Bard PA13601-B, PA13421-A, PA13481-B Adjustments, Alarm Output, LOW Ambient Control Wiring

Page 17

HIGH PRESSURE SWITCH AND LOCKOUT SEQUENCE (Standard Feature)

If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay-on- make time has expired. If the high pressure switch opens again in this same operating cycle the unit will go into manual lockout condition and the alarm circuit will energize. Recycling the wall thermostat resets the manual lockout.

LOW PRESSURE SWITCH, BYPASS, AND LOCKOUT SEQUENCE (Standard Feature)

If the low pressure switch opens for more that 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will reenergize after the delay-on-make time delay has expired. If the low pressure switch remains open or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm circuit will energize. Recycling the wall thermostat resets the manual lockout.

ALARM OUTPUT

Alarm terminal is output connection for applications where alarm signal is desired. This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner or heat pump unit model. The lockout features, both soft and manual, are a function of the Compressor Control Module.

ADJUSTMENTS

ADJUSTABLE DELAY-ON-MAKE AND DELAY-ON-BREAK TIMER

The potentiometer is used to select Delay-on-Break time from 30 seconds to 5 minutes. Delay-on-Make (DOM) timing on power-up and after power interruptions is equal to 2 minutes plus 10% of Delay-on-Break (DOB) setting:

0.5 minute

(30 seconds)

DOB

= 123 second DOM

1.0 minute

(60 seconds)

DOB

= 126 second DOM

2.0minute (120 seconds) DOB = 132 second DOM

3.0minute (160 seconds) DOB = 138 second DOM

4.0minute (240 seconds) DOB = 144 second DOM

5.0minute (300 seconds) DOB = 150 second DOM

LOW AMBIENT CONTROL

Optional Low Ambient Control

An optional low ambient control is available for both factory and field installed options. The low ambient control is to be applied to the PA13 Series models when operation below 55°outdoor conditions are anticipated. Without this device, the evaporating pressure would fall off, and the indoor coil would ice over.

The fan cycling control cycles the fan motor on, once the liquid refrigerant pressure reaches 350 psig, and off, once it has dropped to 225 psig. It will continue to cycle between these parameters depending on outdoor temperatures and the load/stage of the system.

This cycling maintains a minimum liquid pressure affecting the minimum suction pressure. This effect insures an evaporating temperature that is slightly above the point of ice formation on the evaporator.

This field installed option is Bard Part #CMA-28. See Figure 7.

FIGURE 7

LOW AMBIENT CONTROL WIRING

Manual

2100-467

Page

17 of 23

Image 17
Contents Bryan, Ohio Bard Manufacturing CompanyContents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsGeneral Instructions Field Installed Heater Packages OptionalShipping Damage GeneralHz Circuit a Electrical SpecificationsHeater Package Volts Model Phase Htr. KW & Capacity Circuit B Optional Field Installed Electric Heater TableDimensions of Units Unit Dimension ChartTypical Installations InstallationLocation GeneralSlab Mounting AT Ground Level Airflow and Service Access ClearancesAS Required Elevated Mounting PlatformAIR Filters Condensate Drain TrapFilter Requirements & Sizes Condensate Drain TrapWiring 24V LOW Voltage Control Circuit Wiring Main PowerTransformer Taps ThermostatsUnit Control Panel LOW Voltage WiringStart UP Safety PracticesTopping OFF System Charge Start UP NotesStart UP and Operation Three Phase Scroll Compressor Start UP InformationSequence of Operation Indoor Blower MotorAlarm Output AdjustmentsAdjustable DELAY-ON-MAKE and DELAY-ON-BREAK Timer LOW Ambient Control WiringService Hints Service and TroubleshootingPressure Service Ports FAN Blade SettingsSuction and Discharge Tube Brazing Brazing DiagramTroubleshooting GE ECM Motors Troubleshooting GE ECM Motors Cont’d On Page 23 in Table Pressure TableReturn Air Pressure 100 105 115 120 125 ModelReturn Air Pressure 100 105 110 115 120 125 Model

PA13601-B, PA13481-A, PA13601-A, PA13481-B, PA13421-A specifications

Bard is a renowned name in the HVAC (Heating, Ventilation, and Air Conditioning) industry, known for its innovative products that ensure comfort and efficiency in various settings. The models PA13421-B, PA13421-A, PA13481-B, PA13601-A, and PA13481-A are prime examples of Bard's commitment to quality and technology, providing reliable performance and advanced features suitable for both commercial and residential applications.

The PA13421-B and PA13421-A are designed for energy efficiency, boasting high SEER (Seasonal Energy Efficiency Ratio) ratings that significantly reduce energy consumption without sacrificing performance. These units utilize a scroll compressor, which is known for its quiet operation and superior reliability. Additionally, they feature advanced microprocessor control systems that allow for precise temperature regulation and can be easily integrated into building management systems.

The PA13481-B and PA13481-A models are equipped with durable, heavy-gauge cabinets that protect the internal components from environmental factors, ensuring longevity and minimal maintenance. These units also incorporate a high-capacity airflow design, which improves indoor air quality by effectively circulating air throughout the space. The implementation of variable-speed blowers further enhances comfort levels by adjusting airflow based on real-time demand.

The PA13601-A model stands out with its versatility, as it can operate effectively in a wide range of climates. Its design includes a robust refrigerant management system that ensures optimal performance even in extreme temperatures, making it a favorite for users in harsher environments. This model also features a comprehensive diagnostic system that alerts users to potential issues before they escalate, facilitating proactive maintenance.

All these models emphasize sustainability, incorporating environmentally friendly refrigerants that comply with international regulations. Bard's dedication to reducing carbon footprints is evident in these units, which not only perform admirably but also contribute to a greener planet.

In summary, the Bard PA13421-B, PA13421-A, PA13481-B, PA13601-A, and PA13481-A models exemplify cutting-edge technology and superior engineering in the HVAC sector. With their energy-efficient designs, robust construction, and advanced control systems, these HVAC solutions provide reliable comfort for users while being mindful of environmental impact.