Bard PA13481-B, PA13421-A, PA13481-A, PA13601-A Suction and Discharge Tube Brazing, Brazing Diagram

Page 19

SUCTION AND DISCHARGE TUBE BRAZING

Compliant Scroll compressors have copper plated steel suction and discharge tubes. These tubes are far more rugged and less prone to leaks than copper tubes used on other compressors. Due to different thermal properties of steel and copper, brazing procedures may have to be changed from those commonly used.

To disconnect: heat joint Areas 2 and 3 slowly and uniformly until braze material softens and the tube can be pulled out of suction fitting. (See Figure 9.)

To connect:

Recommended brazing materials: silfos with minimum 5% silver or silver braze material with flux.

Reinsert tube into fitting.

Heat tube uniformly in Area 1 moving slowly to Area 2. When joint reaches brazing temperature, apply brazing material. (See Figure 9)

Heat joint uniformly around the circumference to flow braze material completely around the joint.

Slowly move torch into Area 3 to draw braze material into joint. (See Figure 9.)

Do not overheat joint.

FIGURE 9

BRAZING DIAGRAM

MIS-1179

Manual

2100-467

Page

19 of 23

Image 19
Contents Bryan, Ohio Bard Manufacturing CompanyContents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsGeneral Field Installed Heater Packages OptionalGeneral Instructions Shipping DamageHz Circuit a Electrical SpecificationsHeater Package Volts Model Phase Htr. KW & Capacity Circuit B Optional Field Installed Electric Heater TableDimensions of Units Unit Dimension ChartGeneral InstallationTypical Installations LocationSlab Mounting AT Ground Level Airflow and Service Access ClearancesAS Required Elevated Mounting PlatformCondensate Drain Trap Condensate Drain TrapAIR Filters Filter Requirements & SizesThermostats Wiring Main PowerWiring 24V LOW Voltage Control Circuit Transformer TapsUnit Control Panel LOW Voltage WiringStart UP Notes Safety PracticesStart UP Topping OFF System Charge Indoor Blower Motor Three Phase Scroll Compressor Start UP Information Start UP and Operation Sequence of OperationLOW Ambient Control Wiring AdjustmentsAlarm Output Adjustable DELAY-ON-MAKE and DELAY-ON-BREAK TimerFAN Blade Settings Service and TroubleshootingService Hints Pressure Service PortsSuction and Discharge Tube Brazing Brazing DiagramTroubleshooting GE ECM Motors Troubleshooting GE ECM Motors Cont’d 115 120 125 Model Pressure TableOn Page 23 in Table Return Air Pressure 100 105Return Air Pressure 100 105 110 115 120 125 Model