Goodmans Package Heat Pump Units, GPH 13 H service manual 28.2, 11.2, 412, 151

Page 16

16

MODEL: GPH1330H41**

 

 

 

 

EXPANDED PERFORMANCE DATA

 

 

 

COOLING OPERATION

 

 

 

 

 

 

 

 

 

 

 

Design Subcooling, 12±3 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 8±3 °F @ the compressor suction access fitting connection.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

 

 

 

75

 

 

 

85

 

 

 

95

 

 

105

 

 

 

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering Indoor Wet

Bulb Temperature

 

 

 

 

 

 

 

 

 

 

 

IDB*

 

Airflow

 

59

63

 

67

71

59

63

 

67

71

59

63

 

67

71

59

63

 

67

71

59

63

67

71

59

 

63

67

71

 

 

 

 

MBh

28.6

29.2

 

31.2

33.4

27.9

28.5

 

30.5

32.6

27.3

27.9

 

29.8

31.8

26.6

27.2

 

29.0

31.1

25.3

25.8

27.6

29.5

23.4

 

23.9

25.6

27.3

 

 

 

 

S/T

1.00

0.93

0.76

0.57

1.00

0.97

0.79

0.59

1.00

1.00

0.81

0.60

1.00

1.00

0.83

0.62

1.00

1.00

0.86

0.65

1.00

 

1.00

0.87

0.65

 

 

 

1180

Delta T

22

21

18

15

22

21

19

15

21

22

19

15

21

21

19

15

20

20

19

15

18

 

19

17

14

 

 

 

KW

2.06

2.10

2.17

2.23

2.21

2.26

2.33

2.40

2.35

2.40

2.47

2.55

2.47

2.52

2.60

2.68

2.57

2.62

2.71

2.80

2.66

 

2.71

2.80

2.89

 

 

 

 

AMPS

8.8

9.0

9.2

9.5

9.4

9.6

9.9

10.2

10.1

10.3

10.6

11.0

10.7

10.9

11.3

11.6

11.3

11.6

11.9

12.3

11.9

 

12.2

12.5

13.0

 

 

 

 

HI PR

252

271

286

298

282

304

321

335

321

346

365

381

366

394

416

433

411

443

468

488

455

 

489

517

539

 

 

 

 

LO PR

114

121

132

141

120

128

140

149

125

133

145

155

132

140

153

163

138

147

160

171

143

 

152

166

176

 

 

 

 

MBh

27.8

28.4

30.3

32.4

27.1

27.7

29.6

31.7

26.5

27.1

28.9

30.9

25.8

26.4

 

28.2

30.1

24.5

25.1

26.8

28.6

22.7

 

23.2

24.8

26.5

 

 

 

 

S/T

0.95

0.89

0.72

0.54

0.98

0.92

0.75

0.56

1.00

0.94

0.77

0.57

1.00

0.97

 

0.79

0.59

1.00

1.00

0.82

0.62

1.00

 

1.00

0.83

0.62

 

80

 

1050

Delta T

23

22

19

15

23

22

19

16

23

22

19

16

23

23

 

20

16

21

22

19

15

20

 

20

18

14

 

 

KW

2.04

2.09

2.15

2.22

2.20

2.24

2.31

2.38

2.33

2.38

2.45

2.53

2.45

2.50

 

2.58

2.66

2.55

2.60

2.69

2.77

2.63

 

2.69

2.78

2.87

 

 

 

 

AMPS

8.7

8.9

9.2

9.4

9.3

9.5

9.8

10.1

10.0

10.2

10.5

10.9

10.6

10.8

 

11.2

11.5

11.2

11.5

11.8

12.2

11.8

 

12.1

12.4

12.9

 

 

 

 

HI PR

249

268

283

295

280

301

318

331

318

342

361

377

362

390

 

412

429

407

438

463

483

450

 

484

511

533

 

 

 

 

LO PR

113

120

131

140

119

127

139

148

124

132

144

153

130

139

 

151

161

136

145

159

169

141

 

150

164

175

 

 

 

 

MBh

25.6

26.2

28.0

29.9

25.0

25.6

27.3

29.2

24.4

25.0

26.7

28.5

23.8

24.4

 

26.0

27.8

22.7

23.1

24.7

26.4

21.0

 

21.4

22.9

24.5

 

 

 

 

S/T

0.91

0.86

0.70

0.52

0.95

0.89

0.72

0.54

0.97

0.91

0.74

0.55

1.00

0.94

0.76

0.57

1.04

0.98

0.79

0.59

1.05

 

0.98

0.80

0.60

 

 

 

 

Delta T

23

22

19

16

24

23

20

16

24

23

20

16

24

23

20

16

24

23

20

16

22

 

