Bard PA13421-A, PA13481-B Condensate Drain Trap, AIR Filters, Filter Requirements & Sizes

Page 12

5.OTHER INSTALLATIONS – Many other installations are possible with the packaged air conditioner. No matter what the installation, always consider the following facts:

A.Insure that the discharge air is not obstructed in any way so as to cause operation difficulties.

B.The indoor coil drain pan is equipped with a coupling that must be piped through a condensate drain trap to a suitable drain.

C.Always mount the unit is such a position that it may be easily reached for servicing and maintenance.

D.Insure that the unit is clear so that proper air flow over the outdoor coil will be maintained.

If this unit is operated in cooling below a 55° outdoor ambient temperature, the installation of low ambient controls (CMA-28) to unit is required.

CONDENSATE DRAIN TRAP

It is very important to provide a trap in the condensate drain line to allow a positive liquid seal in the line and assure correct drainage from the coil condensate pan.

Install condensate drain trap shown in Figure 8. Use drain connection size or larger. Do not operate unit without trap. Unit must be level or slightly inclined toward drain. With a trap installed on a unit located in an unconditioned area, water in the trap may freeze. It is recommended that the trap material be of a type that will allow for expansion of water when it freezes.

AIR FILTERS

Air filters for the return air side of the system are not provided as part of these models, and must be field supplied and installed as part of the final installation.

Prior thought should be given to return air location and placement of the air filter(s). The air filter(s) must be of adequate size and readily accessible to the operator of the equipment. Filters must be adequate in size and properly maintained for proper operation. If this is not done, excessive energy use, poor performance, and multiple service problems will result. It is impossible to oversize air filters. Generous sizing will result in cleaner air and coils as well as lower operating costs and extend the time between required changes. Table 5 shows minimum filter areas and recommended filter sizes. Actual filter sizes can vary with the installation due to single or multiple returns utilizing a filter/grille arrangement or being placed immediately ahead of the indoor coil face in the return air duct.

TABLE 5

FILTER REQUIREMENTS & SIZES

Model No.

Minimum Filter Area

Recommended

Size

 

 

 

 

 

PA1324

462 Square Inches

 

PA1330

15 x 30-5/8 x 1

(3.21 Square Feet)

PA1336

 

 

 

 

 

 

PA1342

608 Square Inches

 

PA1348

(2) 16 x 20 x 1

(4.62 Square Feet)

PA1360

 

 

 

 

 

 

NOTE: If roof hood accessory is to be used, information on air filters may be found under that heading in this manual. Air filters are supplied as part of that package.

FIGURE 5

CONDENSATE DRAIN TRAP

MIS-136

Manual

2100-467

Page

12 of 23

Image 12
Contents Bard Manufacturing Company Bryan, OhioContents Getting Other Information and Publications For More INFORMATION, Contact These PublishersField Installed Heater Packages Optional General InstructionsShipping Damage GeneralElectrical Specifications Hz Circuit aHeater Package Volts Model Phase Optional Field Installed Electric Heater Table Htr. KW & Capacity Circuit BUnit Dimension Chart Dimensions of Units Installation Typical Installations Location GeneralAirflow and Service Access Clearances Slab Mounting AT Ground LevelElevated Mounting Platform AS RequiredCondensate Drain Trap AIR FiltersFilter Requirements & Sizes Condensate Drain TrapWiring Main Power Wiring 24V LOW Voltage Control CircuitTransformer Taps ThermostatsLOW Voltage Wiring Unit Control PanelSafety Practices Start UPTopping OFF System Charge Start UP NotesThree Phase Scroll Compressor Start UP Information Start UP and OperationSequence of Operation Indoor Blower MotorAdjustments Alarm OutputAdjustable DELAY-ON-MAKE and DELAY-ON-BREAK Timer LOW Ambient Control WiringService and Troubleshooting Service HintsPressure Service Ports FAN Blade SettingsBrazing Diagram Suction and Discharge Tube BrazingTroubleshooting GE ECM Motors Troubleshooting GE ECM Motors Cont’d Pressure Table On Page 23 in TableReturn Air Pressure 100 105 115 120 125 ModelReturn Air Pressure 100 105 110 115 120 125 Model