

197

196

 

(1)Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

(2)Maximum Overcurrent Protection Device: MUST use time delay fuses or HACR-type Circuit Breakers of the same size as noted.

(3)Installer must supply a 3/4" to 7/8" adapter for suction line connections.

(4)Installer must supply a 7/8" to 1 1/8" adapter for suction line connections.

NOTES:

*Always check the S&R plate for electrical data on the unit being installed.

*Installer will need to supply 7/8" to 1 1/8" adapters for suction line connections.

*Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.

*Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT NOT THE INDOOR COIL.

NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.

9

Image 9
Contents Technical Manual Product Identification 024GSX130363A AA AA Product DesignDimensions Condensing Unit Specifications 208/230-60-1Or 3/4 GSX13018-601B GSX130181C GSX13036-603,4 VSX130361A VSX130421A VSX130481A VSX130181A VSX130241A VSX130301AVSX13018 & 601B GSX130181A Cooling Performance DataBulb Temperature Model GSX130181AA / CA*F1824*6** / ZP16K5E-PFV105 115 22.0 Entering Indoor Wet Bulb Temperature359 21.3105 115 Entering Indoor Wet Bulb Temperature GSX130241AModel GSX130241AA / CA*F1824*6** / ZP20K5-PFV 27.1 Airflow379 132Model GSX130301AA / CA*F3030*6** / ZP24K5E-PFV GSX130301A28.4 400GSX130361A 35.0 Model GSX130361AA / CA*F4860*6** / ZP31K5E-PFV11.9 39013.3 38.2372 133Model GSX130421AA / CA*F4860*6** / ZP34K5-PFV GSX130421A40.0 13.815.1 43.9136 42.6Model GSX13048-1AA / CA*F4860*6** / ZP39K5E-PFV GSX130481A46.0 15.7GSX130601A Model GSX130601AA / CA*F4860*6**/ ZP51K5E-PFV Cooling Performance Data GSX130181B*/VSX130181A 18.0 16.9 Cooling Performance Data GSX130181C*/VSX130181B11.7 11.6 140 153 163 Entering Indoor Dry Bulb Temperature12.8 13.0 13.2 376 397 41422.2 Cooling Performance Data GSX130241B*/VSX130241A363 Cooling Performance Data GSX130301B*/VSX130301A 381 410 432 451 10.4 10.8478 498 136 114 12232.8 Cooling Performance Data GSX130361B*/VSX130361A373 38.0 Cooling Performance Data GSX130421B*/VSX130421A41.0 14.7142 Cooling Performance Data GSX130481B*/VSX130481A 147 16.2Cooling Performance Data GSX130601B*/VSX130601B 20.2 20.9 21.7 145 158 168 Entering Indoor Dry Bulb Temperature21.4 22.2 23.0 454 479 500GSX130363A KW =Total system powerCooling Operation 346 GSX130483A380 GSX130484A Cooling Performance Data 52.8 GSX130603A399 391 GSX130604A430 Performance Test Performance DataDiagrams WiringGSX13018-601B*/GSX130181C* VSX13018-601A Wiring DiagramsVSX130181B GSX13036-603,4A