21

18

15

 

 

 

920

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

2.00

2.04

2.10

2.16

2.14

2.19

2.26

2.33

2.27

2.32

2.39

2.47

2.39

2.44

2.52

2.60

2.49

2.54

2.62

2.71

2.57

 

2.62

2.71

2.80

 

 

 

 

AMPS

8.5

8.7

8.9

9.2

9.1

9.3

9.6

9.9

9.8

10.0

10.3

10.6

10.4

10.6

10.9

11.3

10.9

11.2

11.5

11.9

11.5

 

11.8

12.1

12.5

 

 

 

 

HI PR

242

260

275

286

271

292

308

321

308

332

350

366

351

378

399

416

395

425

449

468

437

 

470

496

517

 

 

 

 

LO PR

110

117

127

135

116

123

134

143

120

128

140

149

126

134

147

156

132

141

154

164

137

 

146

159

169

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBh

29.1

29.7

31.1

33.1

28.4

29.0

30.3

32.4

27.7

28.3

29.6

31.6

27.1

27.6

28.9

30.8

25.7

26.2

27.5

29.3

23.8

 

24.3

25.4

27.1

 

 

 

 

S/T

1.00

1.00

0.91

0.74

1.00

1.00

0.94

0.76

1.00

1.00

0.96

0.78

1.00

1.00

0.99

0.81

1.00

1.00

1.00

0.84

1.00

 

1.00

1.00

0.84

 

 

 

1180

Delta T

23

23

22

19

22

23

22

19

22

22

22

19

21

21

22

19

20

20

21

19

19

 

19

20

18

 

 

 

KW

2.08

2.12

2.18

2.25

2.23

2.28

2.35

2.42

2.37

2.42

2.49

2.57

2.49

2.54

2.62

2.71

2.59

2.64

2.73

2.82

2.68

 

2.74

2.82

2.92

 

 

 

 

AMPS

8.9

9.0

9.3

9.6

9.5

9.7

9.9

10.3

10.2

10.4

10.7

11.1

10.8

11.0

11.3

11.7

11.4

11.7

12.0

12.4

12.0

 

12.3

12.6

13.1

 

 

 

 

HI PR

254

273

289

301

285

307

324

338

324

349

369

384

369

398

420

438

416

447

472

493

459

 

494

522

544

 

 

 

 

LO PR

115

123

134

142

122

129

141

151

126

135

147

156

133

141

154

164

139

148

162

172

144

 

153

167

178

 

 

 

 

MBh

28.3

28.8

30.2

32.2

27.6

28.1

29.5

31.4

26.9

27.5

28.8

30.7

26.3

26.8

28.1

29.9

25.0

25.5

26.7

28.4

23.1

 

23.6

24.7

26.3

 

 

 

 

S/T

0.99

0.96

0.86

0.70

1.00

0.99

0.90

0.73

1.00

1.00

0.92

0.75

1.00

1.00

0.95

0.77

1.00

1.00

0.98

0.80

1.00

 

1.00

0.99

0.81

 

85

 

1050

Delta T

25

24

23

20

24

24

23

20

24

24

23

20

23

23

23

20

22

22

23

20

20

 

21

21

19

 

 

KW

2.06

2.10

2.17

2.23

2.21

2.26

2.33

2.40

2.35

2.40

2.47

2.55

2.47

2.52

2.60

2.68

2.57

2.62

2.71

2.80

2.66

 

2.71

2.80

2.89

 

 

 

 

AMPS

8.8

9.0

9.2

9.5

9.4

9.6

9.9

10.2

10.1

10.3

10.6

11.0

10.7

10.9

11.3

11.6

11.3

11.6

11.9

12.3

11.9

 

12.2

12.5

13.0

 

 

 

 

HI PR

252

271

286

298

282

304

321

335

321

346

365

381

366

394

416

433

411

443

468

488

455

 

489

517

539

 

 

 

 

LO PR

114

121

132

141

120

128

140

149

125

133

145

155

132

140

153

163

138

147

160

171

143

 

152

166

176

 

 

 

 

MBh

26.1

26.6

27.8

29.7

25.5

26.0

27.2

29.0

24.9

25.3

26.5

28.3

24.3

24.7

25.9

27.6

23.0

23.5

24.6

26.2

21.3

 

21.8

22.8

24.3

 

 

 

 

S/T

0.96

0.92

0.83

0.68

0.99

0.96

0.86

0.70

1.00

0.98

0.89

0.72

1.00

1.00

0.91

0.74

1.00

1.00

0.95

0.77

1.00

 

1.00

0.96

0.78

 

 

 

920

Delta T

25

25

23

20

25

25

23

20

25

25

24

20

24

25

24

20

23

23

23

20

21

 

22

22

19

 

 

 

KW

2.01

2.05

2.12

2.18

2.16

2.21

2.27

2.35

2.29

2.34

2.41

2.49

2.41

2.46

2.54

2.62

2.51

2.56

2.64

2.73

2.59

 

2.65

2.73

2.82

 

 

 

 

AMPS

8.6

8.8

9.0

9.3

9.2

9.4

9.6

9.9

9.9

10.1

10.4

10.7

10.4

10.7

11.0

11.3

11.0

11.3

11.6

12.0

11.6

 

11.9

12.2

12.6

 

 

 

 

HI PR

244

263

277

289

274

295

311

325

311

335

354

369

355

382

403

420

399

430

454

473

441

 

475

501

523

 

 

 

 

LO PR

111

118

128

137

117

124

136

145

121

129

141

150

128

136

148

158

134

142

155

165

138

 

147

161

171

 

 

* Entering Indoor Dry Bulb Temperature

 

 

NOTE: Shaded area

is AHRI Rating Conditions

 

 

 

KW = Total system power

 

 

 

 

 

 

 

 

High and low pressures are measured at the liquid and suction access fittings.

 

 

 

 

 

 

 

 

 

AMPS: Unit amps (comp.+ evaporator + condenser fan motors)

 

COOLING PERFORMANCE DATA

GPH1330H41**

Image 16
Contents Technical Manual Goodman will not be responsible Product IdentificationFor any injury or property damage Do not connect or use any device Outside Slab Installation Horizontal H Product DesignRooftop Installation Horizontal H Electrical Data *Blower Only, Heat Mode Minimum Circuit MaximumOvercurrent Ampacity Protection ampsProduct Dimensions GPH1324-60H41Package Heat Pump Specifications GPH1324-36H41AB GPH1336H41ACGPH1342H41AB GPH1348-60H41BB Accessories Part Number DescriptionBlower Performance Data GPH1324-60H41Performance Data FormulasCooling Performance Data GPH1324H41105 115 Entering Indoor Wet 138105 115 Entering Indoor Wet Bulb Temperature 24.0GPH1330H41 105 115Airflow 26.128.2 11.2412 151GPH1336H41 32.435.0 149GPH1342H41 37.5Outdoor Ambient Temperature 105 115 40.515.8 392GPH1348H41 42.646.0 GPH1360H41 21.1 57.5388 Package Heat Pump Specifications GPH1342-60H41 Wiring Diagrams GPH1324, 30, 42H41AB / GPH1336H41AC GPH1348H41BBGPH1360H41BB Before Servicing Sources MAY be Property Damage

GPH 13 H, Package Heat Pump Units specifications

Goodmans Package Heat Pump Units, specifically the GPH 13 H model, represent an advanced solution in residential and commercial climate control. Known for their efficiency and reliability, these heat pumps offer a combination of heating and cooling capabilities, making them ideal for year-round comfort.

One of the standout features of the GPH 13 H is its energy efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of 13, it efficiently converts energy into heating and cooling, which can lead to significant savings on utility bills. This efficiency is not only beneficial for homeowners looking to reduce their energy footprint, but it also qualifies for many energy rebate programs.

Durability is another hallmark of the GPH 13 H. Built with robust materials, the unit is designed to withstand various weather conditions, ensuring longevity and reliable performance. Components are treated to resist corrosion, which extends the lifespan of the heat pump and enhances its efficiency.

The GPH 13 H utilizes innovative inverter technology, allowing it to adjust its cooling and heating output according to the space's specific needs. This results in more consistent temperatures and improved indoor comfort. Additionally, the variable-speed compressor operates at different levels, reducing energy consumption while providing effective heating and cooling.

In terms of installation, the GPH 13 H offers versatility. Its compact design facilitates easy placement in various locations, making it suitable for both new construction and retrofitting existing spaces. The unit's all-in-one design simplifies installation by minimizing the need for external ductwork.

Quiet operation is a critical consideration for many homeowners, and Goodmans excels in this area. The GPH 13 H is engineered to minimize noise levels, ensuring a peaceful indoor environment. This feature makes it an excellent choice for residential areas where noise may be a concern.

The unit also features advanced control systems, including programmable thermostats that allow users to set specific temperature schedules. This feature not only enhances user comfort but also contributes to energy savings by preventing unnecessary heating or cooling when spaces are unoccupied.

Overall, Goodmans Package Heat Pump Units, GPH 13 H, combine efficiency, durability, and advanced technology to deliver a reliable climate control solution. With its focus on energy savings, quiet operation, and flexibility in installation, this model stands out as a leading choice for those seeking optimal home comfort. Its thoughtful design and engineering make it a worthwhile investment in both residential and commercial settings.